Toshiba RAV-SM1406BT-E Item No. DN table Selection of function, Description, At shipment, 0000

Models: RAV-SM456BT-E RAV-SM566BT-TR RAV-SM566BT-E RAV-SM456BT-TR RAV-SM806BT-E RAV-SM806BT-TR RAV-SM1106BT-TR RAV-SM1106BT-E RAV-SM1406BT-TR RAV-SM1606BT-TR RAV-SM1606BT-E RAV-SM1406BT-E RAV-SM406BT-TR

1 104
Download 104 pages 55.2 Kb
Page 66
Image 66

Item No. (DN) table (Selection of function)

DN

Item

 

 

 

Description

 

 

 

 

 

 

 

 

At shipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01

Filter sign lighting time}

0000

: None

 

 

 

 

 

 

 

 

 

 

0002

: 2500H

 

 

 

 

0002

: 2500H (4-Way/Duct/Ceiling Type)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02

Dirty state of filter

0000

: Standard

 

0001 : High degree of dirt

 

0000

: Standard

 

 

 

 

 

 

 

 

 

 

(Half of standard time)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03

Central control address

0001

: No.1 unit

to

0064 : No.64 unit

 

 

 

0099

: Unfixed

 

 

 

 

0099

: Unfixed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

Heating suction temp shift

0000

: No shift

 

0001 : +1°C

 

 

 

 

 

0002

: +2°C

 

 

 

 

0002

: +2°C

to

0010 : –10°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Up to recommendation + 6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0F

Cooling only

0000

: Heat pump

 

0001 : Cooling only

 

 

 

0000

: Heat pump

 

 

 

 

 

 

(No display of [AUTO] [HEAT])

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

Type

0004

: Concealed duct type

0007 : Ceiling type

 

 

 

According to model type

 

 

0014

: Compact 4-way cassette type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

Indoor unit capacity

0000

: Unfixed

 

0006 :

40 type

 

 

 

According to capacity type

 

 

0007

: 45 type

 

0009 :

56 type

 

 

 

 

 

 

 

 

 

 

 

 

0012

: 80 type

 

0015 : 110 type

 

 

 

 

 

 

 

 

 

 

 

 

0017

: 140 type

 

0018 : 160 type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

Line address

0001

: No.1 unit

to

0030 : No.30 unit

 

 

 

0099

: Unfixed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

Indoor unit address

0001

: No.1 unit

to

0064 : No.64 unit

 

 

 

0099

: Unfixed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

Group address

0000

: Individual

 

0001 : Master of group

 

 

 

0099

: Unfixed

 

 

 

 

0002

: Follower of group

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19

Louver type

0000

: No louver

 

0001 : Swing only

 

 

 

According to model type

 

(Air direction adjustment)

0002

: 1-way

 

0003 : 2-way

 

 

 

 

 

 

 

 

 

 

 

 

 

None for concealed duct

0004

: 4-way

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1E

Temp difference of

0000

: 0 deg to

 

0010 :

10 deg

 

 

 

0003

: 3 deg (Ts±1.5)

 

automatic cooling/heating

(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)

 

 

 

 

 

 

 

 

mode selection COOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT, HEAT COOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

Auto restart after power

0000

: None

 

0001 : Auto restart

 

 

 

0000

: None

 

 

 

failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2A

Option

 

 

 

 

 

 

 

 

 

 

 

 

 

0002

: Default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2b

Thermo output selection

0000

: Indoor thermo ON

 

 

 

 

 

 

 

 

 

0000: Thermo. ON

 

(T10 e)

0001

: Output of outdoor comp-ON receiving

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2E

Option

 

 

 

 

 

 

 

 

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

Option

 

 

 

 

 

 

 

 

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31

Option

 

 

 

 

 

 

 

 

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

Sensor selection

0000

: Body TA sensor0001 :

Remote controller sensor

 

0000

: Body sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33

Temperature indication

0000

: °C (celsius)

 

0001 : °F (Fahrenheit)

 

 

 

0000

: °C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

Option

 

 

 

 

 

 

 

 

 

 

 

 

 

0003

: Default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5d

High ceiling selection

 

 

 

 

 

 

 

 

 

 

 

 

 

According to capacity type

 

(External static pressure

<Concealed Duct type>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

selection)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set data

0000

 

0001

 

0002

 

0003

 

0004

 

 

0005

 

0006

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External static

40 Pa

 

30 Pa

 

65 Pa

 

50 Pa

 

80 Pa

 

 

100 Pa

 

120 Pa

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To 3HP

 

 

 

4 to 6HP

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

(Factory

 

 

(Factory

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

default)

 

 

 

default)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The list above is when SW501-1 and SW501-2 is OFF.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 66 –

Page 66
Image 66
Toshiba RAV-SM1406BT-E Item No. DN table Selection of function, Description, At shipment, Concealed Duct type, Set data