Toshiba RAV-SM806BT-E, RAV-SM406BT-TR E04 error, E10 error, Are wiring in indoor unit and

Models: RAV-SM456BT-E RAV-SM566BT-TR RAV-SM566BT-E RAV-SM456BT-TR RAV-SM806BT-E RAV-SM806BT-TR RAV-SM1106BT-TR RAV-SM1106BT-E RAV-SM1406BT-TR RAV-SM1606BT-TR RAV-SM1606BT-E RAV-SM1406BT-E RAV-SM406BT-TR

1 104
Download 104 pages 55.2 Kb
Page 47
Image 47

[E04 error]

NO

Does outdoor operate?

YES

Is group address setup of

NO

 

Check CODE No. [14].

 

 

 

 

 

 

remote controller correct?

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are wiring in indoor unit and

NO

 

 

1, 2, 3 inter-unit cables correct?

 

 

 

YES

 

 

 

 

 

 

 

 

 

Correct wiring and

inter-unit cables.

Are wirings of terminal blocks (1, 2, 3) wired to CN67 normal?

YES

Does the voltage

NO

Correct wiring of connector

and terminal blocks.

between 2 and 3 of the indoor unit NO inter-unit terminal blocks

(1, 2, 3) vary?

Check indoor P.C. board

(MCC-1631).

Defect Replace

Check indoor P.C. board.

Defect Replace

As shown in the following figure,

carry out measurement within 20 seconds after the power was turned on.

S5277G

Black

3

White

2

1

Terminal block

Check outdoor P.C. board.

Defect Replace

[E10 error]

YES

Is there no disorder of power supply?

NO

Check indoor control P.C. board

(MCC-1631).

Defect Replace

Check power supply voltage.

Correct lines.

Check and eliminate noise, etc.

– 47 –

Page 47
Image 47
Toshiba RAV-SM806BT-E, RAV-SM406BT-TR, RAV-SM1406BT-E, RAV-SM1606BT-E E04 error, E10 error, Are wiring in indoor unit and