Field Controls MPL-B, WML-C manual Combustion AIR, Chimney Venting

Page 5

through a refrigeration unit unless the unit is specifically approved for such service.

Generally, a six-inch clearance between the air conditioning evaporator coil and the heat exchanger will provide adequate airflow through the evaporator coil.

The blower speed must be checked and adjusted to compensate for the pressure drop caused by the evaporator coil. Refer to Appendix B for recommended wiring and electrical connections of the air conditioning controls.

COMBUSTION AIR

When a furnace is installed in the full basement of a typical frame or brick house, infiltration is normally adequate to provide air for combustion and draft operation. If the furnace is installed in a closet or utility room, two (2) ventilation openings must be provided connecting to a well ventilated space (full basement, living room or other room opening thereto, but not a bedroom or bathroom). One opening shall be located 6" from the top and bottom of the enclosure at the front of the furnace. For furnaces located in buildings of unusually tight construction, such as those with high quality weather stripping, caulking, windows and doors, or storm sashed windows, or where basement windows are well sealed, a permanent opening communicating with a well ventilated attic or with the outdoors shall be provided, using a duct if necessary. Size all of the openings and associated ductwork by the standards provided in the latest Oil Installation Code editions; NFPA 31 in the United States, CAN/CSA B139 in Canada. Take all fuel burning appliances in the area into consideration when calculating combustion and ventilation air requirements.

The Model CAS-2B-90E Furnace Boot manufactured by Field Controls, Inc. may be used with the furnace to obtain combustion air from outdoors. Use of this device does not alter the need for ventilation air; however, it does provide a good source of combustion air and is connected to the oil burner.

CHIMNEY VENTING

The chimney must be sized correctly and be in good repair. If the chimney is oversized, there is a high risk of the flue gases condensing resulting in damage to the chimney and other venting parts. This problem may be corrected by the use of an appropriately sized chimney liner.

If the chimney serves the WML-C furnace only, the vent should be sized at 5-inch minimum. The MPL-B should be 6-inch minimum. The data provided in Table 3 is based on dedicated venting. If the furnace is to be co-vented with other appliances, refer to NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances, NFPA 31, Standard for the Installation of Oil Burning Equipment or CAN/CSA B139, Installation Code For Oil Burning Equipment for correct sizing information.

NOTE: This furnace is approved for use with L-Vent.

NOTE: Maximum temperature for L- Vent is 575°F (300°C).

IMPORTANT: The chimney must be capable of providing sufficient draft at all times for the safe removal of the products of combustion.

The chimney should be tested under “winter” conditions; doors and windows closed, all other fossil fuel burning appliances on, clothes dryer on, bathroom fans on, etc. If the chimney cannot overcome the competition for air, it will be necessary to access the reason for it, and take corrective action. If the chimney is found to be sized correctly and in good repair, it will probably be necessary to re-evaluate the availability of combustion and ventilation air, and take corrective action.

The flue pipe should be as short as possible with horizontal pipes sloping upward toward the chimney at a rate of one-quarter inch to the foot. The flue pipe should not be smaller in cross sectional area than the flue collar on the furnace. The flue pipe should connect to the chimney such that the flue pipe extends into, and terminates flush with the inside surface of the chimney liner. Seal the joint between the pipe and the lining. The chimney outlet should be at least two feet above the highest point of a peaked roof. All unused chimney openings should be closed. Chimneys must conform to local, provincial or state codes, or in the absence of local regulations, to the requirements of the National Building Code.

See Figure 2 and Table 2 for common chimney problems and their remedies.

THE FURNACE MUST BE CONNECTED TO A FLUE HAVING SUFFICIENT DRAFT AT ALL TIMES TO ENSURE SAFE AND PROPER OPERATION OF THE APPLIANCE.

The flue pipe must not be routed through concealed space, because it must be visually checked for signs of deterioration during the annual inspection and servicing. The flue pipe must not pass through any floor or ceiling, but may pass through a wall where suitable fire protection provisions have been installed. In the United States, refer to the latest edition of NFPA 31 for regulations governing the installation of oil burning equipment. In Canada, refer to the latest edition of CAN/CSA B139 for rules governing the installation of oil burning equipment.

NOTE: THE RECOMMENDED FLUE DRAFT PRESSURE IS -0.02 IN. W.C.

(AS MEASURED UPSTREAM OF THE BAROMETRIC DRAFT REGULATOR). SHOWN IN FIGURE 1.

