Field Controls WML-C Operating Instructions, Before Lighting, To Light Unit, To Shut Down Unit

Page 12

should be checked to ensure that all fan speeds are operating properly.

OPERATING INSTRUCTIONS

Before Lighting

Open all supply and return air registers and grilles.

Open all valves in oil pipes.

Turn on electric power supply

To Light Unit

Set the thermostat above room temperature to call for heat. The burner should start. NOTE: It may be necessary to press the RESET button on the primary combustion control relay.

There will be a fan on time delay before the circulating fan is energized. The Honeywell ST9103 has a fixed fan delay on time of 30 seconds after the burner ignites. The United Technologies 1158- 120 has an adjustable fan on time that is set by selecting the dipswitch combination displayed in Chart 1. This fan on delay can be set at 30, 60, 90 or 120 seconds.

Set the thermostat below room temperature. The oil burner should stop.

The air circulation blower will continue to run until the time off setting selected on the electronic fan timer control times out. The Honeywell ST9103 has an adjustable fan off time of 60, 90, 120 and 150 seconds that is set by selecting a dipswitch combination on the control

board. Similarly the United Technologies 1158-120has an adjustable fan off time of 2, 3, 4 or 6 minutes The fan timer control adjustments may be altered if the air at the room registers is uncomfortably high upon blower start up or shutdown.

The necessary adjustments to the fan control settings should be determined by measuring the temperature of the air in the supply air take-off, or within the first few inches of the supply air trunk. The side mid point of the transition is usually ideal, providing that the thermometer probe is beyond the "line of sight" wherein false readings from radiant heat could be observed. The system temperature rise, the difference in temperature between the supply air and return air, should be within the indicated range on the appliance rating plate.

To check the operation of the limit switch, shut off power to the furnace. Temporarily remove the neutral wire from the direct drive blower motor. Restore the electrical power to the

furnace and set the thermostat above room temperature. After three or four minutes of burner operation, the limit control should turn the burner off. When the limit function test is complete, shut off electrical power to the furnace, replace the neutral wire to the blower fan motor, and then restore power. The blower fan will start up immediately. Once the temperature has dropped and the limit control has reset, the fan will operate until the fan off time is achieved. The oil burner will then resume operation and continue until the thermostat is satisfied. Restore the thermostat setting to a comfortable temperature.

To Shut Down Unit

Set the thermostat to the lowest possible setting.

Set the manual switch (if installed) in the Electrical Power Supply Line to "OFF".

NOTE: If the furnace is to be shut down for an extended period of time, close the oil supply valve to the oil burner.

DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS

ACCUMULATED, WHEN THE FURNACE IS FULL OF VAPOUR, OR WHEN THE COMBUSTION CHAMBER IS VERY HOT. NEVER BURN GARBAGE OR PAPER IN THE FURNACE, AND NEVER LEAVE PAPER OR RAGS AROUND THE UNIT.

12

30318 R4 9/9/2005

Image 12
Contents WML-C and MPL-B Table of Contents DOWN-FLOW Installation IntroductionHeat Loss Location of UnitSuspended Installation AIR ConditioningCombustion AIR Chimney VentingCommon Chimney Problems Piping Installation Optional Side Wall VentingOIL Tank Electrical ConnectionsFAN Timer Board and Limit Control Honeywell ST9103 Dip Switch Blower Off Delay Position TimeDip Switch Blower Delay Position Times Off Seconds Minutes Circulating AIR Blower Humidifier OIL BurnerFurnace Installation SET- UP Checking Over-Fire DraftMaintenance and Service Routine Maintenance By Home OwnerAnnual Service By Contractor Operating Instructions Before LightingTo Light Unit To Shut Down UnitAppendix A- WML-C and MPL-B Burner SET UP AF76YBOIL Burner AIR Adjustment Burner ElectrodesStart UP Power CFMSpeed Size Weight Model55-1/4 19 x 18 x 20 x 20 xAppendix B Wiring Diagrams Beckett Afii Burner Wiring Diagram Riello 40F3 and F5 Burner Wiring Diagram Riello 40BF3 Burner Wiring Diagram Operation of OIL Burner Thermostat calls for heat 30318 R4 9/9/2005 Returns to Idle State Recycle Timer Starts OperationMode Action System Response HeatR7184 LED Diagnostic Light TroubleshootingElectrical Shock Hazard Table C-3 R7184 Troubleshooting Corrective ActionRemount control onto burner housing. Go to step Table C4 System and General Troubleshooting Problem Possible Cause RemedyTiming Final Check OUT Parts Listing Counterflow Horizontal Model WML C Parts Listing Vestibule KIT WML C 30318 R4 9/9/2005 Parts Listing Counterflow Horizontal Model MPL Flame Retention Head MPL 30318 R4 9/9/2005 If Different from Installation Contractor HOMEOWNER’S Reference TableFuel Supplier 30318 R4 9/9/2005 Tel 716 Fax 716