UNIT LOUVER

[3] Writing the setting data to EEPROM

The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values.

Step 1 Push SET , CL and TEST buttons on the remote controller simultaneously for more than 4 seconds.

In the group control operation, the unit No. displayed for the first time is the header unit No.

At this time, the CODE No. (DN) shows “10 ”. Also, the fan of the indoor unit selected starts its operation and the swing operation starts if it has the louvers.

(The unit No. “ ” is displayed if the auto-address setting mode is interrupted in [2] step 2 a)

Step 2 Every time when button is pushed, the indoor unit No. in the group control operation are displayed in order.

(The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values.)

Specify the indoor unit No. with its P.C. board replaced to the P.C. board for indoor unit servicing.

(You cannot perform this operation if “ ” is displayed.)

Step 3 Select the CODE No. (DN) can be selected by pushing the /

• Set the indoor unit type and capacity.

The factory-set values shall be written to the EEPROM by changing the type and capacity.

1. Set the CODE No. (DN) to “10 ”. (without change)

2.

Select the type by pushing

/

buttons for the timer setting.

 

(For example, Concealed Duct standard type is set to “ 0004

”.

 

Refer to table 2)

 

 

 

 

 

3.

Push SET button.

 

 

 

 

 

 

(The operation completes if the setting data is displayed.)

 

4.

Change the CODE No. (DN) to “11 ” by pushing

/

 

 

buttons for the temperature setting.

 

 

 

5.

Select the capacity by pushing

/

buttons for the timer setting.

 

(For example, 80 Type is set to “ 0012

”. Refer to table 3)

 

button for the temperature setting.

<Fig. 1 RBC-AMT32E>

00 04 3- 3 10

6. Push SET button.

3 6 5 1

4 2

(The setting completes if the setting data are displayed.)

 

NOTE: Setting Concealed Duct standard type Indoor Unit model only

7.Using the set temperature / buttons, set “ CE ” to the CODE No. (DN).

8.Using the timer time / buttons, set the data. (0001)

9.Push SET buttons. ( The setting completes if the setting data are displayed.)

CAUTION

Don’t remove the materials.

No materials. The power I.C. (IC101) may break.

<Fig. 2>

10. Push the TEST button to return to the normal stop status.

(It takes approx. 1 min until the remote controller operation is available again.)

– 60 –