Johnson Controls TM9X*MP Accessory Connections, Electronic AIR Cleaner Connection, Twinning

Page 15

ACCESSORY CONNECTIONS

The furnace control will allow power-switching control of various acces- sories.

ELECTRONIC AIR CLEANER CONNECTION

Two 1/4” (6.4 mm) spade terminals (EAC and NEUTRAL) for electronic air cleaner connections are located on the control board. The terminals provide 115 VAC (1.0 amp maximum) during circulating blower opera- tion.

HUMIDIFIER CONNECTION

Two 1/4” (6.4 mm) spade terminals (HUM and NEUTRAL) for humidifier connections are located on the control board. The terminals provide 115 VAC (1.0 amp maximum) during heating system operation.

A mounting hole is provided on the control panel next to the furnace control board for mounting a humidifier transformer if required.

TWINNING

These furnaces are not to be twinned. If more than one furnace is needed in an application, each furnace must have its own complete duct system and its own wall thermostat.

SECTION VI: CONDENSATE PIPING AND FURNACE VENTING CONFIGURATION

CONDENSATE DRAIN LOCATION

As shipped from the factory:

For all 040, 060 & 080K input furnaces the main drain is plumbed through the casing right-side opening when viewed from the front of the furnace.

For all 100 & 120 input furnaces the main drain is plumbed through the casing left-side opening when viewed from the front of the fur- nace.

NOTICE

The Figures 22 - 25 show the condensate drain arrangement for the various possible furnace and vent blower positions.

The condensate hoses must slope downwards at all points.

The furnace condensate pan is self priming and contains an internal trap to prevent flue gas leaking. Do not install an external condensate trap.

When drain hose routing changes are required (shown in Figures 22- 25), be sure to cap all un-used openings.

If rerouting hoses - excess length should be cut off so that no sagging loops will collect and hold condensate - which will cause the furnace to not operate.

No hose clamps are needed for connecting to the condensate pan.

The furnace, evaporator coil, and humidifier drains may be combined and drained together. The evaporator coil drain may have an exter- nal, field-supplied trap prior to the furnace drain connection to prevent conditioned air leakage. All drain connections (furnace, evaporator coil, or humidifier) must be terminated into an open or vented drain as close to the respective equipment as possible. Regular maintenance is required on condensate drainage system.

697936-UIM-B-01211

Condensate must be disposed of properly. Follow local plumbing

or wastewater codes. The drain line must maintain a 1/4" per foot (20 mm/m) downward slope to the drain.

If an external vent tee is being installed, then it must have its own condensate trap before it is disposed into an open or vented drain.

This is not to be considered as a second trap as referenced else- where in this document.

Open Stand Pipe (Anti-siphon air vent)

5” Min.

Tee

To Open Or

Vented Drain

FIGURE 20: Typical. Condensate drain, vertical installation

The condensate will flow to the drain better if an open stand pipe is installed in the drain line. See Figure 20.

If evaporator coil or humidifier drains are combined with the furnace drain, then the open stand pipe could be raised higher, above the 5” minimum.

NOTICE

A loop has been added to the pressure switch vacuum hose. How- ever, ensure that all pressure switch hoses are routed such that they prevent any condensate from entering the pressure switch.

It is possible for condensation to form inside the combustion air (intake) pipe in the summer months if significant length of combustion air pipe passes through conditioned space. This problem can be averted by the addition of a simple drain tee, or a drain tee with a drain on the combustion air pipe as close to the furnace as possible, as shown in Figure 21. This is true for all long horizontal venting in any furnace configuration. This will prevent the condensate from entering the furnace.

