Williams 2903512, 2903511 installation instructions Wall Installation

Page 5

Installation

Installation should be done by a QUALIFIED SERVICE TECHNICIAN.

The furnace must be located on an outside wall.

Wall Installation

Minimum clearances from combustible materials:

Furnace to the top surface of carpeting, tile: 2-inches (50 mm)

Furnace to back wall (0” to spacers):

0-inch (0 mm).

Vent to wall enclosure: 0-inch (0 mm)

Furnace to sidewalls:

3.15-inches (80 mm)

Furnace to ceiling:

10-inches (254 mm)

See Figure 1 showing clearance for installation of vent cap.

WARNING: For the installation of this furnace, the following items must be used as a vent air intake system:

External Vent Cap

(Part Number: WFR–TRM000)

Flanged Air Inlet Tube

(Part Number: WFR–TBO002)

O-Ring

(Part Number: WFN–RNG003)

Flue Outlet Tube

(Part Number: WFR-795)

(All the above items are supplied with the furnace)

Leave at least three-feet in front of the wall furnace for servicing and proper operation. The wall furnace must be installed in such a way that the external casing can be completely removed for servicing.

If there is a shelf above the furnace, it must be be noncombustible. A minimum clearance of 12-inches (300 mm) is recommended between the furnace and the noncombustible shelf above it.

Gas equipment in residential garages must be installed so that all burners and burner ignition devices are located not less than 18-inches (460 mm) above the floor. Such equipment must be located, or protected, so it is not subject to physical damage by a moving vehicle.

The vent terminal of this direct-vent furnace must be located at least 9-inches (230 mm) from any opening through which flue gases could enter a building. The bottom of the vent terminal and the air intake must be located at least 12-inches (300mm) above grade.

DO NOT cover the furnace.

Make sure that the correct gas supply is available.

The furnace requires a 120V, 60 Hz electrical supply.

The furnace must be electrically grounded in accordance with local codes or in the absence of local codes, with the National Electrical Code ANSI/NFPA 70 (latest edition) or in Canada with CAN/CSA-C22.2 No. 3.

WARNING: The nearest point of the vent cap should be a minimum horizontal distant of six (6) feet (1,830 mm) from any pressure regulator. In case of regulator malfunction, the six (6) feet (1,830 mm) distance will reduce the chance of gas entering the vent cap.

4

Image 5
Contents Direct-Vent Wall Furnace General Information and Technical Data Table of ContentsLP Gas Warning Odor Safety Rules and General WarningsSafety Information for Users of LP Gas Some Points to Remember Technical DataWall Installation InstallationPage Outside Location for Vent Terminal Ring Gasket Gas Type Nozzle Part Number Gas ConversionsNozzle Diameter Minimum Manifold Gas PressurePressure Testing of the Gas Supply System Installing a New Main Gas Shutoff ValveGas Supply High Altitudes U.S. OnlyChecking the Gas Manifold Pressure First Firing of the FurnaceChecking the Gas Inlet Pressure Electrical Wiring Operating Instructions For Your Safety Read Before OperatingWhat to do if the RED Lamp is LIT Servicing Checking and Adjusting the Gas Manifold PressureLubrication of Moving Parts Flame Visual CheckAnnual Maintenance Requirements Overview Programmable TimerDay and Time Setting Setting and Adjustment Initial ConditionsProgramming the Timer Manual OperationCancelling of all Preset Programs Cancelling a Single ProgramUsing the Skip Function Skip Function Procedure During OperationStarting Sequence Electrical TroubleshootingTroubleshooting Step Starting Sequence Gas Gas Assembly Replacement PartsJMTR018