11 MANUAL CONTROL

MELSEC-Q

11.4.3 Setting the required parameters for manual pulse generator operation

The "Parameters" must be set to carry out manual pulse generator operation.

The following table shows the setting items of the required parameters for carrying out manual pulse generator operation. When only manual pulse generator operation will be carried out, no parameters other than those shown below need to be set. (Use the initial values or setting values within a range where no error occurs for trouble-free operation.)

Parameters

 

 

 

 

Setting item

Setting requirement

Factory-set initial value

 

 

 

 

(setting details)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.1

 

 

Unit setting

 

 

 

3 (pulse)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.2

 

 

No. of pulses per rotation (Ap) (Unit: pulse)

 

 

 

20000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.3

 

 

Movement amount per rotation (Al) (Unit: pulse)

 

 

 

20000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.4

 

 

Unit magnification (Am)

 

 

 

1 (1-fold)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.5

 

 

Pulse output mode

 

 

 

1 (CW/CCW mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 (current value increases by

 

Pr.6

 

 

Rotation direction setting

 

 

 

forward run pulse output)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.11

Backlash compensation amount (Unit: pulse)

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.12

Software stroke limit upper limit value (Unit: pulse)

 

 

 

2147483647

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.13

Software stroke limit lower limit value (Unit: pulse)

 

 

 

–2147483648

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.14

Software stroke limit selection

 

 

 

0 (current feed value)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.15

Software stroke limit valid/invalid setting

 

 

 

0 (valid)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.17

Torque limit setting value (Unit: %)

 

 

 

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 (Manual pulse generator

 

Pr.22

 

Input signal logic selection

 

 

 

 

 

 

 

 

input is negative logic.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 (Pulse output to drive unit is

 

Pr.23

 

Output signal logic selection

 

 

 

 

 

 

 

 

negative logic.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 (4 times multiplication of A

 

Pr.24

 

Manual pulse generator input selection

 

 

 

 

 

 

 

 

phase/B phase)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

:Setting always required.

:Set according to requirements (Leave set to the initial value when not used.)

REMARK

Parameter settings work in common for all control using the QD75. When carrying out other control ("major positioning control", "high-level positioning control", "OPR positioning control"), the respective setting items must also be matched and set.

Parameters are set for each axis. But Pr.22 Manual pulse generator input logic

(b8),

Pr.24

is set only for axis 1. (The setting for axes 2,3, and 4 is ignored.)

Refer to Chapter 5 "Data Used for Positioning Control" for setting details.

11 - 32

Page 472
Image 472
Mitsubishi Electronics QD75P, QD75D user manual Torque limit setting value Unit % 300, Input signal logic selection