APPENDICES

Appendix 11 Positioning control troubleshooting

MELSEC-Q

Trouble type

Questions/Trouble

 

 

 

Remedy

No.

 

 

The PLC CPU power was turned OFF or the PLC CPU

 

 

 

was reset, etc., during flash ROM writing, which deleted

 

 

Display reads "FFFFH" when a

the data in the flash ROM.

 

 

parameter is read with GX

Initialize the parameters, and reset the required

1

 

Configurator-QP.

parameters.

 

 

 

(Refer to Section 13.2 "Parameter initialization function"

 

Parameter

 

for details.)

 

 

Set the "

 

Parameter initialization request" to "1".

 

 

How can the parameters be

Cd.2

 

 

returned to their initial values

(Refer to Section 13.2 "Parameter initialization function"

2

 

(default values)?

 

 

for details.)

 

 

 

 

 

A parameter error occurred

The parameter may have been overwritten in the

 

 

although the parameter was set

sequence program.

3

 

correctly by GX Configurator-QP.

Review the sequence program.

 

 

 

 

 

 

 

 

 

 

 

 

In the QD75, deceleration stops are executed after the

 

 

The machine overruns if operating

machine exceeds hardware stroke limit range. Because of

 

 

at high speeds when the hardware

this, more time is required for the deceleration stop as the

4

 

stroke limit range is exceeded.

speed increases, and the overrun becomes larger.

 

 

(The deceleration time becomes shorter at lower speeds,

 

 

 

 

 

 

so the overrun becomes smaller.)

 

Hardware stroke limit

 

Use a "JOG operation", " Inching operation" or "Manual

 

 

pulse generator operation" to return the machine to inside

 

 

When the machine exceeded the

the hardware stroke limit range.

 

 

hardware stroke limit range,

(When the hardware stroke limit range is exceeded,

 

 

positioning toward inside the range

positioning will not start toward inside the range even

5

 

was started, but the machine did

when so commanded. Once the range is exceeded, a

 

 

not start.

return to inside the range can only be executed using a

 

 

 

"JOG operation", "Inching operation" or "Manual pulse

 

 

 

generator operation".)

 

 

 

 

 

 

 

 

 

 

 

 

 

Exactly one rotation is required,

 

 

 

 

 

 

 

 

 

Degree

but the setting range for a "degree"

Designate "360.000" in the INC control.

6

unit setting is "0 to 359.999...".

The motor will make exactly one rotation.

 

Won't the rotation deviate by

 

 

 

 

 

 

 

 

 

 

 

 

"0.00...1"?

 

 

 

 

 

 

 

 

 

 

If the "movement amount per

Set "movement amount per pulse" in the QD75 using the

 

 

pulse" is calculated as written in

 

 

 

 

 

 

 

 

 

Movement amount

three parameter values of

Pr.2

to

Pr.4

.

 

the manual, settings smaller than

7

per pulse

Try setting the values following the explanations for each

the basic parameter setting range

 

 

 

 

cannot be carried out.

parameter.

 

 

 

 

 

 

 

 

 

 

 

 

 

Will an override setting value

It will be valid.

8

 

written before starting be valid?

 

 

 

 

 

 

 

 

 

 

 

During path control, will the

 

 

 

 

 

 

 

 

 

Override

override still be valid after the point

It will still be valid.

9

is passed?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set the "

 

 

Positioning operation speed override" to

 

 

How can the override be

Cd.13

10

 

canceled?

"100".

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Appendix - 92