Johnson Controls Unitary Products

15

Image 15
Contents Combustion AIR and Vent System List of SectionsList of Figures List of TablesSection I Safety Specific Safety Rules and PrecautionsSafety Requirements Codes and Standards Combustion AIR Quality List of ContaminantsFurnace Location and Clearances InspectionDuct Flanges Floor Base and Ductwork Installation DownflowSection II Ductwork Ductwork General InformationCoil Flange Installation Coil InstallationCOIL/FURNACE Assembly MC/FC/PC Series Coils Furnace Assembly MC & FC Series CoilsCritical Coil Projection Coil / Furnace Assembly HC Series CoilsDownflow Duct Connectors Bottom Return and Attic InstallationsDownflow Application Horizontal ApplicationBtuh kW Filter InstallationCabinet Dimensions Inches Section III FiltersSide Return GAS SafetyGAS Piping Installation Section IV GAS PipingManifold Pressures in. w.c High Altitude Pressure Switch ConversionGAS Orifice Conversion for Propane LP High Altitude GAS Orifice ConversionSupply Voltage Connections Section V Electrical PowerElectrical Power Connections LOW Voltage Control Wiring ConnectionsSingle Stage Air Conditioner Single Stage Furnace Single Stage Heat Pump Single Stage Furnace Twinning Accessory ConnectionsElectronic AIR Cleaner Connection Humidifier ConnectionCondensate Drain Termination Will cause the furnace Johnson Controls Downflow ConfigurationHorizontal Left ConfigurationHorizontal Right Inducer Rotated Model Input Pipe Size Maximum Combustion AIR and Vent SafetySection VII Combustion AIR and Vent System Combustion AIR/VENT Pipe SizingFitting Equivalent Length Combustion AIR and Vent Piping AssemblyElbow a Dimension Combustion AIR / VentingHome Layout Vent ClearancesVent System Vent Applications and TerminationVenting Multiple Units Ambient Combustion Air Supply Downward VentingOutdoor Combustion Air Combustion AIR SupplyCombustion Air Source From Outdoors Dampers, Louvers and Grilles Canada OnlyFree Area Air Supply Openings and Ducts Ventilated Combustion AirVentilated Combustion Air Termination Section Viii START-UP Adjustments Specially Engineered InstallationsVent Blower Rotation GAS Piping Leak Check Ignition System SequenceCalculating the Furnace Input NAT. GAS Revolution Cu Ft Seconds ForRevolution Adjustment of Manifold GAS Pressure & Input Rate Read the inlet gas pressureRead the manifold gas pressure Adjustment of FAN Control Settings Adjustment of Temperature RiseControl Circuit Fuse Section IX Safety ControlsBlower Door Safety Switch Rollout Switch ControlsSection X Normal Operation and Diagnostics Diagnostic Fault Code Storage and Retrieval Section XI Replacement Parts List Replacement Part Contact InformationFabricated Parts Section XII Wiring Diagram Wiring FurnaceJohnson Controls Unitary Products York Drive Norman, OK

TM9X*MP specifications

The Johnson Controls TM9X*MP series represents a significant advancement in the realm of HVAC control systems, positioning itself as a versatile solution for both commercial and residential applications. Renowned for its intelligent design and user-friendly interface, the TM9X*MP series aims to enhance energy efficiency and provide comfort to its users.

One of the standout features of the TM9X*MP series is its advanced communication capabilities. It employs the latest communication protocols, including BACnet and Modbus, which facilitate seamless integration with various building management systems. This connectivity ensures that users can monitor and control their HVAC systems remotely, providing unparalleled convenience and control over their environment.

Further enhancing its adaptability, the TM9X*MP series supports a wide range of HVAC equipment, including heat pumps, rooftop units, and variable air volume systems. This flexibility makes it an ideal choice for diverse applications, catering to the specific needs of different building types and operational requirements.

Energy efficiency is a significant focus of the TM9X*MP series. The system is equipped with advanced algorithms that optimize HVAC performance based on real-time data inputs. By utilizing trends in occupancy and weather forecasts, the TM9X*MP can make informed adjustments to operation schedules and settings, ensuring minimal energy wastage while maintaining optimal comfort levels.

Another notable characteristic of the TM9X*MP series is its intuitive touchscreen interface. This user-centric design makes it easy for operators to navigate through various settings and configurations, reducing the complexity often associated with HVAC controls. The interface can display vital system information, including energy consumption metrics and system diagnostics, empowering users to make informed decisions regarding their HVAC systems.

The TM9X*MP series also prioritizes robustness and reliability. Built with high-quality components, these controllers are designed to withstand varying environmental conditions, ensuring extensive operational longevity. Furthermore, the comprehensive support and resources provided by Johnson Controls augment the TM9X*MP series’ reputation for exceptional service and performance.

In conclusion, the Johnson Controls TM9X*MP series is a versatile and reliable solution for modern HVAC control needs. Its advanced communication capabilities, energy-efficient algorithms, user-friendly interface, and robust design make it a strong contender in the market, catering to the dynamic demands of contemporary heating and cooling applications. Whether for large commercial buildings or smaller residential units, the TM9X*MP series stands out as a top-tier choice for HVAC management.