Johnson Controls GG9S*MP, TG9S*MP installation manual Combustion AIR Supply, Outdoor Combustion Air

Page 25

364861-UIM-B-0708

COMBUSTION AIR SUPPLY

All installations must comply with Section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149.1 or .2 Installation Code - latest edi- tions.

This furnace is certified to be installed with one of three possible com- bustion air intake configurations.

1. OUTDOOR COMBUSTION AIR: This is a direct vent configuration

where the combustion air is supplied through a PVC or ABS pipe

that is connected to the PVC coupling attached to the furnace and

is terminated in the same atmospheric zone as the vent. This type

of installation is approved on all models. Refer to Figure 36.

2. AMBIENT COMBUSTION AIR: Combustion air is supplied from

the area surrounding the furnace through openings in the furnace

casing. The combustion air and the vent pipes are not terminated

in the same atmospheric zone. Refer to Figure 21 for vent termina-

tions. Refer to "Ambient Combustion Air Supply" for proper instal-

COMBUSTION AIR

Vent pipe cements into socket just above top panel

Or vent pipe may be clamped into outlet of drain coupling

lation. Refer to Figure 36.

3. VENTILATED COMBUSTION AIR: Combustion air is supplied

through a PVC or ABS pipe that is connected to the PVC coupling

attached to the burner box and is terminated in a ventilated attic or

crawl space. The combustion air and the vent pipes are not termi-

nated in the same atmospheric zone. Refer to Figure 37 for attic

and crawl space termination. Only the combustion air intake may

terminate in the attic. The vent must terminate outside.

Outdoor Combustion Air

Combustion Air Intake/Vent Connections

This installation requires combustion air to be brought in from outdoors. This requires a properly sized pipe (Shown in Figure 30) that will bring air in from the outdoors to the furnace combustion air intake collar on the burner box. The second pipe (Shown in Figure 30) is the furnace vent pipe.

FIGURE 35: Combustion Airflow Path Through The Furnace Casing

This type of installation requires that the supply air to the appli- ance(s) be of a sufficient amount to support all of the appliance(s) in the area. Operation of a mechanical exhaust, such as an exhaust fan, kitchen ventilation system, clothes dryer or fireplace may cre- ate conditions requiring special attention to avoid unsatisfactory operation of gas appliances. A venting problem or a lack of supply air will result in a hazardous condition, which can cause the appli- ance to soot and generate dangerous levels of CARBON MONOX- IDE, which can lead to serious injury, property damage and / or death.

An unconfined space is not less than 50 cu.ft (1.42 m3) per 1,000 Btu/ hr (0.2928 kW) input rating for all of the appliances installed in that area.

Connects to collar on top of burner box

Vent pipe cements into socket just above top panel

Or vent pipe may be clamped into outlet of drain coupling

Rooms communicating directly with the space containing the appli- ances are considered part of the unconfined space, if doors are fur- nished with openings or louvers.

A confined space is an area with less than 50 cu.ft (1.42 m3) per 1,000 Btu/hr (0.2928 kW) input rating for all of the appliances installed in that area. The following must be considered to obtain proper air for combus- tion and ventilation in confined spaces.

Combustion Air Source From Outdoors

The blocking effects of louvers, grilles and screens must be given con- sideration in calculating free area. If the free area of a specific louver or grille is not known, refer to Table 11, to estimate free area.

Table 11: Estimated Free Area

FIGURE 34: Direct Vent Air Intake Connection and Vent Connection

The combustion air intake pipe should be located either through the wall (horizontal or side vent) or through the roof (vertical vent). Care should be taken to locate side vented systems where trees or shrubs will not block or restrict supply air from entering the terminal.

Also, the terminal assembly should be located as far as possible from a swimming pool or a location where swimming pool chemicals might be stored. Be sure the terminal assembly follows the outdoor clearances listed in Section #1 “Outdoor Air Contaminants.”

Ambient Combustion Air Supply

This type installation will draw the air required for combustion from within the space surrounding the appliance and from areas or rooms adjacent to the space surrounding the appliance. This may be from within the space in a non-confined location or it may be brought into the furnace area from outdoors through permanent openings or ducts. It is not piped directly into the furnace. A single, properly sized pipe from the furnace vent connector to the outdoors must be provided. It is recom- mended that the supplied intake coupling & 18” of pipe be attached to the furnace to prevent accidental blockage of the combustion air intake.

Wood or Metal

Wood 20-25%*

Louvers or Grilles

Metal 60-70% *

 

 

Screens+

1/4” (0.635 cm)

mesh or larger 100%

 

 

 

* Do not use less than 1/4”(0.635 cm) mesh

+Free area of louvers and grille varies widely; the installer should follow louver or grille manufacturer’s instructions.

Dampers, Louvers and Grilles (Canada Only)

1.The free area of a supply air opening shall be calculated by sub- tracting the blockage area of all fixed louvers grilles or screens from the gross area of the opening.

2.Apertures in a fixed louver, a grille, or screen shall have no dimen- sion smaller than 0.25” (0.64 cm).

3.A manually operated damper or manually adjustable louvers are not permitted for use.

4.A automatically operated damper or automatically adjustable lou- vers shall be interlocked so that the main burner cannot operate unless either the damper or the louver is in the fully open position.

