Outline of judgment

When one of the following phenomena appears, an error of the power relay (RY01) is considered; therefore replace the P.C. board.

The operation started from the remote controller.

The fan stops immediately.

The display on the remote controller disappears.

After approx. 1minute

30 seconds, "Under setting" is displayed.

The screen of the remote controller enters in STOP status.

The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with the following method.

Method to judge the erroneous position by display panel of the indoor unit (lamp display of the wireless receiving part)

The indoor unit monitors the operating status of the air conditioner, and the blocked contents of self-diagnosis are displayed restricted to the following cases if a protective circuit works.

 

 

 

 

 

 

 

 

: Go off,

: Go on,

: Flash (0.5 sec.)

 

 

 

 

 

 

 

 

 

Lamp indication

Check code

Cause of trouble occurrence

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

Timer

Ready

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply OFF or miswiring between lamp indication unit and indoor unit

 

No indication at all

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E01

Receiving error

 

 

 

 

 

 

 

 

 

 

 

 

 

Receiving unit

Miswiring or wire connection error

 

 

 

 

 

 

E02

 

 

 

 

 

 

Sending error

 

 

 

 

 

 

 

 

between receiving unit and indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E03

Communication stop

 

 

 

 

 

 

Operation

Timer

Ready

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E08

Duplicated indoor unit No.

 

 

Setup error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flash

 

 

 

 

E09

Duplicated master units of remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E10

Communication error between CPUs on indoor unit P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E18

Wire connection error between indoor units, Indoor power OFF

 

 

 

 

 

 

 

(Communication stop between indoor header and follower)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

Timer

Ready

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E04

Miswiring between indoor unit and outdoor unit or connection erorr

 

 

 

 

 

 

 

(Communication stop between indoor and outdoor units)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flash

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

Timer

Ready

P10

Overflow was detected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protective device of indoor unit worked.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P12

Indoor DC fan error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alternate flash

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P03

Outdoor unit discharge temp. error

 

Protective device of

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P04

Outdoor high pressure system error

outdoor unit worked.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P05

Negative phase detection error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P07

Heat sink overheat error

 

 

Outdoor unit error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas leak detection error

 

 

 

 

 

 

Operation

Timer

Ready

P15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P19

4-way valve system error (Indoor or outdoor unit judged.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P20

Outdoor unit high pressure protection

 

 

 

 

 

 

Alternate flash

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P22

Outdoor unit: Outdoor unit error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protective device of

 

 

 

 

 

 

 

P26

Outdoor unit: Inverter Idc operation

 

1

 

 

 

 

 

 

 

 

 

 

outdoor unit worked.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P29

Outdoor unit: Position detection error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P31

Stopped because of error of other indoor unit in a group

 

 

 

 

 

 

 

 

(Check codes of E03/L03/L07/L08)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1: These are representative examples and the check code differs according to the outdoor unit to be combined.

– 38 –

Page 38
Image 38
Toshiba RAV-SM456BT-E, RAV-SM406BT-TR Outline of judgment, Lamp indication Check code Cause of trouble occurrence

RAV-SM456BT-E, RAV-SM566BT-TR, RAV-SM566BT-E, RAV-SM456BT-TR, RAV-SM806BT-E specifications

Toshiba has long been recognized as a leader in air conditioning technology, and their latest models, including the RAV-SM806BT-E, RAV-SM566BT-TR, RAV-SM1106BT-E, RAV-SM456BT-E, and RAV-SM1406BT-E, are prime examples of innovation in climate control solutions. These models combine energy efficiency, advanced technology, and user-friendly features to meet diverse cooling and heating needs for both residential and commercial spaces.

The RAV-SM806BT-E is notable for its impressive cooling and heating capabilities, making it suitable for larger areas. With a robust cooling capacity of 8.0 kW, this model is equipped with inverter technology, providing variable speed control that optimizes energy consumption while ensuring consistent comfort levels. Its quiet operation makes it ideal for settings where noise control is crucial, such as offices and bedrooms.

Similarly, the RAV-SM566BT-TR offers a balanced solution for medium-sized environments. With a capacity of 5.6 kW, it features advanced air filtration systems that enhance indoor air quality by removing dust, allergens, and pollutants. This model is particularly appreciated in regions with high air pollution levels, providing a healthier living or working environment.

The RAV-SM1106BT-E stands out for its high efficiency and eco-friendly refrigerant use. This model is designed to reduce greenhouse gas emissions while delivering significant cooling output, making it a responsible choice for environmentally conscious consumers. Additionally, Toshiba’s smart temperature control technology allows users to precisely manage their climate settings through a user-friendly remote control or smartphone app, offering convenience and ease of use.

For those looking for a compact yet powerful solution, the RAV-SM456BT-E is designed to fit smaller spaces without sacrificing performance. With a cooling capacity of 4.5 kW, it still utilizes sophisticated inverter technology, ensuring minimal energy loss and optimal heating and cooling efficiency. Its compact design allows for flexible installations in varied spaces.

Lastly, the RAV-SM1406BT-E model emphasizes versatility and performance. With a cooling capacity of 14.0 kW, it is designed for larger commercial spaces, delivering powerful climate control while maintaining energy efficiency. Its advanced multi-zone system allows simultaneous operation across different areas, adapting to the unique requirements of each zone.

In summary, Toshiba's RAV-SM series reflects the company's commitment to innovation, energy efficiency, and user comfort. Each model offers unique features tailored to specific needs, setting new standards in the air conditioning industry. Whether for residential or commercial use, these systems provide reliable performance while promoting sustainable practices.