10 - 25
MELSEC-Q
10 HIGH-LEVEL POSITIONING CONTROL
Start time chart
The following chart shows a time chart in which the positioning data No. 1, 2, 10,11, and 12 of axis 1 are continuously executed as an example.(1) Block start data setting example
Axis 1 block
start data Da.11
Shape
Da.12
Start data No.

Da.13

Special start
instruction

Da.14

Parameter
1st point 1: Continue 1 0: Block start
2nd point 0: End 10 0: Block start
(2) Positioning data setting example
Axis 1 position-
ing data No. Da.1
Operation pattern
1 11: Continuous path control
2 00: Positioning complete
10 11: Continuous path control
11 11: Continuous path control
12 00: Positioning complete
(3) Start time chart
[Y10]
PLC READY signal
QD75 READY signal
[X10]
[XC]
Positioning complete signal
V
t
Error detection signal
Positioning data No.
Dwell time
12(00)
Operation pattern
1(11)
1st point [buffer memory address 26000]
2nd point [buffer memory address 26001]
11(11)
10(11)
2(00)
7000
1
-32767
10
(8001H)
(000AH)
Cd.3 Positioning start No.
Cd.4 Positioning start point No.
Positioning start signal
[X0]
Start complete signal
BUSY signal
[X8]
[X14]
[Y0]
Dwell time
Fig. 10.3 Start time chart for high-level posi tioning control (block start)