Johnson Controls Unitary Products

25

Image 25
Contents List of Sections Section I SafetyList of Figures List of TablesSafety Requirements Specific Safety Rules and PrecautionsCombustion AIR Quality List of Contaminants Inspection Codes and StandardsDirectly BELOW. Keep Clear of ALL OBSTRUC- Tions Furnace Location and Clearances Section II DuctworkDuctwork General Information Coil Installation Floor Base and Ductwork Installation DownflowCOIL/FURNACE Assembly MC/FC/PC Series Coils Furnace Assembly MC & FC Series CoilsFurnace Assembly MC Series Coils only Coil Flange InstallationFurnace Assembly PC Series Coils Coil / Furnace Assembly HC Series CoilsBottom Return and Attic Installations Downflow Duct Connectors Attic InstallationSuspended Furnace / Crawl Space Installation Horizontal ApplicationCabinet Dimensions Inches Filter InstallationSection III Filters Btuh kW NominalGAS Piping Installation GAS SafetySection IV GAS Piping Side ReturnHigh Altitude Pressure Switch Conversion Section V Electrical PowerElectrical Power Connections GAS Orifice Conversion for Propane LPSupply Voltage Connections LOW Voltage Control Wiring ConnectionsAfue AC 5D HP 2C Section VI Twinning and Staging Single-Wire Staging Single-Wire Twinning OperationSingle-Wire Staging Instructions Single-Wire Staging OperationCondensate Drain Termination Condensate Drain LocationCondensate Drain Trap and Drain Freeze Protection Inducer Rotated for Right Side Venting Airflow Horizontal Left Inducer Rotated Horizontal Right Inducer Rotated Section Viii Combustion AIR and Vent System Combustion AIR and Vent SafetyCombustion AIR/VENT Pipe Sizing Combustion AIR / Venting Combustion AIR and Vent Piping AssemblyFitting Equivalent Length Furnace Vent Connection SizesHome Layout Vent ClearancesVent Applications and Termination Vent SystemVenting Multiple Units Outdoor Combustion Air Combustion AIR SupplyCombustion Air Source From Outdoors Ambient Combustion Air SupplyFree Area Air Supply Openings and DuctsVentilated Combustion Air Specially Engineered InstallationsVentilated Combustion Air Termination Vent Blower RotationGAS Piping Leak Check Section IX START-UP AdjustmentsIgnition System Sequence Calculating the Furnace Input Natural GASSeconds For Seconds For Size of Test Dial Revolution Cu FtRevolution Cu Ft Read the inlet gas pressure Adjustment of Manifold GAS Pressure & Input RateRead the manifold gas pressure Inlet GAS Pressure RangeSection X Safety Controls Furnace Control Diagnostics TroubleshootingLimit Controls Sequence of OperationDiagnostic Fault Code Storage and Retrieval Section XI Replacement Parts List Section XII Wiring Diagram Johnson Controls Unitary Products York Drive Norman, OK Protection Models ESP Nominal Size awg @ Over Current AmpsMed-Lo Factory HeatingHorizontal Right

TG9S*MP, GG9S*MP specifications

Johnson Controls has long been at the forefront of building efficiency solutions, and their TG9S*MP and GG9S*MP series exemplify this commitment. These two-stage, multi-position gas furnaces are designed for optimal comfort and performance in residential applications, and they come packed with a variety of features that enhance their efficiency and operational capabilities.

One of the standout features of the TG9S*MP and GG9S*MP furnaces is their efficient two-stage operation. This technology allows the unit to operate at a lower capacity most of the time, which translates into reduced energy consumption and costs. When the demand for heating increases, the furnace automatically shifts to a higher capacity, ensuring a consistent and comfortable indoor temperature. This flexibility not only enhances comfort but also extends the lifespan of the unit as it doesn't have to work harder than necessary.

Energy efficiency is a crucial characteristic of both models. With an Annual Fuel Utilization Efficiency (AFUE) rating of up to 96%, these furnaces convert a significant amount of the fuel they consume into usable heat. Such efficiency ratings not only help in reducing energy bills but also have a positive impact on the environment by minimizing greenhouse gas emissions.

Both models feature advanced technology in their design, including a fully modulating gas valve and a variable-speed blower motor. The modulating valve adjusts the gas flow in response to the thermostat’s signals, allowing for precise temperature control and improved comfort. Meanwhile, the variable-speed blower motor enhances airflow while operating quietly, significantly improving overall indoor air quality by promoting even heat distribution throughout the home.

From a structural standpoint, the TG9S*MP and GG9S*MP are built with durable materials designed for longevity. Their compact design allows for flexible installation options, whether in a closet, attic, or basement. The furnaces also come equipped with a robust heat exchanger crafted from high-quality materials, which ensures both reliability and efficiency.

In conclusion, the Johnson Controls TG9S*MP and GG9S*MP furnaces provide homeowners with efficient, reliable, and comfortable heating solutions. With advanced features such as two-stage operation, impressive AFUE ratings, and modern technology integrations, these models stand out in the market as dependable options for both energy savings and year-round comfort. Whether you're a homeowner looking to upgrade your heating system or a contractor seeking high-quality products for your clients, these furnaces represent a smart choice.