9 MAJOR POSITIONING CONTROL
(4) If the value set in " Da.6 Positioning address/movement amount" is outsidethe software stroke limit ( Pr.12 ,Pr.13 ) setting range, an error "Softwarestroke limit +, – (error code: 507 or 508)" will occur at the posit ioning start, andthe operation will not start.(5) An error (error code: 507 or 508) will occur if the new current value is outsidethe software stroke limit range.
Positioning data setting examples
The following table shows the setting examples when " current val ue changing" isset in the positioning data No. 1 of axis 1.
Setting item Setting example Setting details
Da.1 Operation
pattern Positioning complete
Set "Positioning complete" assuming that
the next positioning data will be executed.
("Continuous path control" cannot be set by
current value change.)
Da.2 Control
system Current value changing Set the current value changing.
Da.3 Acceleration
time No. Setting not required (Setting value is
ignored.)
Da.4 Deceleration
time No. Setting not required (Setting value is
ignored.)
Da.5 Axis to be
interpolated Setting not required (Setting value is
ignored.)
Da.6
Positioning
address/
movement
amount
10000.0 m
Set the address to which address change is
desired. (Assuming that the " Pr.1 Unit
setting" is set to "mm".)
Da.7 Arc address Setting not required (Setting value is
ignored.)
Da.8 Command
speed Setting not required (Setting value is
ignored.)
Da.9 Dwell time Setting not required (Setting value is
ignored.)
Axis 1
positioning
data No. 1
Da.10 M code 10
Set this when other sub operation
commands are issued in combination with
the No. 1 positioning data.
Refer to Section 5.3 "List of positioning data" for information on the setting details.