Toshiba RAV-SM806BT-TR Outline of specifications, Remarks, “8. SETUP AT LOCAL, Site And Others”

Models: RAV-SM456BT-E RAV-SM566BT-TR RAV-SM566BT-E RAV-SM456BT-TR RAV-SM806BT-E RAV-SM806BT-TR RAV-SM1106BT-TR RAV-SM1106BT-E RAV-SM1406BT-TR RAV-SM1606BT-TR RAV-SM1606BT-E RAV-SM1406BT-E RAV-SM406BT-TR

1 104
Download 104 pages 55.2 Kb
Page 33
Image 33

No.

Item

 

Outline of specifications

 

 

 

Remarks

 

 

 

 

 

 

19

Save operation

1)

Turn on SAVE button on the remote controller.

 

Carry out setting

 

 

2)

During operation of save operation,

lights on the

operation during stop of

 

 

 

wired remote controller.

 

 

 

the unit; otherwise the

 

 

3)

During save operation, the current release control is

unit stops operation.

 

 

For the setup operation,

 

 

 

performed with the restriction ratio set in EEPROM on

 

 

 

refer to

 

 

 

the outdoor unit.

 

 

 

 

 

 

 

 

 

“How to set contents of

 

 

4)

The restriction ratio can be set by keeping

SAVE

button

 

 

 

save operation” in

 

 

 

pushed for 4 seconds or more on the remote controller.

 

 

 

Sction

 

 

5)

When validating the save operation, the next operation

 

 

8. SETUP AT LOCAL

 

 

 

starts with save operation valid because contents are

SITE AND OTHERS”.

 

 

 

held even when operation stops, operation mode

 

 

 

 

 

changes or power supply is reset.

 

 

 

 

6)The restriction ratio can be set by changing the setup data of CODE No. (DN) [C2] in the range of 50 to 100% (every 1%, Setting at shipment: 75%).

20 8°C heating/Frost

1)

This functional is intended for the cold latitudes and

 

protective operation

 

performs objective heating operation

 

 

 

(8°C heating operation).

In a group connection,

 

2)

This function is valid only for combination with the

if there is even one

 

 

outdoor units.

combination with other

 

3)

Using the indoor CODE No. [D1] (1 bit), Valid/Invalid of

unit, “This function is not

 

provided.” is displayed.

 

 

this function is set up at the customer’s side.

 

 

 

The setup by CODE No. is Invalid [0]/Valid [1] and Invalid [0] has been set at the shipment.

4)This operation is the heating operation which sets 8°C

as the setup temperature of the target.

The setup temperature

5) This function starts operation by pushing temperature

jumps from [18] to [8].

 

button

during heating operation; besides by

 

pushing

button for 4 seconds or more after

 

temperature reached the minimum set temperature.

 

6)To stop/release this operation, select and execute one from the following operations.

c Push button:

Heating operation 18°C setting) continues.

d Push [START/STOP] button: Air conditioner stops.

(Heating 18°C operation at the next start)

e Push MODE :

Other operation mode is selected and the operation continues.

7)As the setup temperature is 8°C and the human heating is not targeted, the cold air discharge preventive control (Item 7) is made invalid to suppress the intermittent operation.

8)The settings of the air direction and air volume are changeable during this operation.

9)The indoor fan stops to protect the compressor for 2 minutes after start of heating operation (Thermo-ON) by this function.

– 33 –

Page 33
Image 33
Toshiba RAV-SM806BT-TR, RAV-SM406BT-TR Outline of specifications, Remarks, “8. SETUP AT LOCAL, Site And Others”, Save