6 - 28

MELSEC-Q
6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL
Starting conditions

To start the control, the following conditions must be satisfied.

The necessary start conditions must be incorporated in the sequence pr ogram so

that the control is not started when the conditions are not satisfied.

Device
Signal name Signal state Axis 1 Axis 2 Axis 3 Axis 4
PLC READY signal ON PLC CPU preparation completed Y0
QD75 READY signal ON QD75 preparation completed X0
Synchronization flag ON QD75 buffer memory
Accessible X1
Axis stop signal OFF Axis stop signal is OFF. Y4 Y5 Y6 Y7
M code ON signal OFF M code ON signal is OFF. X4 X5 X6 X7
Error detection signal OFF No error is present. X8 X9 XA XB
BUSY signal OFF BUSY signal is OFF. XC XD XE XF
Interface
signal
Start complete signal OFF Start complete signal is OFF. X10 X 11 X12 X13
Drive unit READY signal ON Drive unit preparation completed
Stop signal OFF Stop signal is OFF.
Upper limit (FLS) ON Within limit range
External
signal
Lower limit (RLS) ON W ithin limit range
: When the synchronous setting of the PLC CPU is made in the nonsynchronous mode, this must be
provided as an interlock.
When it is made in the synchronous mode, no interlock must be provided in the program because the
flag is turned ON when calculation is run on the PLC CPU.