Installation
Installation should be done by a QUALIFIED SERVICE TECHNICIAN.
The furnace must be located on an outside wall.
Wall Installation
Minimum clearances from combustible materials:
•Furnace to the top surface of carpeting, tile:
•Furnace to back wall (0” to spacers):
•Vent to wall enclosure:
•Furnace to sidewalls:
•Furnace to ceiling:
See Figure 1 showing clearance for installation of vent cap.
WARNING: For the installation of this furnace, the following items must be used as a vent air intake system:
External Vent Cap
(Part Number:
Flanged Air Inlet Tube
(Part Number:
(Part Number:
Flue Outlet Tube
(Part Number:
(All the above items are supplied with the furnace)
Leave at least
If there is a shelf above the furnace, it must be be noncombustible. A minimum clearance of
Gas equipment in residential garages must be installed so that all burners and burner ignition devices are located not less than
The vent terminal of this
DO NOT cover the furnace.
Make sure that the correct gas supply is available.
The furnace requires a 120V, 60 Hz electrical supply.
The furnace must be electrically grounded in accordance with local codes or in the absence of local codes, with the National Electrical Code ANSI/NFPA 70 (latest edition) or in Canada with
WARNING: The nearest point of the vent cap should be a minimum horizontal distant of six (6) feet (1,830 mm) from any pressure regulator. In case of regulator malfunction, the six (6) feet (1,830 mm) distance will reduce the chance of gas entering the vent cap.
4