Toshiba RAV-SM1606BT-E, RAV-SM406BT-TR Outline of specifications, Remarks, Tc n, Conditions

Models: RAV-SM456BT-E RAV-SM566BT-TR RAV-SM566BT-E RAV-SM456BT-TR RAV-SM806BT-E RAV-SM806BT-TR RAV-SM1106BT-TR RAV-SM1106BT-E RAV-SM1406BT-TR RAV-SM1606BT-TR RAV-SM1606BT-E RAV-SM1406BT-E RAV-SM406BT-TR

1 104
Download 104 pages 55.2 Kb
Page 28
Image 28

No.

8

Item

Outline of specifications

Remarks

 

 

 

Freeze preventive control

1) The cooling operation (including Dry operation) is

Tcj:

(Low temperature release)

performed as follows based on the detected

Indoor heat exchanger

 

temperature of Tc sensor or Tcj sensor.

 

sensor temperature

 

When [J] zone is detected for 6 minutes

 

 

(Following figure), the commanded frequency is

 

 

decreased from the real operation frequency.

 

 

After then the commanded frequency changes

 

 

every 30 seconds while operation is performed in

 

 

[J] zone.

 

 

 

 

In [K] zone, time counting is interrupted and the

 

 

operation is held.

 

 

 

 

When [ I ] zone is detected, the timer is cleared

 

 

and the operation returns to the normal operation.

 

 

If the commanded frequency becomes S0

 

 

because the operation continues in [J] zone, the

 

 

return temperature A is raised from 5°C to 12°C

 

 

until [ I ] zone is detected and the indoor fan

 

 

operates with [L] mode.

 

 

 

˚C

 

 

 

 

5

I

A

 

 

 

K

 

 

 

2

J

 

 

 

 

 

 

 

In heating operation, the freeze-preventive control

Tcn:

 

works if 4-way valve is not exchanged and the

Tc temperature when 5

 

following conditions are satisfied.

 

minutes elapsed after

 

(However the temperature for J zone dashing control

activation

 

is changed from 2°C to –5°C.)

 

Tc (n – 1):

 

<Conditions>

 

 

 

 

 

Tc temperature at start

 

• When c or d is established 5 minutes after

 

time

 

activation.

 

 

 

cTcn Tc (n – 1) – 5

dTcn < Tc (n – 1) – 1 and Tcn Ta < 5°C