Lennox International Inc Merit Series Gas Furnace installation instructions

Page 16

Common Venting Using Metal−Lined Masonry Chimney

 

 

SEALED

 

MAX. LENGTH

 

 

−− SEE NOTE 1

 

5 ft. (1.5 m)

BELOW.

 

MIN. LENGTH −− AS

 

minimum

EXTERIOR

SHORT AS PRACTICAL

 

CHIMNEY WITH

 

 

 

 

METAL

 

 

LINER

VENT CONNECTOR

 

4 in. (102 mm)

 

 

minimum

 

 

 

FURNACE

 

OTHER

 

 

APPLIANCE

 

 

 

PERMANENTLY

 

 

SEALED FIREPLACE

 

 

OPENING

NOTE 1 − Refer to the provided venting tables for installations. Refer to the capacity requirements shown in the provided venting tables.

FIGURE 24

DO NOT insulate the space between the liner and the chimney wall with puffed mica or any other loose gran- ular insulating material.

IMPORTANT

SINGLE appliance venting of a fan-assisted furnace into a tile-lined masonry chimney (interior or outside wall) is PROHIBITED. The chimney must first be lined with either type B1 vent or an insulated single wall flexible vent lining system which has been sized ac- cording to the provided venting tables and the vent pipe manufacturer’s instructions.

A fan−assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met:

SThe chimney is currently serving at least one drafthood− equipped appliance;

SThe vent connectors and chimney are sized according to the provided venting tables.

If type B1 double-wall vent is used inside a chimney, no oth- er appliance can be vented into the chimney. The outer wall of type B1 vent pipe must not be exposed to flue products. A type B1 vent or masonry chimney liner shall terminate above the roof surface with a listed cap or a listed roof as- sembly according to the terms of their respective listings and the vent manufacturer’s instructions.

When inspection reveals that an existing chimney is not safe for the intended purpose, it shall be rebuilt to conform to nationally recognized standards, lined or relined with suitable materials, or replaced with a gas vent or chimney suitable for venting ML180UH series units. The chimney passageway must be checked periodically to ensure that it is clear and free of obstructions.

Do not install a manual damper, barometric draft regulator, or flue restrictor between the furnace and the chimney. Never connect a Category I appliance to a chimney that is servicing a solid−fuel appliance. If a fireplace chimney flue is used to vent this appliance, the fireplace opening must be permanently sealed.

A type B or listed chimney lining system that passes through an unused masonry chimney flue is not considered to be exposed to the outdoors.

General Venting Requirements

Vent all ML180UH furnaces according to these instruc- tions:

1 − Vent diameter recommendations and maximum allow- able piping runs are found in the provided venting tables.

2 − In no case should the vent or vent connector diameter be less than the diameter specified in the provided venting tables.

3 − The minimum vent capacity determined by the sizing tables must be less than the low fire input rating and the maximum vent capacity must be greater than the high fire input rating.

4 − Single appliance vents − If the vertical vent or tile-lined chimney has a larger diameter or flow area than the vent connector, use the vertical vent diameter to de- termine the minimum vent capacity and the vent connector diameter to determine the maximum vent capacity. The flow area of the vertical vent, however, shall not exceed 7 times the flow area of the listed ap- pliance categorized vent area, drafthood outlet area or flue collar area unless designed according to approved engineering methods.

5 − Multiple appliance vents − The flow area of the largest section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent area, drafthood outlet area or flue collar area unless de- signed according to approved engineering methods.

