Williams 1773511, 1773512 Gas Conversions, Gas Type, Nozzle Part Number, Nozzle Diameter, Maximum

Page 9
Gas Conversions

Gas Conversions

Converting to another gas type must be performed by a qualified service technician. If the type of the gas supplied to the dwelling is not the same type as your furnace (natural or LPG gas), it must be converted.

It will be necessary to do the following:

1.Change nozzle.

a.Remove the screw indicated to the right.

2. Without removing anything else, remove the nozzle from the burner inserting the screwdriver as indicated by the arrow.

Nozzle

3. Change the nozzle, attach the screw indicated at point 1 and set the burner pressure as indicated in the table below:

Gas Type

Nozzle Part Number

Natural Gas

JGLL065

LP Gas

JGLL067

Nozzle Diameter

0.09in.

0.05in.

 

Gas Type

 

 

Minimum Inlet Line Gas

 

 

Maximum

 

 

 

 

Pressure

 

 

Manifold Gas Pressure

 

 

 

 

 

 

 

 

 

Natural Gas

 

 

7.0-inches w.c.

 

 

3.2-inches w.c.

 

 

LP Gas

 

 

11.0-inches w.c.

 

 

10.6-inches w.c.

 

Minimum

Manifold Gas Pressure

1.8-inches w.c.

6.5-inches w.c.

4. Check the gas pressure and settings.

Minimum Burner Pressure Setting:

1.Set LOW burner capacity by pressing button Z2

2.Connect a micro manometer to the test gauge B (Figure 8)

3.Rotate the internal screw “D” (Figure 8) and set the pressure at the correct value

Maximum Burner Pressure Setting:

1.Set HI burner capacity by pressing button Z2

2.Connect a micro manometer to the test gauge B (Figure 8)

3.Rotate the external screw “C” (Figure 8) and set the pressure at the correct value

8

Image 9
Contents Direct-Vent Wall Furnace Williams Furnace Co., 250 West Laurel Street, Colton, CA 92324 U.S.AInstructions to Installer Table of Contents General Information and Technical DataSafety Information for Users of LP Gas Safety Rules and General WarningsLP Gas Warning Odor That’s your signal to go into immediate actionSome Points to Remember Technical DataWall Installation InstallationOutside Location for Vent Terminal Air inlet tube length = wall thickness + 3/32-inches 2.4 mmFlue outlet tube length = wall thickness + 1-5/16-inches 7.9 mm A + 33.3 mm 13. Relocate the vent cap and attach it with the screws. Figure Gas Type Gas ConversionsNozzle Part Number Nozzle DiameterInstalling a New Main Gas Shutoff Valve High Altitude AdjustmentPressure Testing of the Gas Supply System Gas SupplyChecking the Gas Inlet Pressure First Firing the FurnaceChecking the Gas Manifold Pressure A B CElectrical Wiring Diagram Key Operating Instructions FOR YOUR SAFETY READ BEFORE OPERATINGOPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCEHOW TO SHUT OFF THE APPLIANCE USING THE FEATURES OF YOUR FURNACEWHAT TO DO IF THE RED LAMP IS LIT Servicing Checking and Adjusting the Gas Manifold PressureChecking, Removing and Reassembling of the Vent Air Intake System Lubrication of Moving PartsAnnual Maintenance Requirements Overview Programmable TimerDay and Time Setting Setting and Adjustment Initial ConditionsProgramming the Timer Manual OperationCancelling of all Preset Programs Cancelling a Single ProgramUsing the Skip Function Skip Function Procedure During OperationTroubleshooting Step Troubleshooting Starting Sequence ElectricalStep Summer Mode StepTroubleshooting Step Starting Sequence Gas Replacement Parts Gas AssemblyElectric Box S - Combustion Blower Motor M1 - Overheat Thermostat RP8 Flame Sensor RP7 Spark Igniter 2 piecesM2 - Fan Thermostat Fan Blades 4 pieces M - Fan Motor 2 Pieces Part NumberJLTT015 Part Number JLTT023 Part Number JMTR017