Page 16

364861-UIM-B-0708

SECTION VII: CONDENSATE PIPING AND FURNACE VENTING CONFIGURATION

CONDENSATE DRAIN LOCATION

As shipped from the factory:

For all 040, 060, & 080K input furnaces the main drain is plumbed through the casing right-side opening when viewed from the front of the furnace.

For all 100, 120, & 130K input furnaces the main drain is plumbed through the casing left-side opening when viewed from the front of the furnace.

NOTE: On 130K BTU models, there is no provision for the vent to exit the top of the cabinet, the vent must always exit one of the sides.

NOTE: The Figures 23 - 26 show the condensate drain arrange- ment for the various possible furnace and vent blower positions.

The condensate hoses must slope downwards at all points.

The condensate water will flow to the drain better id a tee with a short, open end, length of pipe is installed in the drain line. The top of the pipe should terminate at least to the middle of the condensate pan which is located inside the furnace.

The furnace condensate pan is self priming and con- tains an internal trap to prevent flue gas leaking. Do not install an external condensate trap.

When drain hose routing changes are required (shown in Figures 23- 26), be sure to cap all un-used openings.

If rerouting hoses - excess length should be cut off so that no sagging loops will collect and hold condensate - which will cause the furnace to not operate.

No hose clamps are needed for connecting to the condensate pan.

The condensate drain from the furnace may be connected in com- mon with the drain from an air conditioning coil if allowed by local code.

Condensate must be disposed of properly. Follow local plumbing or wastewater codes. The drain line must maintain a 1/4" per foot (0.635 cm per meter) downward slope to the drain.

CONDENSATE DRAIN TERMINATION

A condensate sump pump MUST be used if required by local codes, or if no indoor floor drain is available. The condensate sump pump must be approved for use with acidic condensate.

DO NOT terminate condensate drain in a chimney, or where the drain line may freeze. The line must terminate at an inside drain to prevent freezing of the condensate and possible property damage.

DO NOT trap the drain line at any other location than at the conden- sate drain trap supplied with the furnace.

CONDENSATE DRAIN TRAP AND DRAIN FREEZE PROTECTION

Special precautions MUST be made if installing furnace in an area which may drop below freezing. This can cause improper operation or damage to the equipment. If the furnace is installed in an area that has the potential of freezing, the drain line must be protected. Use a 3 to 6 watt per foot at 115 vac, 40º F (4.4° C) self-regulating, shielded and waterproof heat tape. Wrap the drain line outside of the furnace with the heat tape and secure with ties. Follow the heat tape manufacturer's rec- ommendations.

Use only Propylene Glycol (RV anti-freeze) to winterize the furnace. Refer to the manufacturer’s specification to ensure that it is compat- ible with plastics and other components of the furnace. DO NOT use Ethylene Glycol anti-freeze in the furnace.