Page 16

Image 16
Contents Installation Instructions ML180UH Table of ContentsUnit Dimensions − inches mm TOP ViewParts Arrangement ML180UH Gas Furnace Safety InformationShipping and Packing List Use of Furnace as Construction Heater GeneralCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space Setting Equipment Return Air Plenum Right Horizontal Application Installation Clearances Top LeftEnd Bottom Filters Duct SystemVenting Upflow PositionTop Vent Discharge Left Side Vent DischargeHorizontal Right Position Horizontal Left PositionSide Vent Discharge Vent Connection Upflow and Horizontal Position Common Venting Using Metal−Lined Masonry Chimney −1/2 Cated or common venting system, you must inspect 18 − The common vent diameter must always be at least asFeet FAN + FAN FAN + NAT 112 175 169 278 Carbon Monoxide Poisoning Hazard Ers or straps. Install a drip leg in vertical pipe runs to − In some localities, codes may require the installationGas Piping Every 8 to 10 feet 2.44 to 3.01 m with suitable hangLeft−Side Air Discharge Horizontal ApplicationRight−Side Air Discharge Electrical Interior MAKE−UP BOX InstallationElectrostatic Discharge ESD Thermostat Designations ML180UH Schematic Wiring Diagram and Sequence of Operation Typical ML180UH Field Wiring Diagram Integrated ControlFor Your Safety Read Before Lighting Unit Start−UpProper Combustion Gas Pressure AdjustmentHigh Altitude Other Unit Adjustments Manifold Pressure Settings at all AltitudesHeat FAN-OFF Time in Seconds No Jumper453 900 750680 885Single Side Return Air − Air volumes in bold require field 1391860 653Service Electrical SHOCK, Fire Or Explosion HazardML180UH BURNER, Combustion AIR Inducer Assembly Heat Exchanger Removal−090, −110 −135 units −045 and −070 unitsPage Planned Service Repair Parts ListIntegrated Control Diagnostic Codes DescriptionTroubleshooting Heating Sequence of Operation Normal Heating Mode Abnormal Heating ModeHeating Sequence Troubleshooting Cooling Sequence of Operation Normal Cooling Mode Abnormal Cooling ModeTroubleshooting Continuous Fan Sequence of Operation Continuous Heat Speed FAN Sequence of Operation

Merit Series Gas Furnace specifications

Lennox International Inc. is a leading name in the heating and cooling industry, and their Merit Series Gas Furnace embodies the commitment to quality and efficiency that the company is known for. The Merit Series is designed to provide reliable heating in a sustainable manner, making it an excellent choice for homeowners seeking comfort without excessive energy bills.

One of the standout features of the Merit Series Gas Furnace is its efficiency ratings. The units in this series typically boast Annual Fuel Utilization Efficiency (AFUE) ratings of up to 95%. This level of efficiency means that the furnace converts a significant portion of the fuel it uses into heat, ultimately lowering operating costs. Such energy-efficient performance is not only beneficial for the wallet but also promotes environmental sustainability.

The Merit Series also incorporates advanced technologies that enhance its operation. The inclusion of a multi-speed blower motor is a notable feature that provides thoughtful airflow management throughout the home. By adjusting the speed according to the heating needs, the furnace optimizes comfort levels while minimizing noise and energy consumption. Homeowners can enjoy a warm environment without the disruptive sounds often associated with traditional furnaces.

Moreover, the Merit Series comes equipped with durable construction materials designed to withstand the test of time. From the robust heat exchanger to the heavy-gauge cabinet, Lennox focuses on longevity and reliability. This ensures that homeowners can trust their furnace to operate effectively even in the harshest winter conditions.

Safety features are also integral to the design of the Merit Series Gas Furnace. With an integrated Flame Sensor and a built-in safety shut-off system, the furnace ensures that any irregularities in operation are promptly detected and addressed. Such measures provide peace of mind for families using the heating system throughout the cold months.

Installation and maintenance are further simplified with the Merit Series. Its design facilitates easier access for HVAC professionals, allowing for quicker installations and routine service, ensuring that homeowners spend less time and money on upkeep.

In conclusion, Lennox International Inc.'s Merit Series Gas Furnace combines efficiency, advanced technology, and robust construction, making it a top choice for families looking to enhance their home's heating system. With its energy-saving innovations and commitment to reliability, the Merit Series stands as an exemplary option in today’s market.