Outline of specifications

Remarks

 

 

 

 

 

17

DC motor

1)

When the fan operation has started, positioning of

 

 

 

 

the stator and the rotor are performed.

 

 

 

 

(Moves slightly with tap sound)

 

 

 

2)

The motor operates according to the command from

 

 

 

 

the indoor controller.

 

 

Notes)

 

 

 

 

 

 

• When the fan rotates while the air conditioner stops

 

 

 

due to entering of outside air, etc, the air conditioner

 

 

 

may operate while the fan motor stops.

 

 

 

 

• When a fan lock is found, the air conditioner stops, and

Check code [P12]

 

an error is displayed.

 

 

 

 

 

 

• If static pressure of the used duct does not match with

 

 

 

the setup value of static pressure, which was decided

 

 

 

in the static pressure setting code No. [5D], the air

 

 

 

conditioner may stop or an error code may be displayed.

 

 

 

 

 

 

 

 

 

 

18 Self-clean

1)

When cooling operation mode (AUTO COOL, COOL, DRY) stopped, the following

operation

 

three self-clean operations are performed.

 

 

 

(Dry operation)

 

 

 

 

 

 

 

 

 

 

Compressor

Self-clean

FAN

Drain pump

 

 

 

 

 

 

 

 

ON period

operation period

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 to 10 min.

 

None

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 to 60 min.

 

1 hour

Fan (UL)

STOP

 

 

 

 

 

 

 

 

 

 

 

 

 

60 min. to

 

2 hours

 

 

 

 

 

 

 

 

 

 

 

 

 

2)

During operation of self-clean,

lights on the wired

And it is not also on the

 

 

remote controller screen. However the operation

wireless remote controller.

 

 

lamp (Green LED) goes off.

 

 

It is recognized as [STOP]

 

3)

To stop the self-clean operation, push twice the

from the remote monitor

 

 

[ON/OFF] button on the remote controller

 

side.

 

 

continuously. (Stop the operation as compressor ON

 

 

 

 

time in the table above: 10 minutes or below.)

 

 

 

4)

When the follower unit executes self-clean operation

 

 

 

 

in the group connection, the segment of

is

 

 

 

 

displayed on the wired remote controller screen via

 

 

 

 

master unit.

 

 

 

 

 

 

 

If self-clean operation is not used, set invalidity

 

 

 

 

(does not use) of the self-clean operation by

 

 

 

 

changing [0001 (At shipment) of CODE No. (DN)

 

 

 

 

[D3] to [0000].

 

 

 

 

 

To erase the display during operation of self-clean, change CODE No. [D4] from [0000: Display (At shipment)] to [0001: Non-display].

– 32 –

Page 32
Image 32
Toshiba RAV-SM1106BT-TR Outline of specifications, Remarks, conditioner may stop or an error code may be displayed