15 - 22
MELSEC-Q
15 TROUBLESHOOTING
Classification
of errors Error
code Error name Error Operation status at error occurrence
Positioning
operation 546 Illegal setting of ABS
direction in unit of
degree
The setting value of ABS direction in
the unit of degree is as follows.
• Set outside the setting range.
• A figure other than "0" is set when
the software stroke limit is valid.
At start: The system will not operate.
During operation:
The system decelerates to a
stop.
(Note that, in the continuous
positioning control and continuous
path control, the system continues
operating with the setting set at the
time of start even if the setting is
changed during the operation.)
800 Hold error In the PLC CPU unit parameter
"Output at error stop", the setting for
QD75 is "Hold".
At start: The system will not operate.
During operation:
The system stops with the
setting (deceleration
stop/sudden stop) of the
detailed parameter 2 sudden
stop selection
(stop group 3).
(Note that the deceleration stop only
occurs during the manual pulse
generator operation.)
801 Flash ROM write
error Data is not written to the flash ROM.
802 Flash ROM sum
check error While data is written to the flash
ROM, the power is turned OFF.
At start: The system will not operate.
803 PLC CPU error The PLC CPU resulted in an error.
804 Dedicated instruction
error
• The ABRST instruction is
executed with the status set to
other than 0.
• The PSTRT instruction is
executed with the start No. set to
other than 10 to 600, 7000 to 7004
and 9001 to 9004.
• The TEACH instruction is
executed with the teaching data
selection set to other than 0 and 1.
• The TEACH instruction is
executed with the positioning data
No. set to other than 1 to 600.
• The instruction of a non-existent
axis is specified by the ABRST ,
PSTRT or TEACH instruction.
At start: The system will not operate.
During operation:
The system stops with the
setting (deceleration
stop/sudden stop) of the
detailed parameter 2 sudden
stop selection
(stop group 3).
(Note that the deceleration stop only
occurs during the manual pulse
generator operation.)
805 Flash ROM write
number error
Data is written to the flash ROM
continuously 25 times or more from
the sequence program.
I/F
806 Dedicated instruction
I/F error Mismatching occurs between the
PLC CPU and QD75.
At start: The system will not operate.