Johnson Controls TM9X*MP Combustion AIR and Vent Piping Assembly, Combustion AIR / Venting

Page 22

697936-UIM-B-01211

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STANDARD ELBOW

LONG (SWEEP) ELBOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIGURE 26: Dimensions

 

 

 

 

 

 

 

 

TABLE 8: Elbow Dimensions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Elbow "A" Dimension

 

 

 

 

 

 

 

 

2" Standard

2-5/16"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3" Standard

3-1/16"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2" Sweep

3-1/4"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3" Sweep

4-1/16"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions are those required in Standard ASTM D-3311.

TABLE 9: Equivalent Length of Fittings

Fitting

Equivalent Length

2" 90° sweep elbow

5 feet of 2" pipe

2" 45° sweep elbow

2-1/2 feet of 2" pipe

2" 90° standard elbow

7 feet of 2" pipe

2" 45° standard elbow

3-1/2 feet of 2" pipe

3" 90° sweep elbow

5 feet of 3" pipe

3" 45° sweep elbow

2-1/2 feet of 3" pipe

3" 90° standard elbow

7 feet of 3" pipe

3" 45° standard elbow

3-1/2 feet of 3" pipe

4" 90° elbow (sweep or standard)

5 feet of 4" pipe

4" 45° elbow (sweep or standard)

2-1/2 feet of 4" pipe

2" corrugated connector

10 feet of 2" pipe

3" corrugated connector

10 feet of 3" pipe

4" corrugated connector

10 feet of 4" pipe

Example:

An 80,000 BTUH furnace requires 32 feet of pipe and five 90º elbows. Using 2" pipe and standard elbows, the total equivalent length will be:

32 feet of 2" pipe =

32 equivalent feet

5 - 90º standard 2" elbows = (5 x 7) =

35 equivalent feet

Total =

67 equivalent feet of 2" pipe

This exceeds the 65 foot maximum equivalent length of 2" pipe allowed for that model and is thus not acceptable.

By using sweep elbows, the total equivalent length will be:

32 feet of 2" pipe =

32 equivalent feet

5 - 90º sweep 2" elbows = (5 x 5) =

25 equivalent feet

Total =

57 equivalent feet of 2" pipe

This is less than the 65 foot maximum equivalent length of 2" pipe allowed for that model and is thus acceptable.

Alternatively, using 3" pipe and standard elbows, the total equivalent length will be:

32 feet of 3" pipe =

32 equivalent feet

5 - 90º standard 3" elbows = (5 x 7) =

35 equivalent feet

Total =

67 equivalent feet of 3" pipe

This is less than the 90 foot maximum equivalent length of 3" pipe allowed for that model and is thus acceptable.

TABLE 10: Combustion Air Intake and Vent Connection Size at Furnace (All Models)

FURNACE VENT CONNECTION SIZES

Furnace Input

All

Intake Pipe Size

2” (5.1 cm)

Vent Pipe Size

2” (5.1 cm)

Furnace vent pipe connections are sized for 2” (5.1 cm). pipe. Any pipe size change must be made outside the furnace casing in a verti- cal pipe section to allow proper drainage of condensate. An offset using two 45º (degree) elbows will be required for plenum clearance when the vent is increased to 3” (7.6 cm).

Accessory concentric vent / intake termination kits 1CT0302 and 1CT0303, and for Canadian applications 1CT0302-636 and 1CT0303-636 are available and approved for use with these fur- naces. Horizontal sidewall vent terminations kits 1HT0901 & 1HT0902 are also approved for use with these furnaces.

COMBUSTION AIR AND VENT PIPING ASSEMBLY

The final assembly procedure for the combustion air and vent piping is as follows:

1.Cut piping to the proper length beginning at the furnace.

2.Deburr the piping inside and outside.

3.Chamfer (bevel) the outer edges of the piping.

4.Dry-fit the vent piping assembly from the furnace to the outside ter- mination checking for proper fit support and slope.

5.Dry-fit the combustion air piping assembly checking for proper fit, support and slope on the following systems:

a.Sealed combustion air systems from the furnace to the out- side termination.

b.Ventilated combustion air systems from the furnace to the attic or crawl space termination.

Solvent cements are flammable and must be used in well-ventilated areas only. Keep them away from heat, sparks and open flames. Do not breathe vapors and avoid contact with skin and eyes.

6.Disassemble the combustion air and vent piping, apply cement primer and the cement per the manufactures instructions. Primer and cement must conform to ASTM D2564 for PVC, or ASTM D2235 for ABS piping.

7.All joints must provide a permanent airtight and watertight seal.

8.Support the combustion air and vent piping such that it is angled a minimum of 1/4” per foot (21 mm/m) so that condensate will flow back towards the furnace. Piping should be supported with pipe hangers to prevent sagging.

9.Seal around the openings where the combustion air and / or vent piping pass through the roof or sidewalls.

COMBUSTION AIR / VENTING

The vent must be installed with the minimum required clearances, and must comply with local codes and requirements.

