Field Controls MPL-B, WML-C manual Mode Action System Response, Heat

Page 25

Table C-1: ELECTRONIC FAN TIMER BOARD (EFT) DETAILED SEQUENCE OF OPERATION

Mode

 

 

Action

 

 

 

 

System Response

 

 

 

 

 

 

 

a. EFT closes oil primary control T - T connections).

 

Thermostat calls for heat. ("W"

b. Ignition system and R7184 oil primary control start the furnace. Oil flows as long as

 

 

the oil primary control senses flame.

 

terminal is energized).

 

 

 

 

 

 

c.

Burner motor is energized and heat "fan on" delay timing begins. When timing is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

complete, the circulator fan is energized at heat speed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a. R7184 oil primary control is de-energized, terminating the burner cycle.

 

Thermostat ends call for heat.

b. Heat "fan off" delay timing begins. Length of delay depends on EFT dipswitch

 

 

settings. When timing is complete, the circulator fan is de-energized.

 

("W" terminal is de-energized).

 

HEAT

c.

EFT returns to standby mode, (Oil primary control and circulator fan are off, unless

 

 

 

 

 

 

 

 

 

 

 

 

 

 

continuous fan operation is selected at the thermostat).

 

 

 

 

 

 

 

a. Oil primary control locks out within lockout timing, (30 seconds).

 

Burner fails to light.

 

 

b.

Burner motor is de-energized. (Even though thermostat is still calling for heat).

 

 

 

c.

If circulator fan has started, it continues through the selected heat “fan off” delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

period.

 

 

 

 

 

 

 

 

 

 

 

Established flame fails.

 

a.

 

Burner motor is de-energized and oil primary control goes into recycle mode.

 

 

b.

 

If the selected heat “fan off” delay timing is longer than the recycle delay

 

 

 

 

 

 

 

 

timing, the circulator fan continues to run through the next trial for ignition.

 

Thermostat

begins

call

for

a. Cooling contactor is energized immediately.

 

cool. (G and Y terminals are

 

b. Circulator fan is energized at cool speed.

COOL

energized).

 

 

 

 

 

 

 

 

 

 

 

Thermostat ends call for cool.

a. Cooling contactor is de-energized immediately.

 

 

(G and Y

terminals

are

de-

 

b.

Circulator fan turns off immediately.

 

energized).

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat begins call for fan.

a. Circulator fan is energized immediately at cooling speed.

 

(G terminal is energized).

 

FAN

 

 

 

 

Thermostat

ends call

for fan.

a. Circulator fan is de-energized immediately.

 

 

(G terminal is de-energized).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a. Oil primary control shuts off burner.

 

 

 

 

 

 

 

b. Circulator fan is energized immediately at heat speed.

 

Limit switch string opens.

 

c.

EFT opens oil primary control T - T connections. Circulating fan runs as long as

 

 

 

limit string stays open.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d. If

there is a call for cooling or fan, the circulating fan switches from heating to

 

 

 

 

 

 

 

 

cooling speed.

LIMIT

Limit

switch

string

closes

a. EFT begins heat “fan off” delay sequence.

 

b. Circulating fan turns off after the selected heat “fan off” timing.

 

(with existing call for heat).

c. EFT re-closes oil primary control T - T connections.

 

 

 

 

 

 

 

d. Oil primary control is energized, initiating burner light off.

 

 

 

 

 

 

 

 

 

 

 

Limit

switch

string

closes

a.

 

Circulator fan turns off when heat “fan off” delay time is complete.

 

b.

 

Normal operation resumes; EFT control is in standby mode awaiting next

 

(without existing call for heat).

 

 

 

thermostat command.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

Continuous

circulating fan

is

a. Circulating fan is energized when there is no call for heat, cool, or fan.

b. If fan operation is required by a call for heat, cool, or fan, the EFT switches off the

connected.

 

 

 

 

 

 

 

 

 

 

continuous fan speed tap before energizing the other fan speed.

 

 

 

 

 

 

 

 

EAC

Electronic

Air

Cleaner

is

 

Electronic air cleaner (EAC) connections are energized when the heat or cool

 

speed of the circulator fan is energized. EAC connections are not energized when

connected.

 

 

 

 

 

 

 

 

 

 

 

the optional continuous fan terminal is energized.

