Johnson Controls TM9X*MP installation manual Section X Normal Operation and Diagnostics

Page 34

697936-UIM-B-01211

PRESSURE SWITCHES

This furnace is supplied with two pressure switches, which monitor the flow through the combustion air/vent piping and condensate drain sys- tem. These switches de-energize the gas valve if any of the following conditions are present. Refer to "CONDENSATE PIPING AND FUR- NACE VENTING CONFIGURATION" for tubing connections.

1.Blockage of combustion air piping or terminals.

2.Blockage of condensate drain piping.

3.Blockage of vent piping or terminal.

4.Failure of combustion air blower motor.

LIMIT CONTROLS

There is a high temperature limit control located on the furnace vesti- bule panel near the gas valve. This is an automatic reset control that provides over temperature protection due to reduced airflow. This may be caused by:

1.A dirty filter.

2.If the indoor fan motor should fail.

3.Too many supply or return registers closed or blocked off.

The control module will lockout if the limit trips 5 consecutive times. If this occurs, control will reset & try ignition again after 1 hour.

SECTION X: NORMAL OPERATION AND DIAGNOSTICS

NORMAL OPERATION SEQUENCE

The following describes the sequence of operation of the furnace. Refer to Owners Manual for component location.

Continuous Blower

Cooling/heating thermostats have a fan switch that has an ON and AUTO position. In the ON position the thermostat circuit is completed between terminals R and G. The motor will operate continuously on the speed tap wire that is connected to the “G” terminal on the furnace con- trol board. To obtain a different contant air circulation, change the wire to another speed wire.

Intermittent Blower - Cooling

Cooling/heating thermostats have a fan switch that has an ON and AUTO position. In the AUTO position the thermostat circuit is completed between terminals R and G when there is a call for cooling. The motor will operate on the speed tap wire that is connected to the HI COOL cooling terminal on the control board. The fan off setting is fixed at 60 seconds to improve cooling efficiency.

Heating Cycle

When the thermostat switch is set on HEAT and the fan is set on AUTO, and there is a call for heat, a circuit is completed between terminals R and W of the thermostat. When the proper amount of combustion air is being provided, the pressure switch will close, the ignition control pro- vides a 17-second ignitor warm-up period, the gas valve then opens, the gas starts to flow, ignition occurs and the flame sensor begins its sensing function. The blower motor will energize 30 seconds after the gas valve opens, if a flame is detected. Normal furnace operation will continue until the thermostat circuit between R and W is opened, which causes the ignition system and gas valve to de-energize and the burner flames to be extinguished. The vent motor will operate for 15 seconds and the blower motor will operate for the amount of time set by the fan- off delay jumper located on the control board. See Figure 39. The heat- ing cycle is now complete, and ready for the start of the next heating cycle.

If the flame is not detected within 7 seconds of the gas valve opening, the gas valve is shut off and a retry operation begins. Also, if the flame is lost for 2 seconds during the 10-second stabilization period, the gas valve is shut off and a retry operation begins. During a retry operation, the vent motor starts a 15 second inter-purge and the ignitor warm-up time is extended to 27 seconds. If the flame is established for more than 10 seconds after ignition during a retry, the control will clear the ignition attempt (retry) counter. If three retries occur during a call for heat, the furnace will shut down for one hour. If at the end of the one hour shut down there is a call for heat, the furnace will initiate a normal start cycle. If the problem has not been corrected the furnace will again lockout after three retries.

A momentary loss of gas supply, flame blowout, or a faulty flame probe circuit will result in a disruption in the flame and be sensed within 1.0 seconds. The gas valve will de-energize and the control will begin a recycle operation. A normal ignition sequence will begin after a 15 sec- ond inter-purge. If during the five recycles the gas supply does not return, or the fault condition is not corrected the ignition control will lock- out for 60 minutes.

During burner operation, a momentary loss of power for 50 milliseconds or longer will de-energize the gas valve. When the power is restored, the gas valve will remain de-energized and the ignition sequence will immediately restart.

TROUBLESHOOTING

The following visual checks should be made before troubleshooting:

1.Check to see that the power to the furnace and the ignition control module is ON.

2.The manual shut-off valves in the gas line to the furnace must be open.

3.Make sure all wiring connections are secure.

4.Review the sequence of operation. Start the system by setting the thermostat above the room temperature. Observe the system’s response. Then use the troubleshooting section in this manual to check the system’s operation.

Never bypass any safety control to allow furnace operation. To do so will allow furnace to operate under potentially hazardous conditions.

Do not try to repair controls. Replace defective controls with UPG Source 1 Parts.

Never adjust pressure switch to allow furnace operation.

FURNACE CONTROL DIAGNOSTICS

The furnace has built-in, self-diagnostic capability. A blinking LED light on the control board can flash red, green or amber to indicate various conditions. The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED light will indicate the failure code.

The SLOW flash speed is two seconds on and two seconds off.

The other flash codes listed below have the following timing: LED light will turn on for 1/3 second and off for 1/3 second. This pattern will be repeated the number of times equal to the code. There will be a two- second pause between codes. For example, the six red flash code will flash the LED light on and off six times, then will be off for two seconds. This pattern will repeat as long as the fault condition remains.

SLOW GREEN FLASH: Normal operation, no thermostat calls.

SLOW AMBER FLASH: Normal operation with call for heat.