DRAFT REGULATOR CONTROL

This device is used in conjunction with conventional chimney venting. This control (or draft regulator) automatically maintains a constant negative pressure in the furnace to obtain maximum efficiency. It ensures that proper pressures are not exceeded. If the chimney does not develop sufficient draft, the draft control cannot function properly. The draft regulator, must be installed within the same room or enclosure as the furnace, and should not interfere with the combustion air supplied to the burner. The control should be located a minimum of 3 flue pipe diameters from the furnace breeching and installed in accordance to the instructions supplied with the regulator.

5

30318 R4 9/9/2005

Image 5
Contents WML-C and MPL-B Table of Contents Introduction DOWN-FLOW InstallationHeat Loss Location of UnitAIR Conditioning Suspended InstallationChimney Venting Combustion AIRCommon Chimney Problems Optional Side Wall Venting Piping InstallationOIL Tank Electrical ConnectionsHoneywell ST9103 Dip Switch Blower Off Delay Position Time FAN Timer Board and Limit ControlDip Switch Blower Delay Position Times Off Seconds Minutes Circulating AIR BlowerOIL Burner HumidifierChecking Over-Fire Draft Furnace Installation SET- UPAnnual Service By Contractor Maintenance and ServiceRoutine Maintenance By Home Owner Before Lighting Operating InstructionsTo Light Unit To Shut Down UnitAF76YB Appendix A- WML-C and MPL-B Burner SET UPStart UP OIL Burner AIR AdjustmentBurner Electrodes Speed PowerCFM Model Size Weight55-1/4 19 x 18 x 20 x 20 xAppendix B Wiring Diagrams Beckett Afii Burner Wiring Diagram Riello 40F3 and F5 Burner Wiring Diagram Riello 40BF3 Burner Wiring Diagram Operation of OIL Burner Thermostat calls for heat 30318 R4 9/9/2005 Operation Returns to Idle State Recycle Timer StartsHeat Mode Action System ResponseElectrical Shock Hazard R7184 LED Diagnostic LightTroubleshooting Corrective Action Table C-3 R7184 TroubleshootingRemount control onto burner housing. Go to step Problem Possible Cause Remedy Table C4 System and General TroubleshootingTiming Final Check OUT Parts Listing Counterflow Horizontal Model WML C Parts Listing Vestibule KIT WML C 30318 R4 9/9/2005 Parts Listing Counterflow Horizontal Model MPL Flame Retention Head MPL 30318 R4 9/9/2005 Fuel Supplier If Different from Installation ContractorHOMEOWNER’S Reference Table 30318 R4 9/9/2005 Tel 716 Fax 716

MPL-B, WML-C specifications

Field Controls, a leader in the HVAC industry, offers innovative solutions for air quality and equipment efficiency. Among their range of products, the WML-C and MPL-B series stand out for their remarkable features and advanced technologies, catering to the unique needs of both residential and commercial applications.

The WML-C series is designed for optimal ventilation and air quality management. It integrates seamlessly with existing HVAC systems, providing crucial airflow control and ensuring that indoor environments maintain optimal levels of fresh air. One of its key features is the variable speed fan technology, which adjusts according to the desired airflow rate, thereby enhancing energy efficiency. This not only reduces operational costs but also contributes to a more sustainable environment.

The MPL-B series, on the other hand, focuses on purification and filtration. Equipped with advanced media filters, it effectively captures airborne particles, allergens, and pollutants, which is essential for maintaining clean indoor air. The MPL-B series utilizes a multi-stage filtration system that includes HEPA filters, ensuring that the air circulated within spaces meets high standards for cleanliness and safety.

Both the WML-C and MPL-B models utilize smart technology for enhanced control and monitoring. With integrated sensors, users can receive real-time data on air quality, humidity levels, and system performance, allowing for proactive management and maintenance. Additionally, they are compatible with various building management systems, enabling integration into larger infrastructure for comprehensive environmental control.

Durability and reliability are paramount in the design of these units. Built from high-quality materials, both the WML-C and MPL-B are engineered to withstand rigorous usage and varying environmental conditions. Their compact designs allow for flexible installation options, making them suitable for a wide range of settings.

In summary, Field Controls’ WML-C and MPL-B series offer cutting-edge solutions for air quality and HVAC efficiency. With innovative features such as variable speed technology, multi-stage filtration, and smart monitoring capabilities, these systems are ideal for enhancing indoor environments while maintaining energy efficiency and sustainability. They not only meet but exceed the expectations of modern HVAC requirements, making them a valuable investment for any property owner.