Toshiba RAV-SM1106BT-E Operation of diagnostic function, Check, Status of, Judgment and measures

Models: RAV-SM456BT-E RAV-SM566BT-TR RAV-SM566BT-E RAV-SM456BT-TR RAV-SM806BT-E RAV-SM806BT-TR RAV-SM1106BT-TR RAV-SM1106BT-E RAV-SM1406BT-TR RAV-SM1606BT-TR RAV-SM1606BT-E RAV-SM1406BT-E RAV-SM406BT-TR

1 104
Download 104 pages 55.2 Kb
Page 44
Image 44

 

Operation of diagnostic function

 

 

 

 

 

 

 

 

 

Check

 

Status of

 

 

 

code

 

 

 

Judgment and measures

 

Cause of operation

air conditioner

Condition

 

Indoor

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

 

 

H03

Current detection circuit error

Stop

Displayed when

1. Check outdoor P.C. board.

error is detected

 

(AC current detection circuit)

 

 

 

 

 

 

 

 

 

 

Open phase of 3-phase power supply

 

Displayed when

1. Check open phase of 3-phase power supply.

P05

Stop

2. Black lead wire to be connected to CN03 of outdoor P. C.

error is detected

 

 

 

 

 

 

board does not pass through T611.

 

 

 

 

 

 

 

 

 

 

1.

Check connection of Ps sensor connector.

 

 

 

Displayed when

2.

Check failure of Ps sensor.

F23

Ps sensor error

Stop

3. Check compressing power error of compressor.

error is detected

 

 

 

4.

Check 4-way valve error.

 

 

 

 

 

 

 

 

5.

Check outdoor P.C. board error.

 

 

 

 

 

 

 

 

 

 

1.

Check service valves are fully opened.

 

 

 

 

 

(Gas side, Liquid side)

 

 

 

 

2.

Check clogging of outdoor PMV. (PMV1, 2)

 

 

 

Displayed when

3.

Check SV2 circuit.

H06

Low pressure protective operation

Stop

4. Check Ps sensor error.

error is detected

 

 

 

 

5.

Check clogging of indoor filter.

 

 

 

 

6.

Check clogging of refrigerant pipe.

 

 

 

 

7.

Check of outdoor fan operation. (In heating mode)

 

 

 

 

8.

Check short of refrigerant.

 

 

 

 

 

 

Discharge temp. error

 

Displayed when

1. Check refrigerating cycle (Gas leak)

P03

Discharge temp. (TD) over specified value

Stop

2. Trouble of electronic expansion valve

error is detected

 

was detected.(1.6)

 

3.

Check discharge temp. sensor (TD).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check case thermostat and connector.

 

Case thermostat operation

 

Displayed when

2.

Check gas leak, recharge

H04

Stop

3. Check full open of service valve.

Abnormal overheat of compressor

error is detected

 

 

4.

Check PMV (Pulse Motor Valve).

 

 

 

 

 

 

 

 

5.

Check broken pipe.

 

 

 

 

 

 

 

 

 

 

1.

Check service valves are fully opened.

 

 

 

 

 

(Gas side, Liquid side)

 

 

 

 

2.

Check of outdoor fan operation.

 

 

 

 

3.

Check motor error of outdoor fan.

 

 

 

Displayed when

4.

Check clogging of outdoor PMV. (PMV1, 2)

P04

High pressure SW system error

Stop

5. Check clogging of heat exchanger in indoor/outdoor units.

error is detected

 

 

 

6.

Short-circuit status of suction/discharge air in outdoor unit.

 

 

 

 

 

 

 

 

7.

Check outdoor P.C. board error.

 

 

 

 

8.

Check fan system error (Cause of air volume drop) at

 

 

 

 

 

indoor side.

 

 

 

 

9.

Check PMV opening status in indoor unit.

 

 

 

 

 

P05

Power supply voltage error

Stop

Displayed when

1. Check power supply voltage.

error is detected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High pressure protective operation

 

 

1.

Check outdoor heat exchanger sensor (TL).

 

 

 

2.

Check indoor heat exchanger sensor (TC, TCJ).

 

• During cooling operation, outdoor temp.

 

 

 

 

 

3.

Check full open of service valve.

 

sensor (TL) detected temperature over

 

 

P20

 

Displayed when

4. Check indoor/outdoor fan.

specified temp.

Stop

 

error is detected

5.

Check PMV (Pulse Motor Valve).

 

• During heating operation, indoor temp.

 

 

 

 

 

 

 

6. Check clogging and short circuit of indoor/outdoor heat

 

sensor (TC, TCJ) detected temperature over

 

 

 

specified temp.

 

 

 

exchanger.

 

 

 

 

7. Overcharge of refrigerant. Recharge

 

 

 

 

 

 

 

 

Displayed when

1. Check lock of fan motor.

P22

Outdoor fan system error

Stop

2. Check power supply voltage between L2 and N.

error is detected

 

 

 

3. Check outdoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

1. When performing operation while taking-off compressor

P26

Short-circuit error of compressor driving

Stop

Displayed when

 

wire, P26 error occurs. Check control P.C. board.

 

 

element

error is detected

2. When performing operation while taking-off compressor

 

 

 

 

 

 

 

wire, an error does not occur. (Compressor rare short)

 

 

 

 

 

P29

Position detection circuit error

Stop

Displayed when

1. Check control P.C. board.

error is detected

 

 

 

 

 

 

 

 

 

 

 

 

 

– 44 –

Page 44
Image 44
Toshiba RAV-SM1106BT-E Operation of diagnostic function, Check, Status of, Judgment and measures, Cause of operation