LED STEADY OFF – If the LED light does not flash at all, check for power to the board and check for a blown fuse on the board. If the board is properly powered and the fuse is not blown, the control board may need to be replaced.

34

Johnson Controls Unitary Products

Image 34
Contents List of Tables List of SectionsList of Figures Combustion AIR and Vent SystemSpecific Safety Rules and Precautions Section I SafetySafety Requirements Combustion AIR Quality List of Contaminants Codes and StandardsInspection Furnace Location and ClearancesDuctwork General Information Floor Base and Ductwork Installation DownflowSection II Ductwork Duct FlangesFurnace Assembly MC & FC Series Coils Coil InstallationCOIL/FURNACE Assembly MC/FC/PC Series Coils Coil Flange InstallationBottom Return and Attic Installations Coil / Furnace Assembly HC Series CoilsDownflow Duct Connectors Critical Coil ProjectionHorizontal Application Downflow ApplicationSection III Filters Filter InstallationCabinet Dimensions Inches Btuh kWSection IV GAS Piping GAS SafetyGAS Piping Installation Side ReturnHigh Altitude GAS Orifice Conversion High Altitude Pressure Switch ConversionGAS Orifice Conversion for Propane LP Manifold Pressures in. w.cLOW Voltage Control Wiring Connections Section V Electrical PowerElectrical Power Connections Supply Voltage ConnectionsSingle Stage Air Conditioner Single Stage Furnace Single Stage Heat Pump Single Stage Furnace Humidifier Connection Accessory ConnectionsElectronic AIR Cleaner Connection TwinningCondensate Drain Termination Will cause the furnace Downflow Configuration Johnson ControlsConfiguration Horizontal LeftHorizontal Right Inducer Rotated Combustion AIR/VENT Pipe Sizing Combustion AIR and Vent SafetySection VII Combustion AIR and Vent System Model Input Pipe Size MaximumCombustion AIR / Venting Combustion AIR and Vent Piping AssemblyElbow a Dimension Fitting Equivalent LengthVent Clearances Home LayoutVent Applications and Termination Vent SystemVenting Multiple Units Combustion AIR Supply Downward VentingOutdoor Combustion Air Ambient Combustion Air SupplyDampers, Louvers and Grilles Canada Only Combustion Air Source From OutdoorsFree Area Ventilated Combustion Air Air Supply Openings and DuctsVentilated Combustion Air Termination Specially Engineered Installations Section Viii START-UP AdjustmentsVent Blower Rotation Ignition System Sequence GAS Piping Leak CheckCalculating the Furnace Input NAT. GAS Seconds For Revolution Cu FtRevolution Read the inlet gas pressure Adjustment of Manifold GAS Pressure & Input RateRead the manifold gas pressure Adjustment of Temperature Rise Adjustment of FAN Control SettingsRollout Switch Controls Section IX Safety ControlsBlower Door Safety Switch Control Circuit FuseSection X Normal Operation and Diagnostics Diagnostic Fault Code Storage and Retrieval Replacement Part Contact Information Section XI Replacement Parts ListFabricated Parts Wiring Furnace Section XII Wiring DiagramJohnson Controls Unitary Products York Drive Norman, OK

TM9X*MP specifications

The Johnson Controls TM9X*MP series represents a significant advancement in the realm of HVAC control systems, positioning itself as a versatile solution for both commercial and residential applications. Renowned for its intelligent design and user-friendly interface, the TM9X*MP series aims to enhance energy efficiency and provide comfort to its users.

One of the standout features of the TM9X*MP series is its advanced communication capabilities. It employs the latest communication protocols, including BACnet and Modbus, which facilitate seamless integration with various building management systems. This connectivity ensures that users can monitor and control their HVAC systems remotely, providing unparalleled convenience and control over their environment.

Further enhancing its adaptability, the TM9X*MP series supports a wide range of HVAC equipment, including heat pumps, rooftop units, and variable air volume systems. This flexibility makes it an ideal choice for diverse applications, catering to the specific needs of different building types and operational requirements.

Energy efficiency is a significant focus of the TM9X*MP series. The system is equipped with advanced algorithms that optimize HVAC performance based on real-time data inputs. By utilizing trends in occupancy and weather forecasts, the TM9X*MP can make informed adjustments to operation schedules and settings, ensuring minimal energy wastage while maintaining optimal comfort levels.

Another notable characteristic of the TM9X*MP series is its intuitive touchscreen interface. This user-centric design makes it easy for operators to navigate through various settings and configurations, reducing the complexity often associated with HVAC controls. The interface can display vital system information, including energy consumption metrics and system diagnostics, empowering users to make informed decisions regarding their HVAC systems.

The TM9X*MP series also prioritizes robustness and reliability. Built with high-quality components, these controllers are designed to withstand varying environmental conditions, ensuring extensive operational longevity. Furthermore, the comprehensive support and resources provided by Johnson Controls augment the TM9X*MP series’ reputation for exceptional service and performance.

In conclusion, the Johnson Controls TM9X*MP series is a versatile and reliable solution for modern HVAC control needs. Its advanced communication capabilities, energy-efficient algorithms, user-friendly interface, and robust design make it a strong contender in the market, catering to the dynamic demands of contemporary heating and cooling applications. Whether for large commercial buildings or smaller residential units, the TM9X*MP series stands out as a top-tier choice for HVAC management.