8 OPR CONTROL

MELSEC-Q

Restrictions

(1) Always limit the servomotor torque after the "

Pr.47

Creep speed" is reached. If the

torque is not limited, the servomotor may fail when the machine presses against the stopper. (Refer to Section 12.4.2 "Torque limit function".)

(2)Use an external input signal as the zero signal.

(3)The OPR retry function cannot be used in "stopper stop method 3)".

Precautions during operation

(1)If the zero signal is input before the workpiece stops at the stopper, the workpiece will stop at that position, and that position will become the OP.

At this time an error will not occur.

V

Pr. 47 Creep speed

Stops at stopper

t

Zero signal

 

 

Valid torque limit range

Torque limit

 

 

ON

Machine OPR start

OFF

(Positioning start signal)

 

 

ON

OPR request flag

OFF

[ Md.31 Status : b3]

 

 

ON

OPR complete flag

OFF

 

[ Md.31 Status : b4]

 

Deviation counter clear output

 

Pr.55 Deviation counter clear signal output time

Md.26 Axis operation status Standing by

In OPR

 

 

 

 

Md.34 Movement amount Inconsistent

0

after near-point dog ON

 

 

 

 

Md.20 Current feed value

 

 

 

 

Inconsistent

Value the machine moved is stored

Machine feed value

 

 

 

 

 

 

 

 

Standing by

OP address

Fig. 8.11 When the zero signal is input before the stop at the stopper

(2)When a machine OPR is stopped with the stop signal, perform a machine OPR again. If the restart command is turned ON after a stop with the stop signal, an error "OPR restart not possible" (error code: 209) occurs.

8 - 15

Page 293
Image 293
Mitsubishi Electronics QD75D, QD75P user manual Restrictions, Standing by OP address