5 - 20
MELSEC-Q
5 DATA USED FOR POSITIONING CONTROL
5.2 List of parameters5.2.1 Basic parameters 1
Setting value, setting range Setting value buffer memory
address
Item Value set with peripheral device Value set with sequence
program
Default
value Axis 1 Axis 2 Axis 3 Axis 4
0 : mm 0
1 : inch 1
2 : degree 2
Pr.1 Unit setting
3 : pulse 3
3 0 150 300 450
Pr.2
No. of pulses per
rotation (Ap)
(Unit : pulse)
1 to 65535
1 to 65535
1 to 32767
:Set as a decimal
32768 to 65535
:Convert into hexadecimal
and set
20000 1 151 301 451
Pr.3
Movement amount per
rotation (Al)
The setting value range differs according to the " Pr.1 Unit
setting".
Here, the value within the [Table 1] range is set.
[Table 1] on right page
20000 2 152 302 452
1 : 1-fold 1
10 : 10-fold 10
100 : 100-fold 100
Movement amount per pulse
Pr.4
Unit magnification (Am) 1000 : 1000-fold 1000
1 3 153 303 453
Pr.1 Unit setting
Set the unit used for defining positioning operations. Choose from the following
units depending on the type of the control target: mm, inch, degree, or pulse.
Different units can be defined for different axes (axis 1 to 4).
(Example) Different units (mm, inch, degree, and pulse) are applic able to different
systems:
mm or inch.....X-Y table, conveyor (Se lect mm or inch depending on the
machine specifications.)
degree........... Rotating body (360 degrees/rotation)
pulse.............. X-Y table, conveyor
When you change the unit, note that the values of other parameters and d ata
will not be changed automatically.
After changing the unit, check if the parameter and data values are with in the
allowable range.
Set "degree" to exercise speed-position switching control (ABS m ode).