Toshiba RAV-SM1606BT-E, RAV-SM406BT-TR, RAV-SM1406BT-E, RAV-SM1606BT-TR Description, At shipment

Models: RAV-SM456BT-E RAV-SM566BT-TR RAV-SM566BT-E RAV-SM456BT-TR RAV-SM806BT-E RAV-SM806BT-TR RAV-SM1106BT-TR RAV-SM1106BT-E RAV-SM1406BT-TR RAV-SM1606BT-TR RAV-SM1606BT-E RAV-SM1406BT-E RAV-SM406BT-TR

1 104
Download 104 pages 55.2 Kb
Page 67
Image 67

DN

Item

 

Description

At shipment

 

 

 

 

60

Timer set

0000 : Available (Operable)

0000 : Available

 

(Wired remote controller)

0001 : Unavailable (Operation prohibited)

 

 

 

 

 

 

8b

Correction of high heat feeling

0000 : None

0001 : Correction

0000 : None

 

 

 

 

 

42

Self clean time

0000: None

 

0002: 1 hour

 

 

0001: 0.5h to 0.012: 6.0h

 

 

 

The case that compressor-ON time is 10 to 60 minutes is

 

 

 

set up. When ON time is over 60 minutes, the operating

 

 

 

time becomes two times of it.

 

 

 

 

 

 

C2

Power saving

0050: 50% to

0100: 100%

0075: 75%

 

(Current demand × % to outdoor unit)

 

 

 

 

 

 

 

 

CC

Forced stop setting for self clean

0000: None

0001: Set

0000: None

 

 

 

 

CD

Self clean stop function when [START/

When stopping the air conditioner (including “Fire alarm”

0000: Valid

 

STOP] operation was prohibited

of the control system, etc.) while [START/STOP] operation

 

 

 

is prohibited (Central 1, 2) from the central controller side,

 

 

 

0000: Valid (No self cleaning)

 

 

 

0001: Invalid (Self cleaning)

 

 

 

 

 

D0

Existence of Power save operation

0000: Invalid (Unavailable)

0001: Valid (Available)

 

 

0001: Valid (Available)

 

 

 

 

 

D1

Existence of 8°C heating operation

0000: Invalid (Unavailable)}

0000: Invalid

 

function

0001: Valid (Available)

(Unavailable)

 

 

 

 

D3

Revolution count of self clean

0000: Invalid (Self cleaning is not performed.)

0011: Valid

 

 

0011: Valid (Self cleaning is performed at 310 rpm.)

(310rpm/operation)

 

 

 

 

D4

Display/ No display of [SELF CLEANING]

0000: Displayed, 0001: Not displayed

0000: Displayed

 

during self clean operation

 

 

 

 

 

 

 

 

– 67 –

Page 67
Image 67
Toshiba RAV-SM1606BT-E, RAV-SM406BT-TR, RAV-SM1406BT-E, RAV-SM1606BT-TR, RAV-SM1406BT-TR Description, At shipment