15 TROUBLESHOOTING

MELSEC-Q

Classification

Warning

Warning name

Warning

Operation status at warning

 

of warnings

code

occurrence

 

 

 

 

 

 

 

 

 

 

 

 

Outside manual

The manual pulse generator 1 pulse

• When input magnification is set at

 

Manual pulse

 

pulse generator

101 or higher: Re-set to 100.

 

401

input magnification is set at 0 or 101

 

generator

input magnification

• When input magnification is set at 0:

 

 

 

range

or higher.

Re-set to 1.

 

 

 

 

 

 

500

Deceleration/stop

The speed change request is issued

The speed change is not carried out.

 

 

 

speed change

during deceleration stop.

 

 

 

 

 

 

 

 

Positioning

operation

 

 

The new value exceeds the speed

• The speed is controlled with the

 

Speed limit value

speed limit value.

501

limit value when the speed is

over

• The "speed limiting flag" is turned

 

changed during operation.

 

 

ON.

 

 

 

503

M code ON signal

The M code ON signal is turned ON

Continue executing the positioning

ON start

when the positioning data is

data.

 

executed.

 

 

 

 

No operation

In the positioning by block starting,

 

505

the 50th point of the positioning start

The operation is terminated.

termination setting

 

data is set to CONTINUE.

 

 

 

 

 

506

FOR to NEXT nest

FOR to NEXT is nested.

 

 

construction

 

 

 

Speed-position

The switching signal for speed-

The operation is continued.

 

switching (during

position switching control (INC

508

 

acceleration) signal

mode) is turned ON during

 

 

 

 

ON

acceleration.

 

 

 

 

• When a command speed is

 

 

 

changed:

 

 

• At a continuous operation interrupt

Change to a value as near a new

 

 

request, the distance required

speed value as possible.

 

 

deceleration stop is not long

• When a target position is changed:

509

Insufficient

enough.

Adjust the speed to a value as

remaining distance

• At a speed change request, the

near the command speed as

 

 

 

remaining distance is shorter than

possible, and then change to a

 

 

the distance required for speed

target position.

 

 

change.

(When the operation pattern is a

 

 

 

continuous path control, ignore the

 

 

 

operations stated above.)

 

 

 

 

 

 

Code 1 is set for the step start

 

511

Step not possible

information when the step is outside

The step will not start.

 

 

standby.

 

 

Illegal external

The detailed parameter 2 "External

Even if the external command signal

512

command function selection" setting

is turned ON, the system will not

command function

 

 

range is exceeded.

perform anything.

513

Insufficient

The movement amount is not large

The system stops immediately after it

movement amount

enough for automatic deceleration.

reaches the positioning address.

 

15 - 34

Page 638
Image 638
Mitsubishi Electronics QD75P Occurrence Outside manual, When input magnification is set at, Input magnification, Over