Field Controls WML-C, MPL-B manual FAN Timer Board and Limit Control, Circulating AIR Blower

Page 8

main electrical panel; however, accessory equipment such as electronic air cleaners and humidifiers may be included on the furnace circuit. Although a suitably located circuit breaker can be used as a service switch, a separate service switch is advisable. The service switch is necessary if reaching the circuit breaker involves becoming close to the furnace, or if the furnace is located between the circuit breaker and the means of entry to the furnace room. The furnace switch (service switch) should be clearly marked, installed in an easily accessible area between the furnace and furnace room entry, and be located in such a manner to reduce the likelihood that it would be mistaken as a light switch or similar device.

The power requirements for all models: 120 VAC, 1 , 60 Hz., 12A.

Accessories requiring 120 VAC power sources such as electronic air cleaners and humidifier transformers may be powered from the ST9103 EFT. Do not use the direct drive motor connections as a power source, since there is a high risk of damaging the accessories by exposure to high voltage from the auto- generating windings of the direct drive motor.

Thermostat wiring connections and air conditioning contactor low voltage connections are shown in the wiring

diagrams. Some micro-electronic thermostats require additional controls and wiring. Refer to the thermostat manufacturer's instructions.

The thermostat should be located approximately 5 feet above the floor, on an inside wall where there is good natural air circulation, and where the thermostat will be exposed to average room temperatures. Avoid locations where the thermostat will be exposed to cold drafts, heat from nearby lamps and appliances, exposure to sunlight, heat from inside wall stacks, etc.

Normal heat anticipator setting: 0.1 A. For more precise adjustment, the heat anticipator may be adjusted to the amperage draw of the heating control circuit as measured between the "R" and "W" terminals of the thermostat. To reduce the risk of damaging the heat anticipator, do not measure circuit without first removing one of the two wires first. To determine the heating circuit amperage draw:

1.Disconnect one of the “R” or “W” wires from the thermostat terminal.

2.Connect an ammeter between the wire and the thermostat terminal to which it was attached.

3.Note the amperage reading when the heating contacts are closed. (System switch must be on “HEAT” if so equipped.

4.Re-connect the thermostat wire. If the thermostat is serving a combination heating and air conditioning system, pay particular attention to polarity.

5.When the thermostat is reconnected and re-plumbed, adjust the heat anticipator setting to match the observed amperage reading.

FAN TIMER BOARD AND LIMIT CONTROL

The Electronic Fan Timer integrates control of all burner and circulator fan operations. This control is the central wiring point for most of the electrical components in the furnace. The Honeywell ST9103 has a fixed fan delay on time of 30 seconds after the burner ignites. The United Technologies 1158- 120 has an adjustable fan on time that is set by selecting the dipswitch combination displayed in Table 6. This fan on delay can be set at 30, 60, 90 or 120 seconds. This provides a delay between the burner ignition and blower start-up to eliminate excessive flow of cold air when the blower comes on. The Honeywell ST9103 has an adjustable fan off time of 60, 90, 120 and 150 seconds that is set by selecting a dipswitch combination on the control board displayed in Table 5. Similarly the United Technologies 1158-120have an adjustable fan off time of 2, 3, 4 or 6 minutes displayed in Table 6. The fan off delay time starts when the burner motor is de-energized at the end of a call for heat. Blower shutdown is delayed to remove any residual heat from the heat exchanger and improve the annual efficiency of the furnace.

The electronic fan timer board works in conjunction with snap disc limit controls, which perform a safety function, and breaks power to the oil burner primary control, which shuts off the burner if the furnace over-heats. The limit control is thermally operated and automatically resets. The limit control is factory installed, pre-set and is not adjustable.

If a limit control opens, the Honeywell ST9103 will energize the circulating fan. When the limit control closes the burner is re-energized and the heating cycle begins again.

If the limit control opens with the United Technologies 1158-120electronic fan control, the circulating fan will be energized as well. When the limit closes, the control initiates a two minute delay. When this delay is finished, the fan off timer will begin. At the end of the fan off time cycle the burner will be energized, initiating a normal burner cycle.

TABLE 5

Honeywell ST9103

 

 

Dip Switch

 

 

Blower Off Delay

 

 

 

 

Position

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

 

 

 

 

 

 

 

On

 

On

 

 

60 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On

 

Off

 

 

90 seconds

 

 

Off

 

On

 

 

120 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Off

 

Off

 

 

150 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 6

 

 

 

 

 

United Technologies 1158-120

 

 

 

 

 

 

 

 

 

 

 

Dip Switch

 

 

Blower Delay

 

 

 

Position

 

 

Times

 

1

 

2

 

3

4

On

Off

 

 

 

 

 

 

 

 

Seconds

Minutes

 

Off

 

Off

 

 

 

 

30

 

 

 

On

 

Off

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Off

 

On

 

 

 

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On

 

On

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Off

Off

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On

Off

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Off

On

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On

On

 

6

 

 

 

 

 

 

 

 

 

 

 

 

Note: It is advisable not to set the fan on delay time for a time period longer than 90 seconds at highest input. Longer fan on delay times may result in nuisance limit trips.

