Lennox International Inc Merit Series Gas Furnace Gas Pressure Adjustment, Proper Combustion

Page 30

11 − Are flame rollout switches tripped? If flame rollout switches are tripped, call the service technician for in- spection.

Heating Sequence Of Operation

(follow steps below or see Figure 32 for more detail)

1 − When thermostat calls for heat, combustion air blower starts.

2 − Combustion air pressure switch proves blower opera- tion. Switch is factory−set and requires no adjustment.

3 − After a 15−second prepurge, the hot surface ignitor en- ergizes.

4 − After a 20−second ignitor warm−up period, the gas valve solenoid opens. A 4−second trial for ignition peri- od begins.

5 − Gas is ignited, flame sensor proves the flame, and the combustion process continues.

6 − If flame is not detected after first ignition trial, the igni- tion control will repeat steps 3 and 4 four more times before locking out the gas valve (ATCHGUARD" flame failure mode). The ignition control will then auto- matically repeat steps 1 through 6 after 60 minutes.

7 − To interrupt the 60−minute ATCHGUARD" period, move thermostat from to then back to

Heat." Heating sequence then restarts at step 1.

Gas Pressure Adjustment

Gas Flow (Approximate)

TABLE 10

GAS METER CLOCKING CHART

 

Seconds for One Revolution

 

 

 

 

 

 

 

ML180UH

Natural

 

LP

 

Unit

1 cu ft

2 cu ft

 

1 cu ft

 

2 cu ft

 

Dial

Dial

 

Dial

 

DIAL

 

 

 

 

 

 

 

−045

80

160

 

200

 

400

 

 

 

 

 

 

 

−070

55

110

 

136

 

272

 

 

 

 

 

 

 

−090

41

82

 

102

 

204

 

 

 

 

 

 

 

−110

33

66

 

82

 

164

 

 

 

 

 

 

 

−135

27

54

 

68

 

136

 

 

 

 

 

 

 

Natural−1000 btu/cu ft

LP−2500 btu/cu ft

 

 

 

 

 

 

 

 

Furnace should operate at least 5 minutes before check- ing gas flow. Determine time in seconds for two revolu- tions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time in table 10 below. If manifold pressure matches table 12 and rate is incorrect, check gas orifices for proper size and restriction. Remove temporary gas meter if installed.

NOTE − To obtain accurate reading, shut off all other gas appliances connected to meter.

Supply Pressure Measurement

A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap. Remove the threaded plug, install a field−provided barbed fitting and connect a manometer to measure supply pressure. See table 12 for proper line pressure. Replace the threaded plug after mea- surements have been taken.

Manifold Pressure Measurement

1 − Remove the threaded plug from the outlet side of the gas valve and install a field−provided barbed fitting. Connect to a manometer to measure manifold pres- sure.

2 − Start unit and allow 5 minutes for unit to reach steady state.

3 − While waiting for the unit to stabilize, observe the flame. Flame should be stable and should not lift from burner. Natural gas should burn blue.

4 − After allowing unit to stabilize for 5 minutes, record manifold pressure and compare to value given in table 12.

NOTE − Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to remove barbed fitting and replace threaded plug.

Proper Combustion

Furnace should operate a minimum 15 minutes with cor- rect manifold pressure and gas flow rate before checking combustion. Take combustion sample beyond the flue out- let and compare to the tables below. The maximum car- bon monoxide reading should not exceed 50 ppm.

TABLE 11

ML180UH

CO2% For Nat

CO2% For L.P.

Unit

 

 

 

 

 

−045

 

 

 

 

 

−070

 

 

 

 

 

−090

7.2 − 7.8

7.5 − 9.0

−110

 

 

 

 

 

−135

 

 

 

 

 

High Altitude

 

 

 

 

 

The manifold pressure may require adjustment and com- bustion air pressure switch may need replacing to ensure proper combustion at higher altitudes. Refer to table 12 for manifold pressure and table 13 for pressure switch change and gas conversion kits.

IMPORTANT

For safety, shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to replace pressure tap plug.

