Field Controls manual Appendix A- WML-C and MPL-B Burner SET UP, AF76YB

Page 13

APPENDIX A- WML-C AND MPL-B BURNER SET UP

WML-C AND MPL-B furnaces may be used with the following oil burners.

Please note: The Beckett AF, and Riello 40F oil burners are for applications using indoor air for combustion only. For sidewall venting applications utilizing outdoor air for combustion, use the Beckett AFII or the Riello 40BF (Balanced Flue) oil burners only.

Table A-1 Beckett AF Oil Burner Set-Up

Beckett AF Series Oil Burners

(For use with chimney vented units only)

Furnace

Model

Output BTU/Hr

Burner

Model

Nozzle

Pump

Pressure

Flow Rate

Head 1

Static

Plate

WML-60C 2

58,000

AF76BNHS

0.50 / 80°A

100 PSIG

0.50 USGPH

F3

3- ⅜ in.

WML-80C

75,000

AF76BNHS

0.65 / 80°A

100 PSIG

0.65 USGPH

F3

3- ⅜ in.

WML-90C

85,600

AF76BNHS

0.75 / 80°A

100 PSIG

0.75 USGPH

F3

3- ⅜ in.

MPL-90B

85,500

AF76XN

0.75 / 80°A

100 PSIG

0.75 USGPH

F3

2- ¾ in.

MPL-100B

96,000

AF76XN

0.85 / 80°A

100 PSIG

0.85 USGPH

F3

2- ¾ in.

 

 

 

 

 

 

 

 

MPL-120B

112,000

AF76XN

1.00 / 60°A

100 PSIG

1.00 USGPH

F3

2- ¾ in.

MPL-130B

123,000

AF76YB

1.10 / 70°A

100 PSIG

1.10 USGPH

F6

2- ¾ in.

1Head is shielded by ceramic insulator. 2 Low Firing Rate Baffle required when using a 0.50-gallon nozzle.

Table A-2 Beckett AFII Oil Burner Set-Up

Beckett AFII Series Oil Burners

(For use with sidewall vented units using outdoor combustion air)

Furnace

Model

Output BTU/Hr

Burner

Model

Nozzle

Pump

Pressure

Flow Rate

Head

 

WML-60CB2

63,500

 

AFII-85

 

0.50 / 60°A

 

145 PSIG

0.55 USGPH

 

FB0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WML-80CB2

75,000

 

AFII-85

 

0.60 / 60°A

 

145 PSIG

0.65 USGPH

 

FB3

 

WML-90CB2

85,600

 

AFII-85

 

0.70 / 60°A

 

145 PSIG

0.75 USGPH

 

FB3

 

MPL-90BB2

85,500

 

AFII-150

 

0.70 / 60°A

 

145 PSIG

0.75 USGPH

 

FB0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MPL-100BB2

96,000

 

AFII-150

 

0.80 / 60°A

 

145 PSIG

0.85 USGPH

 

FB3

 

MPL-120BB2

112,000

 

AFII-150

 

0.85 / 70°A

 

145 PSIG

1.00 USGPH

 

FB3

 

 

 

 

 

Table A-3 Riello 40F Series Oil Burner Set-Up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Riello 40F Series Oil Burners

 

 

 

 

 

 

 

 

 

 

(For use with chimney vented units)

 

 

 

 

 

 

Furnace

 

Output

Burner

 

Nozzle

Pump

 

 

Flow Rate

Air Gate

Turbulator

 

Model

 

BTU/Hr

 

Model

 

Pressure

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WML-60CRF

 

59,500

 

40F3

 

0.50 / 60°W

105 PSIG

 

 

0.51 USGPH

2.6

 

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WML-80CRF

 

75,000

 

40F3

 

0.60 / 60°W

115 PSIG

 

 

0.65 USGPH

2.6

 

1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WML-90CRF

 

85,600

 

40F3

 

0.65 / 60°W

135 PSIG

 

 

0.75 USGPH

3.6

 

2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MPL-90BRF

 

85,500

 

40F5

 

0.60 / 60°W

145 PSIG

 

 

0.75 USGPH

2.25

 

0.0

 

MPL-100BRF

 

96,000

 

40F5

 

0.65 / 60°W

145 PSIG

 

 

0.85 USGPH

2.5

 

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MPL-120BRF

 

112,000

 

40F5

 

0.85 / 60°W

145 PSIG

 

 

1.00 USGPH

2.75

 

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

30318 R4 9/9/2005

Image 13
Contents WML-C and MPL-B Table of Contents Introduction DOWN-FLOW InstallationHeat Loss Location of UnitAIR Conditioning Suspended InstallationChimney Venting Combustion AIRCommon Chimney Problems Optional Side Wall Venting Piping InstallationOIL Tank Electrical ConnectionsHoneywell ST9103 Dip Switch Blower Off Delay Position Time FAN Timer Board and Limit ControlDip Switch Blower Delay Position Times Off Seconds Minutes Circulating AIR BlowerOIL Burner Humidifier Checking Over-Fire Draft Furnace Installation SET- UPRoutine Maintenance By Home Owner Maintenance and ServiceAnnual Service By Contractor Before Lighting Operating InstructionsTo Light Unit To Shut Down UnitAF76YB Appendix A- WML-C and MPL-B Burner SET UPBurner Electrodes OIL Burner AIR AdjustmentStart UP CFM PowerSpeed Model Size Weight55-1/4 19 x 18 x 20 x 20 xAppendix B Wiring Diagrams Beckett Afii Burner Wiring Diagram Riello 40F3 and F5 Burner Wiring Diagram Riello 40BF3 Burner Wiring Diagram Operation of OIL Burner Thermostat calls for heat 30318 R4 9/9/2005 Operation Returns to Idle State Recycle Timer StartsHeat Mode Action System ResponseTroubleshooting R7184 LED Diagnostic LightElectrical Shock Hazard Corrective Action Table C-3 R7184 TroubleshootingRemount control onto burner housing. Go to step Problem Possible Cause Remedy Table C4 System and General TroubleshootingTiming Final Check OUT Parts Listing Counterflow Horizontal Model WML C Parts Listing Vestibule KIT WML C 30318 R4 9/9/2005 Parts Listing Counterflow Horizontal Model MPL Flame Retention Head MPL 30318 R4 9/9/2005 HOMEOWNER’S Reference Table If Different from Installation ContractorFuel Supplier 30318 R4 9/9/2005 Tel 716 Fax 716