22

Johnson Controls Unitary Products

Image 22
Contents List of Tables List of SectionsList of Figures Combustion AIR and Vent SystemSpecific Safety Rules and Precautions Section I SafetySafety Requirements Combustion AIR Quality List of Contaminants Codes and StandardsInspection Furnace Location and ClearancesDuctwork General Information Floor Base and Ductwork Installation DownflowSection II Ductwork Duct FlangesFurnace Assembly MC & FC Series Coils Coil InstallationCOIL/FURNACE Assembly MC/FC/PC Series Coils Coil Flange InstallationBottom Return and Attic Installations Coil / Furnace Assembly HC Series CoilsDownflow Duct Connectors Critical Coil ProjectionHorizontal Application Downflow ApplicationSection III Filters Filter InstallationCabinet Dimensions Inches Btuh kWSection IV GAS Piping GAS SafetyGAS Piping Installation Side ReturnHigh Altitude GAS Orifice Conversion High Altitude Pressure Switch ConversionGAS Orifice Conversion for Propane LP Manifold Pressures in. w.cLOW Voltage Control Wiring Connections Section V Electrical PowerElectrical Power Connections Supply Voltage ConnectionsSingle Stage Air Conditioner Single Stage Furnace Single Stage Heat Pump Single Stage Furnace Humidifier Connection Accessory ConnectionsElectronic AIR Cleaner Connection TwinningCondensate Drain Termination Will cause the furnace Downflow Configuration Johnson ControlsConfiguration Horizontal LeftHorizontal Right Inducer Rotated Combustion AIR/VENT Pipe Sizing Combustion AIR and Vent SafetySection VII Combustion AIR and Vent System Model Input Pipe Size MaximumCombustion AIR / Venting Combustion AIR and Vent Piping AssemblyElbow a Dimension Fitting Equivalent LengthVent Clearances Home LayoutVent Applications and Termination Vent SystemVenting Multiple Units Combustion AIR Supply Downward VentingOutdoor Combustion Air Ambient Combustion Air SupplyDampers, Louvers and Grilles Canada Only Combustion Air Source From OutdoorsFree Area Ventilated Combustion Air Air Supply Openings and DuctsVentilated Combustion Air Termination Specially Engineered Installations Section Viii START-UP AdjustmentsVent Blower Rotation Ignition System Sequence GAS Piping Leak CheckCalculating the Furnace Input NAT. GAS Seconds For Revolution Cu FtRevolution Read the inlet gas pressure Adjustment of Manifold GAS Pressure & Input RateRead the manifold gas pressure Adjustment of Temperature Rise Adjustment of FAN Control SettingsRollout Switch Controls Section IX Safety ControlsBlower Door Safety Switch Control Circuit FuseSection X Normal Operation and Diagnostics Diagnostic Fault Code Storage and Retrieval Replacement Part Contact Information Section XI Replacement Parts ListFabricated Parts Wiring Furnace Section XII Wiring DiagramJohnson Controls Unitary Products York Drive Norman, OK

TM9X*MP specifications

The Johnson Controls TM9X*MP series represents a significant advancement in the realm of HVAC control systems, positioning itself as a versatile solution for both commercial and residential applications. Renowned for its intelligent design and user-friendly interface, the TM9X*MP series aims to enhance energy efficiency and provide comfort to its users.

One of the standout features of the TM9X*MP series is its advanced communication capabilities. It employs the latest communication protocols, including BACnet and Modbus, which facilitate seamless integration with various building management systems. This connectivity ensures that users can monitor and control their HVAC systems remotely, providing unparalleled convenience and control over their environment.

Further enhancing its adaptability, the TM9X*MP series supports a wide range of HVAC equipment, including heat pumps, rooftop units, and variable air volume systems. This flexibility makes it an ideal choice for diverse applications, catering to the specific needs of different building types and operational requirements.

Energy efficiency is a significant focus of the TM9X*MP series. The system is equipped with advanced algorithms that optimize HVAC performance based on real-time data inputs. By utilizing trends in occupancy and weather forecasts, the TM9X*MP can make informed adjustments to operation schedules and settings, ensuring minimal energy wastage while maintaining optimal comfort levels.

Another notable characteristic of the TM9X*MP series is its intuitive touchscreen interface. This user-centric design makes it easy for operators to navigate through various settings and configurations, reducing the complexity often associated with HVAC controls. The interface can display vital system information, including energy consumption metrics and system diagnostics, empowering users to make informed decisions regarding their HVAC systems.

The TM9X*MP series also prioritizes robustness and reliability. Built with high-quality components, these controllers are designed to withstand varying environmental conditions, ensuring extensive operational longevity. Furthermore, the comprehensive support and resources provided by Johnson Controls augment the TM9X*MP series’ reputation for exceptional service and performance.

In conclusion, the Johnson Controls TM9X*MP series is a versatile and reliable solution for modern HVAC control needs. Its advanced communication capabilities, energy-efficient algorithms, user-friendly interface, and robust design make it a strong contender in the market, catering to the dynamic demands of contemporary heating and cooling applications. Whether for large commercial buildings or smaller residential units, the TM9X*MP series stands out as a top-tier choice for HVAC management.