13 COMMON FUNCTIONS

13.4 External I/O signal logic switching function

MELSEC-Q

This function switches the signal logic according to the external equipment connected to the QD75.

For the system in which drive unit READY with b-contact, upper limit switch, and lower limit switch are not used, the parameter logic setting can be controlled without wiring if it is changed to a "positive logic".

When the drive unit READY, upper limit switch, and lower limit switch are used, ensure to use them with b-contact.

The details shown below explain about the "External I/O signal logic switching function".

[1]Parameter setting details

[2]Precautions on parameter setting

 

 

[1]

Parameter setting details

 

 

 

 

 

 

 

 

 

 

To use the "External I/O signal logic switching function", set the parameters

 

 

 

 

 

shown in the following table.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting item

 

 

 

Setting details

 

Factory-set

Buffer memory address

 

 

 

 

 

 

 

initial value

Axis 1

Axis 2

Axis 3

Axis 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Selection of logic of signals input from external source to

 

 

 

 

 

 

 

 

 

 

QD75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b0

 

Lower limit

 

 

 

 

 

 

 

 

 

 

 

 

b1

 

Upper limit

 

 

 

 

 

 

 

 

 

 

 

 

b2

 

Drive unit

 

 

 

 

 

 

 

 

 

 

 

 

 

READY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0: Negative logic,

 

 

 

 

 

 

 

 

 

 

 

b3

 

Stop signal

 

 

 

 

 

 

 

 

Input signal logic

 

 

 

1: Positive logic

 

 

 

 

 

 

Pr.22

 

 

 

b4

 

External

0

31

181

331

481

 

 

 

selection

 

 

 

command signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b5

 

Zero signal

 

 

 

 

 

 

 

 

 

 

 

 

b6

 

Near-point signal

 

 

 

 

 

 

 

 

 

 

 

 

b7

 

Unused

Set "0".

 

 

 

 

 

 

 

 

 

 

 

b8

 

Manual pulse

0: Negative logic,

 

 

 

 

 

 

 

 

 

 

 

 

generator input

1: Positive logic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b9 to b15

 

Unused

Set "0".

 

 

 

 

 

 

 

 

 

 

• Selection of logic of signals output from QD75 to external

 

 

 

 

 

 

 

 

 

 

source

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b0

 

Command pulse

0: Negative logic,

 

 

 

 

 

 

 

 

Output signal logic

 

 

signal

1: Positive logic

 

 

 

 

 

 

Pr.23

 

 

 

 

0

32

182

332

482

 

 

selection

 

 

b1 to b3

 

Unused

Set "0".

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b4

 

Deviation counter

0: Negative logic,

 

 

 

 

 

 

 

 

 

 

 

 

clear signal

1: Positive logic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b5 to b15

 

Unused

Set "0".

 

 

 

 

 

Refer to Section 5.2 "List of parameters" for the information on detail settings.

[2]Precautions on parameter setting

(1)The external I/O signal logic switching parameters are validated when the PLC READY signal [Y0] is turned OFF to ON. (The logic is negative right after power-on.)

(2)If each signal logic is set erroneously, the operation may not be carried out correctly.

Before setting, check the specifications of the equipment to be used.