12CONTROL SUB FUNCTIONS

12.7.2 Skip function

MELSEC-Q

The "skip function" is used to stop (deceleration stop) the control of the positioning data being executed at the time of the skip signal input, and execute the next positioning data.

A skip is executed by a skip command ( Cd.37 Skip command) or external command

signal.

The "skip function" can be used during control in which positioning data is used.

The details shown below explain about the "skip function".

[1]Control details

[2]Precautions during control

[3]Setting the skip function from the PLC CPU

[4]Setting the skip function using an external command signal

[1]Control details

The following drawing shows the skip function operation.

Positioning start signal

ON

 

 

OFF

 

 

[Y10, Y11, Y12, Y13]

 

 

BUSYsignal

ON

 

 

OFF

 

 

[XC, XD, XE, XF]

 

 

 

 

 

ON

Positioning complete signal

OFF

 

 

[X14, X15, X16, X17]

V

 

 

 

 

 

Positioning

 

 

t

 

 

 

 

Deceleration by

 

Start of the

 

 

next positioning

 

skip signal

ON

Skip signal

 

OFF

 

 

Fig. 12.37 Operation when a skip signal is input during positioning control

[2]Precautions during control

(1)If the skip signal is turned ON at the last of an operation, a deceleration stop will occur and the operation will be terminated.

(2)When a control is skipped (when the skip signal is turned ON during a control), the positioning complete signals (X14, X15, X16, X17) will not turn ON.

(3)When the skip signal is turned ON during the dwell time, the remaining dwell time will be ignored, and the next positioning data will be executed.

(4)When a control is skipped during interpolation control, the reference axis skip signal is turned ON. When the reference axis skip signal is turned ON, a deceleration stop will be carried out for every axis, and the next reference axis positioning data will be executed.

(5)The M code ON signals (X4, X5, X6, X7) will not turn ON when the M code output is set to the AFTER mode (when "1: AFTER mode" is set in " Pr.18

M code ON signal output timing").

(In this case, the M code will not be stored in " Md.25 Valid M code".)

(6)The skip cannot be carried out by the speed-position and position-speed switching control. It is processed in the same manner as in the speed control.