 

 

 

 

 

 

 

 

HUM

Humidity control is connected.

 

Humidifier connections are energized when the oil burner motor is energized.

 

 

 

 

 

 

 

 

 

 

25

30318 R4 9/9/2005

Image 25
Contents WML-C and MPL-B Table of Contents Introduction DOWN-FLOW InstallationHeat Loss Location of UnitAIR Conditioning Suspended InstallationChimney Venting Combustion AIRCommon Chimney Problems Optional Side Wall Venting Piping InstallationOIL Tank Electrical ConnectionsHoneywell ST9103 Dip Switch Blower Off Delay Position Time FAN Timer Board and Limit ControlDip Switch Blower Delay Position Times Off Seconds Minutes Circulating AIR BlowerOIL Burner HumidifierChecking Over-Fire Draft Furnace Installation SET- UPRoutine Maintenance By Home Owner Maintenance and ServiceAnnual Service By Contractor Before Lighting Operating InstructionsTo Light Unit To Shut Down UnitAF76YB Appendix A- WML-C and MPL-B Burner SET UPBurner Electrodes OIL Burner AIR AdjustmentStart UP CFM PowerSpeed Model Size Weight55-1/4 19 x 18 x 20 x 20 xAppendix B Wiring Diagrams Beckett Afii Burner Wiring Diagram Riello 40F3 and F5 Burner Wiring Diagram Riello 40BF3 Burner Wiring Diagram Operation of OIL Burner Thermostat calls for heat 30318 R4 9/9/2005 Operation Returns to Idle State Recycle Timer StartsHeat Mode Action System ResponseTroubleshooting R7184 LED Diagnostic LightElectrical Shock Hazard Corrective Action Table C-3 R7184 TroubleshootingRemount control onto burner housing. Go to step Problem Possible Cause Remedy Table C4 System and General TroubleshootingTiming Final Check OUT Parts Listing Counterflow Horizontal Model WML C Parts Listing Vestibule KIT WML C 30318 R4 9/9/2005 Parts Listing Counterflow Horizontal Model MPL Flame Retention Head MPL 30318 R4 9/9/2005 HOMEOWNER’S Reference Table If Different from Installation ContractorFuel Supplier 30318 R4 9/9/2005 Tel 716 Fax 716

MPL-B, WML-C specifications

Field Controls, a leader in the HVAC industry, offers innovative solutions for air quality and equipment efficiency. Among their range of products, the WML-C and MPL-B series stand out for their remarkable features and advanced technologies, catering to the unique needs of both residential and commercial applications.

The WML-C series is designed for optimal ventilation and air quality management. It integrates seamlessly with existing HVAC systems, providing crucial airflow control and ensuring that indoor environments maintain optimal levels of fresh air. One of its key features is the variable speed fan technology, which adjusts according to the desired airflow rate, thereby enhancing energy efficiency. This not only reduces operational costs but also contributes to a more sustainable environment.

The MPL-B series, on the other hand, focuses on purification and filtration. Equipped with advanced media filters, it effectively captures airborne particles, allergens, and pollutants, which is essential for maintaining clean indoor air. The MPL-B series utilizes a multi-stage filtration system that includes HEPA filters, ensuring that the air circulated within spaces meets high standards for cleanliness and safety.

Both the WML-C and MPL-B models utilize smart technology for enhanced control and monitoring. With integrated sensors, users can receive real-time data on air quality, humidity levels, and system performance, allowing for proactive management and maintenance. Additionally, they are compatible with various building management systems, enabling integration into larger infrastructure for comprehensive environmental control.

Durability and reliability are paramount in the design of these units. Built from high-quality materials, both the WML-C and MPL-B are engineered to withstand rigorous usage and varying environmental conditions. Their compact designs allow for flexible installation options, making them suitable for a wide range of settings.

In summary, Field Controls’ WML-C and MPL-B series offer cutting-edge solutions for air quality and HVAC efficiency. With innovative features such as variable speed technology, multi-stage filtration, and smart monitoring capabilities, these systems are ideal for enhancing indoor environments while maintaining energy efficiency and sustainability. They not only meet but exceed the expectations of modern HVAC requirements, making them a valuable investment for any property owner.