12 CONTROL SUB FUNCTIONS

MELSEC-Q

Positioning start signal

ON

 

 

 

 

 

OFF

 

 

 

 

 

[Y10, Y11, Y12, Y13]

 

 

 

 

 

 

ON

 

 

 

 

 

BUSY signal [XC, XD, XE, XF] OFF

 

 

 

 

 

M code ON signal

ON

 

 

 

 

 

OFF

 

 

 

 

 

[X4, X5, X6, X7]

 

 

 

 

 

Cd. 7 M code OFF request

0

1

0

 

1

0

 

 

Md. 25 Valid M code

m1

 

 

m2

m3

 

 

V

 

 

 

 

 

Positioning

 

 

 

 

 

 

 

 

 

 

 

 

t

Operation pattern

 

11

 

11

 

00

m1 and m3 indicate set M codes.

Warning occurs at this timing.

Fig. 12.40 Warning due to an M code ON signal during continuous path control

POINT

If the M code output function is not required, set a "0" in setting item " code" of the positioning data.

Da.10

M

[3]Precautions during control

(1)During interpolation control, the reference axis M code ON signal is turned ON.

(2) The M code ON signal will not turn ON if "0" is set in "

Da.10

M code". (The

M code will not be output, and the previously output value will be held in

"

Md.25

Valid M code".)

(3)If the M code ON signal is ON at the positioning start, an error "M code ON signal start (error code: 536)" will occur, and the positioning will not start.

(4)If the PLC READY signal (Y0) is turned OFF, the M code ON signal will turn

OFF and "0" will be stored in "

Md.25

Valid M code".

(5)If the positioning operation time is short during continuous path control, there will not be enough time to turn OFF the M code ON signal, and a warning "M code ON signal ON (error code: 503)" may occur. In this case, set a "0" in

the "

Da.10

M code" of that section's positioning data.

(6)In the AFTER mode during speed control, the M code is not output and the M code ON signal does not turn ON.

(7) If current value changing where "9003" has been set to "

Cd.3

Positioning

start No." is performed, the M code output function is made invalid.