16

Johnson Controls Unitary Products

Image 16
Contents Section I Safety List of SectionsList of Figures List of TablesSafety Requirements Specific Safety Rules and PrecautionsCombustion AIR Quality List of Contaminants Inspection Codes and StandardsDirectly BELOW. Keep Clear of ALL OBSTRUC- Tions Furnace Location and Clearances Section II DuctworkDuctwork General Information Floor Base and Ductwork Installation Downflow Coil InstallationCOIL/FURNACE Assembly MC/FC/PC Series Coils Furnace Assembly MC & FC Series CoilsCoil Flange Installation Furnace Assembly MC Series Coils onlyFurnace Assembly PC Series Coils Coil / Furnace Assembly HC Series CoilsDownflow Duct Connectors Attic Installation Bottom Return and Attic InstallationsSuspended Furnace / Crawl Space Installation Horizontal ApplicationFilter Installation Cabinet Dimensions InchesSection III Filters Btuh kW NominalGAS Safety GAS Piping InstallationSection IV GAS Piping Side ReturnSection V Electrical Power High Altitude Pressure Switch ConversionElectrical Power Connections GAS Orifice Conversion for Propane LPSupply Voltage Connections LOW Voltage Control Wiring ConnectionsAfue AC 5D HP 2C Section VI Twinning and Staging Single-Wire Twinning Operation Single-Wire StagingSingle-Wire Staging Instructions Single-Wire Staging OperationCondensate Drain Termination Condensate Drain LocationCondensate Drain Trap and Drain Freeze Protection Inducer Rotated for Right Side Venting Airflow Horizontal Left Inducer Rotated Horizontal Right Inducer Rotated Section Viii Combustion AIR and Vent System Combustion AIR and Vent SafetyCombustion AIR/VENT Pipe Sizing Combustion AIR and Vent Piping Assembly Combustion AIR / VentingFitting Equivalent Length Furnace Vent Connection SizesVent Clearances Home LayoutVent Applications and Termination Vent SystemVenting Multiple Units Combustion AIR Supply Outdoor Combustion AirCombustion Air Source From Outdoors Ambient Combustion Air SupplyAir Supply Openings and Ducts Free AreaSpecially Engineered Installations Ventilated Combustion AirVentilated Combustion Air Termination Vent Blower RotationSection IX START-UP Adjustments GAS Piping Leak CheckIgnition System Sequence Calculating the Furnace Input Natural GASSeconds For Seconds For Size of Test Dial Revolution Cu FtRevolution Cu Ft Adjustment of Manifold GAS Pressure & Input Rate Read the inlet gas pressureRead the manifold gas pressure Inlet GAS Pressure RangeSection X Safety Controls Troubleshooting Furnace Control DiagnosticsLimit Controls Sequence of OperationDiagnostic Fault Code Storage and Retrieval Section XI Replacement Parts List Section XII Wiring Diagram Johnson Controls Unitary Products York Drive Norman, OK Models ESP Nominal Size awg @ Over Current Amps ProtectionMed-Lo Factory HeatingHorizontal Right

TG9S*MP, GG9S*MP specifications

Johnson Controls has long been at the forefront of building efficiency solutions, and their TG9S*MP and GG9S*MP series exemplify this commitment. These two-stage, multi-position gas furnaces are designed for optimal comfort and performance in residential applications, and they come packed with a variety of features that enhance their efficiency and operational capabilities.

One of the standout features of the TG9S*MP and GG9S*MP furnaces is their efficient two-stage operation. This technology allows the unit to operate at a lower capacity most of the time, which translates into reduced energy consumption and costs. When the demand for heating increases, the furnace automatically shifts to a higher capacity, ensuring a consistent and comfortable indoor temperature. This flexibility not only enhances comfort but also extends the lifespan of the unit as it doesn't have to work harder than necessary.

Energy efficiency is a crucial characteristic of both models. With an Annual Fuel Utilization Efficiency (AFUE) rating of up to 96%, these furnaces convert a significant amount of the fuel they consume into usable heat. Such efficiency ratings not only help in reducing energy bills but also have a positive impact on the environment by minimizing greenhouse gas emissions.

Both models feature advanced technology in their design, including a fully modulating gas valve and a variable-speed blower motor. The modulating valve adjusts the gas flow in response to the thermostat’s signals, allowing for precise temperature control and improved comfort. Meanwhile, the variable-speed blower motor enhances airflow while operating quietly, significantly improving overall indoor air quality by promoting even heat distribution throughout the home.

From a structural standpoint, the TG9S*MP and GG9S*MP are built with durable materials designed for longevity. Their compact design allows for flexible installation options, whether in a closet, attic, or basement. The furnaces also come equipped with a robust heat exchanger crafted from high-quality materials, which ensures both reliability and efficiency.

In conclusion, the Johnson Controls TG9S*MP and GG9S*MP furnaces provide homeowners with efficient, reliable, and comfortable heating solutions. With advanced features such as two-stage operation, impressive AFUE ratings, and modern technology integrations, these models stand out in the market as dependable options for both energy savings and year-round comfort. Whether you're a homeowner looking to upgrade your heating system or a contractor seeking high-quality products for your clients, these furnaces represent a smart choice.