15 TROUBLESHOOTING

MELSEC-Q

Classification

Error

Error name

Error

Operation status at error occurrence

 

of errors

code

 

 

 

 

 

 

 

 

 

 

 

 

954

Deceleration time 2

The set range of the detailed

 

 

 

setting error

parameter 2 "Deceleration time 2" is

 

 

 

 

 

outside the setting range.

 

 

 

 

Deceleration time 3

The set range of the detailed

 

 

 

955

parameter 2 "Deceleration time 3" is

 

 

 

 

setting error

outside the setting range.

 

 

 

 

 

 

 

 

 

 

• The set range of the detailed

 

 

 

 

 

parameter 2 "JOG speed limit value"

 

 

 

956

JOG speed limit

is outside the setting range.

 

 

 

 

 

 

 

 

value error

• The set range of the detailed

 

 

 

 

 

parameter 2 "JOG speed limit value"

 

 

 

 

 

exceeds the speed limit.

 

 

 

 

 

 

 

 

 

 

JOG acceleration

The set range of the detailed parameter

 

 

 

957

time selection setting

2 "JOG acceleration time selection

 

 

 

 

error

setting" is outside the setting range.

 

 

 

 

JOG deceleration

The set range of the detailed parameter

 

 

 

958

time selection setting

2 "JOG deceleration time selection

 

 

 

 

error

setting" is outside the setting range.

At start: The system will not

 

 

 

 

 

 

 

 

Acceleration/

The set range of the detailed

operate.

 

 

959

deceleration process

parameter 2 "Acceleration/deceleration

During operation:

 

 

selection setting

process selection setting" is outside

The system stops with the

 

 

 

error

the setting range.

setting (deceleration

 

 

 

S-pattern ratio

The set range of the detailed

stop/sudden stop) of the

 

 

960

parameter 2 "S-pattern ratio" is outside

detailed parameter 2

 

 

setting error

 

Parameter

Sudden stop selection

 

 

 

the setting range.

 

 

 

 

 

(stop group 3).

 

 

 

Illegal sudden stop

The set range of the detailed

 

 

(Note that the deceleration stop only

 

 

961

parameter 2 "Sudden stop deceleration

 

 

 

deceleration time

time" is outside the setting range.

occurs during the manual pulse

 

 

 

 

 

 

 

 

 

generator operation.)

 

 

 

 

The set range of the detailed

 

 

 

 

 

 

962

Stop group 1 sudden

parameter 2 "Stop group 1 sudden

 

 

 

stop selection error

stop selection" is outside the setting

 

 

 

 

 

range.

 

 

 

 

 

 

 

 

 

 

 

The set range of the detailed

 

 

 

963

Stop group 2 sudden

parameter 2 "Stop group 2 sudden

 

 

 

stop selection error

stop selection" is outside the setting

 

 

 

 

 

range.

 

 

 

 

 

The set range of the detailed

 

 

 

964

Stop group 3 sudden

parameter 2 "Stop group 3 sudden

 

 

 

 

stop selection error

stop selection" is outside the setting

 

 

 

 

 

range.

 

 

 

 

Outside allowance

The set range of the detailed

 

 

 

 

parameter 2 "Allowance circular

 

 

 

966

circular interpolation

 

 

 

 

error width

interpolation error width" is outside the

 

 

 

 

setting range.

 

 

 

 

 

 

 

 

 

External command

The set range of the detailed

 

 

 

 

parameter 2 "External command

 

 

 

967

function selection

 

 

 

function selection" is outside the

 

 

 

 

error

 

 

 

 

setting range.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The set range of the OPR basic

The QD75 READY signal (X0) is not

 

 

980

OPR method error

parameter "OPR method" is outside

 

 

turned ON.

 

 

 

 

the setting range.

 

 

 

 

 

 

 

 

 

 

 

 

15 - 28

Page 632
Image 632
Mitsubishi Electronics QD75P, QD75D user manual Detailed parameter Setting error, Circular interpolation Error width