Toshiba RAV-SM806BT-TR, RAV-SM406BT-TR Check code E01 error, E09 error, Are 2 header units set in

Models: RAV-SM456BT-E RAV-SM566BT-TR RAV-SM566BT-E RAV-SM456BT-TR RAV-SM806BT-E RAV-SM806BT-TR RAV-SM1106BT-TR RAV-SM1106BT-E RAV-SM1406BT-TR RAV-SM1606BT-TR RAV-SM1606BT-E RAV-SM1406BT-E RAV-SM406BT-TR

1 104
Download 104 pages 55.2 Kb
Page 46
Image 46

6-3. Diagnostic Procedure for Each Check Code (Indoor Unit)

Check code

[E01 error]

Is inter-unit cable of A and B normal?

YES

Is there no disconnection or

contact error of connector on harness from terminal block of indoor unit?

NO

NO

Is group control operation?

YES

Is power of all indoor units turned on?

YES

Is power supplied to remote controller?

AB terminal: Approx. DC18V

YES

Are 2 remote controllers set

without header unit?

NO

NO

YES

NO

NO

YES

Correct inter-unit cable

of remote controller

Correct connection of connector.

Check circuit wiring.

Check power connection of indoor unit.

(Turn on power again.)

Check indoor P.C. board (MCC-1631).

Defect Replace

Correct a header unit/a follower unit. (Remote controller address connector)

Check remote controller P.C. board.

Defect Replace

[E09 error]

Are 2 header units set in

YES

2 remote controllers?

 

NO

 

Correct as a header unit

and a follower unit.

Check remote controller P.C. board.

Defect Replace

– 46 –

Page 46
Image 46
Toshiba RAV-SM806BT-TR, RAV-SM406BT-TR, RAV-SM1406BT-E Check code E01 error, E09 error, Are 2 header units set in