Williams 2903512, 2903511 installation instructions Outside Location for Vent Terminal

Page 7

Outside Location for Vent Terminal

Upon delivery, check to make sure the packaging has not been damaged.

1.Remove the furnace from box/packaging taking care not to damage the paper template to be used to mark the holes for mounting the furnace.

2.After marking the appropriate holes using the above mentioned template, make a 2-inch diameter hole.

3.Cut the combustion exhaust and fresh air inlet tubes according to the wall thickness (Figure 2):

Air Inlet Tube Length

= Wall Thickness + 3/32-inch

Flue Outlet Tube Length

= Wall Thickness + 1-5/16 inches

Figure 2

A + 33.3 mm

A + 2.3 mm

Ø 49.2

4.Drill the mounting holes “A” (8 holes) in the wall. If possible, use self-tapping screws, drill 1/8-inch diameter holes. If self-tapping screws cannot be used, drill 1/4-inch diameter holes and use the plastic anchors provided.

5.Install the supporting bracket to the wall; insert the air pipe in the wall through the hole provided in the support bracket. Place the round adhesive gasket around the hole, so that the air pipe remains in its position.

6.Attach the supporting bracket with the screws provided. If possible, use self-tapping screws, drill 1/8-inch diameter holes. If self-tapping screws cannot be used, use the plastic anchors provided.

7.Remove the casing loosening the screws and disconnect the casing grounding cable.

8.Place the adhesive spongy lining behind the furnace. (Figure 3)

Figure 3

9.Attach the flue exhaust flue pipe end (diameter 1” 3/8) on the furnace pipe male connection (Figure 5).

BE SURE THAT THE RUBBER SILICONE O–RING GASKET IS IN POSITION.

10.Remove the front panel by loosing the lateral screws (Figure 4).

11.Install the furnace to the wall leaning the bottom edge of panel “C” (where the fan is located) on the supporting frame, as shown in Figure 6. Attach the furnace to the matching hooks “A”, with light pressure against the wall). Install the heating body of the furnace to the supporting bracket with the two lateral screws.

6

Image 7
Contents Direct-Vent Wall Furnace General Information and Technical Data Table of ContentsSafety Information for Users of LP Gas Safety Rules and General WarningsLP Gas Warning Odor Some Points to Remember Technical DataWall Installation InstallationPage Outside Location for Vent Terminal Ring Gasket Minimum Manifold Gas Pressure Gas ConversionsGas Type Nozzle Part Number Nozzle DiameterHigh Altitudes U.S. Only Installing a New Main Gas Shutoff ValvePressure Testing of the Gas Supply System Gas SupplyChecking the Gas Inlet Pressure First Firing of the FurnaceChecking the Gas Manifold Pressure Electrical Wiring Operating Instructions For Your Safety Read Before OperatingWhat to do if the RED Lamp is LIT Flame Visual Check Checking and Adjusting the Gas Manifold PressureServicing Lubrication of Moving PartsAnnual Maintenance Requirements Overview Programmable TimerManual Operation Setting and Adjustment Initial ConditionsDay and Time Setting Programming the TimerSkip Function Procedure During Operation Cancelling a Single ProgramCancelling of all Preset Programs Using the Skip FunctionStarting Sequence Electrical TroubleshootingTroubleshooting Step Starting Sequence Gas Gas Assembly Replacement PartsJMTR018