15 TROUBLESHOOTING

MELSEC-Q

Classification

Error

Error name

 

 

Error

Operation status at error occurrence

 

of errors

code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The near-point dog signal is turned

 

 

 

203

Dog detection timing

OFF during the deceleration from an

 

 

 

 

fault

OPR speed to a creep speed by the

 

 

 

 

 

near-point dog machine OPR.

The system stops with the setting

 

 

 

 

 

 

 

 

 

 

 

 

 

The zero signal is turned OFF during

(deceleration stop/sudden stop) of the

 

 

 

OP detection timing

detailed parameter 2 Sudden stop

 

 

204

the deceleration from an OPR speed

selection (stop group 3).

 

 

fault

to a creep speed by the stopper

(Note that the deceleration stop only

 

 

 

 

method 2)-OPR.

occurs during the manual pulse

 

 

 

 

 

 

 

 

 

generator operation.)

 

 

 

 

A dwell time is passed during the

 

 

 

 

 

 

205

Dwell time fault

deceleration from a creep speed to a

 

 

 

OPR speed by the stopper method

 

 

 

 

 

 

 

 

 

 

1)-OPR.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In the count method 1 and 2

 

 

 

 

Count method

machine OPR, a parameter "Setting

 

 

 

 

of movement amount after near-

 

 

OPR

206

movement amount

The machine OPR is not started.

 

point dog ON" is smaller than a

 

 

fault

 

 

 

 

distance necessary for deceleration

 

 

 

 

 

 

 

 

 

 

stop from an OPR speed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The OPR request flag is turned ON

 

 

 

207

OPR request ON

when a fast-OPR is started

The fast OPR is not started.

 

 

 

 

(positioning start No. 9002).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPR restart not

The restart command is turned ON

 

 

 

209

after the machine OPR is stopped

The restart is not carried out.

 

 

 

possible

using a stop signal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

213

ABS transmission

 

 

 

 

 

 

 

 

time

Communication cannot be carried

 

 

 

 

 

 

 

 

 

 

out with the servo-amplifier using an

The absolute position restoration is

 

 

214

ABS transmission

absolute position restoration

not carried out.

 

 

instruction.

 

 

 

 

SUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outside JOG speed

At the time of JOG starting, the JOG

The JOG operation is not carried out

 

 

300

range

speed comes out of a specified

when the JOG speed is outside the

 

 

 

 

range.

setting range at the time of JOG start.

 

JOG inching

 

 

 

 

 

 

 

The inching operation is not carried

 

 

301

Inching movement

The inching movement amount

out when the inching movement

 

 

amount error

exceeds the JOG speed limit.

amount exceeds a JOG speed limit at

 

 

 

 

 

 

 

 

 

the time of inching start.

 

 

 

 

 

 

 

 

 

 

The condition data No. is outside the

 

 

 

 

 

setting range when a block using the

 

 

Positioning

500

Illegal condition data

condition data is started by a special

The operation is terminated.

 

operation

 

No.

starting (conditional start, wait start,

 

 

 

 

 

simultaneous start, FOR (condition)).

 

 

 

 

 

(1

 

Condition data No.

 

10)

 

 

 

 

 

 

 

 

 

15 - 8

Page 612
Image 612