CIRCULATING AIR BLOWER

All WML-C AND MPL-B furnace models are equipped with a direct drive blower system. Direct drive blower speed adjustments are not normally required in properly sized extended plenum duct systems. The motor RPM and air CFM delivery will vary automatically to accommodate conditions within the usual range of external static pressures typical of residential duct systems. Under-sized duct systems may require a higher blower speed to obtain a reasonable system temperature rise. Some older duct systems were not designed to provide static pressure. They typically feature special reducing fittings at each branch run and lack block ends on the

8

30318 R4 9/9/2005

Image 8
Contents WML-C and MPL-B Table of Contents DOWN-FLOW Installation IntroductionHeat Loss Location of UnitSuspended Installation AIR ConditioningCombustion AIR Chimney VentingCommon Chimney Problems Piping Installation Optional Side Wall VentingOIL Tank Electrical ConnectionsFAN Timer Board and Limit Control Honeywell ST9103 Dip Switch Blower Off Delay Position TimeDip Switch Blower Delay Position Times Off Seconds Minutes Circulating AIR BlowerHumidifier OIL BurnerFurnace Installation SET- UP Checking Over-Fire DraftAnnual Service By Contractor Maintenance and ServiceRoutine Maintenance By Home Owner Operating Instructions Before LightingTo Light Unit To Shut Down UnitAppendix A- WML-C and MPL-B Burner SET UP AF76YBStart UP OIL Burner AIR AdjustmentBurner Electrodes Speed PowerCFM Size Weight Model55-1/4 19 x 18 x 20 x 20 xAppendix B Wiring Diagrams Beckett Afii Burner Wiring Diagram Riello 40F3 and F5 Burner Wiring Diagram Riello 40BF3 Burner Wiring Diagram Operation of OIL Burner Thermostat calls for heat 30318 R4 9/9/2005 Returns to Idle State Recycle Timer Starts OperationMode Action System Response HeatElectrical Shock Hazard R7184 LED Diagnostic LightTroubleshooting Table C-3 R7184 Troubleshooting Corrective ActionRemount control onto burner housing. Go to step Table C4 System and General Troubleshooting Problem Possible Cause RemedyTiming Final Check OUT Parts Listing Counterflow Horizontal Model WML C Parts Listing Vestibule KIT WML C 30318 R4 9/9/2005 Parts Listing Counterflow Horizontal Model MPL Flame Retention Head MPL 30318 R4 9/9/2005 Fuel Supplier If Different from Installation ContractorHOMEOWNER’S Reference Table 30318 R4 9/9/2005 Tel 716 Fax 716

MPL-B, WML-C specifications

Field Controls, a leader in the HVAC industry, offers innovative solutions for air quality and equipment efficiency. Among their range of products, the WML-C and MPL-B series stand out for their remarkable features and advanced technologies, catering to the unique needs of both residential and commercial applications.

The WML-C series is designed for optimal ventilation and air quality management. It integrates seamlessly with existing HVAC systems, providing crucial airflow control and ensuring that indoor environments maintain optimal levels of fresh air. One of its key features is the variable speed fan technology, which adjusts according to the desired airflow rate, thereby enhancing energy efficiency. This not only reduces operational costs but also contributes to a more sustainable environment.

The MPL-B series, on the other hand, focuses on purification and filtration. Equipped with advanced media filters, it effectively captures airborne particles, allergens, and pollutants, which is essential for maintaining clean indoor air. The MPL-B series utilizes a multi-stage filtration system that includes HEPA filters, ensuring that the air circulated within spaces meets high standards for cleanliness and safety.

Both the WML-C and MPL-B models utilize smart technology for enhanced control and monitoring. With integrated sensors, users can receive real-time data on air quality, humidity levels, and system performance, allowing for proactive management and maintenance. Additionally, they are compatible with various building management systems, enabling integration into larger infrastructure for comprehensive environmental control.

Durability and reliability are paramount in the design of these units. Built from high-quality materials, both the WML-C and MPL-B are engineered to withstand rigorous usage and varying environmental conditions. Their compact designs allow for flexible installation options, making them suitable for a wide range of settings.

In summary, Field Controls’ WML-C and MPL-B series offer cutting-edge solutions for air quality and HVAC efficiency. With innovative features such as variable speed technology, multi-stage filtration, and smart monitoring capabilities, these systems are ideal for enhancing indoor environments while maintaining energy efficiency and sustainability. They not only meet but exceed the expectations of modern HVAC requirements, making them a valuable investment for any property owner.