12CONTROL SUB FUNCTIONS

[4]Setting the torque limit function

MELSEC-Q

(1)To use the "torque limit function", set the "torque limit value" in the parameters shown in the following table, and write them to the QD75. The set details are validated at the rising edge (OFF ON) of the PLC READY signal (Y0).

 

 

Setting item

Setting

Setting details

Factory-set

 

 

value

initial value

 

 

 

 

 

 

 

 

 

 

Torque limit

 

 

 

 

 

 

Pr.17

 

Set the torque limit value as a percentage.

300

 

 

 

setting value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set the torque limit value after the "

 

Creep

 

 

 

 

OPR torque limit

 

Pr.47

 

 

Pr.54

 

300

 

 

 

value

 

speed" is reached. Set as a percentage.

 

 

 

 

 

 

 

 

 

 

 

Refer to Section 5.2 "List of parameters" for setting details.

(2) The "torque limit value" set in the QD75 is set in the " Md.35 Torque limit

stored value". The " Md.35 Torque limit stored value" in the sequence

program is transferred to the "D/A converter module", and the torque is limited.

 

 

QD75

 

 

 

 

 

 

Buffer memory

 

 

 

Drive unit

PLC CPU

 

 

 

Reading by a

 

 

 

Positioning control

FROM command 826

 

 

 

 

 

Stored torque

 

 

 

 

 

 

limit value

 

 

 

 

 

D/A convertor module

Writing by a

 

Torque limiting

TO command

 

Fig. 12.14 Limiting the torque to the drive unit (Axis 1)

The following table shows the " buffer memory address.

Md.35

Torque limit stored value" of the

 

 

 

 

Monitor

 

 

 

 

 

 

 

Buffer memory address

 

 

Monitor item

 

 

Storage details

 

Axis

Axis

Axis

Axis

 

 

value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Torque limit stored

 

The "torque limit value" valid at that time is

 

 

 

 

 

Md.35

 

 

stored. (

 

,

 

, or

 

)

826

926

1026

1126

 

 

value

 

Pr.17

Pr.54

Cd.22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to Section 5.6 "List of monitor data" for information on the setting details.

REMARK

Parameters are set for each axis.

It is recommended that the parameters be set whenever possible with GX Configurator-QP. Execution by sequence program uses many sequence programs and devices. The execution becomes complicated, and the scan times will increase.

12 - 25

Page 501