5 DATA USED FOR POSITIONING CONTROL

MELSEC-Q

Da.10

M code (or condition data No./No. of LOOP to LEND repetitions)

Set an "M code", a "condition data No. ", or the "number of LOOP to LEND

repetitions" depending on how the "

Da.2

Control system" is set.

If a method other than "JUMP instruction" and "LOOP" is selected as the

"Da.2 Control system"

............... Set an "M code".

If no "M code" needs to be output, set "0" (default value).

If "JUMP instruction" or "LOOP" is selected as the " Da.2 Control system"

............... Set the "condition data No." for JUMP.

0 : Unconditional JUMP to the positioning data specified by Da.9 .

1 to 10 : JUMP performed according to the condition data No. specified (a number between 1 and 10).

Make sure that you specify the number of LOOP to LEND repetitions by a number other than "0". The "Control system LOOP setting error" will occur if you specify "0". (error code: 545)

The condition data specifies the condition for the JUMP instruction to be executed.

(A JUMP will take place when the condition is satisfied.)

[Table 1]

 

 

 

 

 

 

 

Value set with peripheral device

 

Value set with sequence program

 

 

 

 

 

Pr.1

setting value

 

 

 

 

 

(unit)

 

 

(unit)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 : mm

 

0.01 to 20000000.00 (mm/min)

 

1 to 2000000000 (10-2mm/min)

 

 

 

 

 

1 : inch

 

0.001 to 2000000.000 (inch/min)

 

1 to 2000000000 (10-3inch/min)

 

 

 

 

 

2 : degree

 

0.001 to 2000000.000 (degree/min)

 

1 to 2000000000 (10-3degree/min)

 

 

 

 

 

3 : pulse

 

1 to 1000000 (pulse/s)

 

1 to 1000000 (pulse/s)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Table 2]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value set with peripheral

Value set with sequence

 

 

Da.2

setting value

 

Setting item

 

 

device

 

program

 

 

 

 

 

 

 

 

 

 

 

JUMP instruction: 82H

Positioning data No.

1 to 600

 

1 to 600

 

Other than JUMP instruction

Dwell time

0 to 65535 (ms)

0 to 65535 (ms)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Table 3]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value set with peripheral

Value set with sequence

 

 

Da.2

setting value

 

Setting item

 

 

device

 

program

 

 

 

 

 

 

 

 

 

 

 

JUMP instruction: 82H

Condition data No.

0 to 10

 

0 to 10

 

Other than JUMP instruction

M code

0 to 65535

 

0 to 65535

 

 

 

 

 

 

 

 

 

 

 

 

LOOP: 83H

 

 

 

 

Repetition count

1 to 65535

 

1 to 65535

 

 

5 - 71

Page 159
Image 159
Mitsubishi Electronics QD75D, QD75P user manual Da.2, Setting value Setting item, Repetition count, Device Program