12CONTROL SUB FUNCTIONS

[2]Software stroke limit check details

MELSEC-Q

 

 

 

 

 

Check details

Processing when

 

 

 

 

 

an error occurs

 

 

 

 

 

 

 

 

 

 

 

 

 

An error shall occur if the current value 1 is outside the software

 

1)

stroke limit range

2.

 

 

 

 

(Check "

Md.20

 

Current feed value" or "

Md.21

Machine feed value".)

An "axis error" will

 

 

 

 

 

 

 

 

occur (error code:

 

An error shall occur if the command address is outside the software

 

507, 508)

 

stroke limit range.

2)

 

 

(Check "

Da.6

Positioning address/movement amount".)

 

 

 

 

 

 

 

 

 

 

1Check whether the " Md.20 Current feed value" or " Md.21

" Pr.14 Software stroke limit selection".

Machine feed value" is set in

2Moveable range from the " Pr.12 Software stroke limit upper limit value" to the "

Software stroke limit lower limit value".

Pr.13

[3]Relation between the software stroke limit function and various controls

 

Control type

 

Limit

Processing at check

 

 

check

 

 

 

 

 

 

OPR control

Machine OPR control

 

 

Check not carried out.

Fast OPR control

 

 

 

 

1-axis linear control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 to 4-axes axis linear

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

interpolation control

 

 

 

 

 

Checks 1) and 2) in the previous section [2] are carried

 

 

 

 

 

 

 

 

Position

1-axis fixed-feed control

 

 

 

 

 

out.

 

 

 

 

 

 

 

 

 

control

2 to 4-axes fixed-feed control

 

 

 

 

 

For speed control:

The axis decelerates to a stop when

 

 

 

 

 

 

 

 

(interpolation)

 

 

 

 

 

 

it exceeds the software stroke limit

 

 

 

 

 

 

 

 

Major

 

2-axis circular interpolation

 

 

 

 

 

 

range.

 

 

 

 

 

 

 

 

control

 

 

 

 

 

For position control:

The axis comes to an immediate

positioning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

stop when it exceeds the software

control

1 to 4-axes speed control

 

 

 

 

 

 

3, 4

 

stroke limit range.

 

 

 

 

 

Speed-position switching control

 

 

 

 

 

 

 

 

Position-speed switching control

3, 4

 

 

 

 

Current value changing

 

 

The current value will not be changed if the new current

 

Other

 

 

value is outside the software stroke limit range.

 

 

 

 

 

 

 

 

control

JUMP instruction, NOP

 

 

Check not carried out.

 

 

instruction, LOOP to LEND

 

 

 

 

 

 

 

 

 

 

 

 

JOG operation, Inching operation

 

 

 

 

5

Check 1) in the previous section [2] is carried out.

 

 

 

 

 

 

 

 

 

 

 

 

 

The machine will carry out a deceleration stop when the

Manual

 

 

 

 

 

 

 

software stroke limit range is exceeded. If the address

control

Manual pulse generator operation

 

 

 

 

5

falls out of the software stroke limit range, the operation

 

 

 

 

 

 

 

 

 

 

 

 

can be started only toward the movable range after an

 

 

 

 

 

 

 

 

error reset.

 

:Check valid

:Check is not made when the current feed value is not updated (Refer to

Pr.21

) at the setting of " current feed

value" in "

Pr.14

Software stroke limit selection" during speed control.

: Check not carried out (check invalid).

: Valid only when "1:valid" is set in the "

Pr.15

Software stroke limit valid/invalid setting".

3: The value in " Md.20 Current feed value" will differ according to the "

control" setting.

4: When the unit is "degree", check is not made during speed control. 5: When the unit is "degree", check is not carried out.

Pr.21

Current feed value during speed

12 - 28

Page 504