5 DATA USED FOR POSITIONING CONTROL

Pr.37 Stop group 1 sudden stop selection

to

Pr.39 Stop group 3 sudden stop selection

MELSEC-Q

Set the method to stop when the stop causes in the following stop groups occur.

Stop group 1 .............. Stop with hardware stroke limit

Stop group 2 .............. PLC CPU error occurrence, PLC READY signal [Y0] OFF, Fault in test mode

Stop group 3 .............. External stop signal

Stop signal from PLC CPU

Stop signal from peripheral device

Error occurrence (excludes errors in stop groups 1 and 2: includes only the software stroke limit errors during JOG operation, speed control, speed-position switching control, and position-speed switching control)

Stop made when the near-point dog signal turns from OFF to ON in counter method machine OPR

The methods of stopping include "0: Normal deceleration stop" and "1: Sudden stop".

If "1: Sudden stop" is selected, the axis will suddenly decelerate to a stop when the stop signal is input.