12 CONTROL SUB FUNCTIONS

MELSEC-Q

(3)Since the upper and lower limit values of the positioning address calculated are outside of the range of Condition 2, use the positioning address within the positioning range of Condition 2 (-2147483648 (m) to 2147483647 (m)).

 

 

 

 

Unit: m

 

 

OP

 

 

-241591910.4

-214748364.8

0

214748364.7

241591909.5

 

 

Usable range in absolute

 

 

Setting disallowed

position detection system

Setting disallowed

2.Concept for the unit of degree

The positioning address is within the range 0° to 359.99999° at the position to which a machine OPR was made.

When the OP position is not 0° , the range is also 0° to 359.99999° .

For positioning in the same direction, control from maximum to minimum (for address increase: 359.99999° to 0° /for address decrease: 0° to 359.99999° ) cannot be exercised. (See below)

OP

359.99999

0

Unusable in absolute position detection system.

Current value cannot be restored properly at power supply on or resetting

 

 

Unusable in absolute position

 

 

 

 

detection system.

359.99999

 

Current value cannot be restored

 

 

properly at power-on or reset.

0

Usable range in absolute position detection system (0 ~ 359.99999)

When positioning is to be used in the absolute position detection system, set the upper and lower limit values of the software stroke limit within the range 0° to 359.99999° .

12 - 57

Page 533
Image 533