Page 30

Image 30
Contents Installation Instructions ML180UH Table of ContentsUnit Dimensions − inches mm TOP ViewParts Arrangement Safety Information ML180UH Gas FurnaceShipping and Packing List Use of Furnace as Construction Heater GeneralCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space Setting Equipment Return Air Plenum Horizontal Application Installation Clearances Top Left RightEnd Bottom Filters Duct SystemTop Vent Discharge VentingUpflow Position Left Side Vent DischargeHorizontal Left Position Horizontal Right PositionSide Vent Discharge Vent Connection Upflow and Horizontal Position Common Venting Using Metal−Lined Masonry Chimney −1/2 Cated or common venting system, you must inspect 18 − The common vent diameter must always be at least asFeet FAN + FAN FAN + NAT 112 175 169 278 Carbon Monoxide Poisoning Hazard Gas Piping Ers or straps. Install a drip leg in vertical pipe runs to− In some localities, codes may require the installation Every 8 to 10 feet 2.44 to 3.01 m with suitable hangHorizontal Application Left−Side Air DischargeRight−Side Air Discharge Interior MAKE−UP BOX Installation ElectricalElectrostatic Discharge ESD Thermostat Designations ML180UH Schematic Wiring Diagram and Sequence of Operation Typical ML180UH Field Wiring Diagram Integrated ControlFor Your Safety Read Before Lighting Unit Start−UpGas Pressure Adjustment Proper CombustionHigh Altitude Other Unit Adjustments Manifold Pressure Settings at all AltitudesHeat FAN-OFF Time in Seconds No Jumper680 453 900750 885860 Single Side Return Air − Air volumes in bold require field1391 653Service Electrical SHOCK, Fire Or Explosion Hazard−090, −110 −135 units ML180UH BURNER, Combustion AIR Inducer AssemblyHeat Exchanger Removal −045 and −070 unitsPage Planned Service Repair Parts ListIntegrated Control Diagnostic Codes DescriptionTroubleshooting Heating Sequence of Operation Normal Heating Mode Abnormal Heating ModeHeating Sequence Troubleshooting Cooling Sequence of Operation Normal Cooling Mode Abnormal Cooling ModeTroubleshooting Continuous Fan Sequence of Operation Continuous Heat Speed FAN Sequence of Operation

Merit Series Gas Furnace specifications

Lennox International Inc. is a leading name in the heating and cooling industry, and their Merit Series Gas Furnace embodies the commitment to quality and efficiency that the company is known for. The Merit Series is designed to provide reliable heating in a sustainable manner, making it an excellent choice for homeowners seeking comfort without excessive energy bills.

One of the standout features of the Merit Series Gas Furnace is its efficiency ratings. The units in this series typically boast Annual Fuel Utilization Efficiency (AFUE) ratings of up to 95%. This level of efficiency means that the furnace converts a significant portion of the fuel it uses into heat, ultimately lowering operating costs. Such energy-efficient performance is not only beneficial for the wallet but also promotes environmental sustainability.

The Merit Series also incorporates advanced technologies that enhance its operation. The inclusion of a multi-speed blower motor is a notable feature that provides thoughtful airflow management throughout the home. By adjusting the speed according to the heating needs, the furnace optimizes comfort levels while minimizing noise and energy consumption. Homeowners can enjoy a warm environment without the disruptive sounds often associated with traditional furnaces.

Moreover, the Merit Series comes equipped with durable construction materials designed to withstand the test of time. From the robust heat exchanger to the heavy-gauge cabinet, Lennox focuses on longevity and reliability. This ensures that homeowners can trust their furnace to operate effectively even in the harshest winter conditions.

Safety features are also integral to the design of the Merit Series Gas Furnace. With an integrated Flame Sensor and a built-in safety shut-off system, the furnace ensures that any irregularities in operation are promptly detected and addressed. Such measures provide peace of mind for families using the heating system throughout the cold months.

Installation and maintenance are further simplified with the Merit Series. Its design facilitates easier access for HVAC professionals, allowing for quicker installations and routine service, ensuring that homeowners spend less time and money on upkeep.

In conclusion, Lennox International Inc.'s Merit Series Gas Furnace combines efficiency, advanced technology, and robust construction, making it a top choice for families looking to enhance their home's heating system. With its energy-saving innovations and commitment to reliability, the Merit Series stands as an exemplary option in today’s market.