9-3. Address Setup (Manual Setting from Remote Controller)

In case that addresses of the indoor units will be determined prior to piping work after wiring work

Set an indoor unit per a remote controller.

Turn on power supply.

(Example of 2-lines wiring)

(Real line: Wiring, Broken line: Refrigerant pipe)

Outdoor

Outdoor

1

2

3

1

2

3

 

1

2

3

 

Indoor

 

A B

 

 

Line address 1

 

 

 

Indoor unit address 1

 

 

1 Push SET + CL + TEST buttons

Group address 1

 

 

A B

 

simultaneously for 4 seconds or more.

1 2 3

Indoor

A B

1

2

2

1 2 3

Indoor

A B

1

3

2

1 2 3

Indoor

A B

2

1

2

1 2 3

Indoor

A B

2

2

2

2 (Line address)

Using the temperature setup / buttons, set 12 to the CODE No.

Remote controller

For the above example, perform setting by connecting singly the wired remote controller without remote controller inter-unit wire.

3

 

 

 

 

 

Group address

 

 

Using timer time

/

buttons, set the line address.

Individual

: 0000

 

Header unit

: 0001

In case of group control

4

 

 

 

 

 

Follower unit : 0002

Push SET button. (OK when display goes on.)

 

 

 

 

5

(Indoor unit address)

 

/

buttons, set 13 to the CODE No.

 

 

Using the temperature setup

 

6

Using timer time

/

buttons, set 1 to the line address.

 

 

 

7

Push SET button. (OK when display goes on.)

 

 

 

8

(Group address)

 

 

/

buttons, set 14 to the CODE No.

 

 

Using the temperature setup

 

9

Using timer time

/

buttons, set 0000 to Individual, 0001 to Header unit, and 0002 to

 

Folloer unit.

 

 

 

 

 

 

 

10 Push

11 Push

SET

TEST

button. (OK when display goes on.)

button.

Setup completes. (The status returns to the usual stop status.)

TEMP.

ON / OFF

2, 5, 8

END 11

1

<Operation procedure>

 

TIMER SET

 

TIME

FILTER

SET CL

RESET TEST

FAN MODE

SAVE VENT

SWING/FIX UNIT LOUVER

3, 6, 9 4, 7, 10

1 2 3 4 5 6 7 8 9 10 11 END

– 81 –

Page 81
Image 81
Toshiba RAV-SM1606BT-TR, RAV-SM406BT-TR 2, 5, 3, 6, 9 4, 7, 1 2 3 4 5 6 7 8 9 10 11 END, button. OK when display goes on