Bryant 355CAV installation instructions Downflow Applications, Condensate Trap Location

Page 10

355CAV

COLLECTOR BOX

DRAIN TUBE (BLUE)

PLUG

CAP

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

DRAIN TUBE (BLUE &

WHITE STRIPED)

COLLECTOR BOX

TUBE EXTENSION

CONDENSATE

TRAP

INDUCER HOUSING (MOLDED) DRAIN TUBE (VIOLET)

A07276

Fig. 9 - Condensate Trap

DOWNFLOW APPLICATIONS

A downflow furnace application is where furnace blower is located above combustion and controls section of furnace, and conditioned air is discharged downwards.

Condensate Trap Location

The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2, 9, or 10.

To relocate condensate trap from the blower shelf to desired location, perform the following:

1.Remove three tubes connected to condensate trap.

2.Remove trap from blower shelf by gently pushing tabs inward and rotaing trap.

3.Remove casing hole filler cap from casing hole. (See Fig. 2 and 10.)

4.Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or death.

Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.

5.Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabls snap into locking position.

6.Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).

COLLECTOR BOX

TUBE (GREEN)

CAP

COLLECTOR BOX

DRAIN TUBE (BLUE)

COLLECTOR BOX

TUBE (PINK)

PLUG

COLLECTOR BOX

DRAIN TUBE (BLUE &

WHITE STRIPED)

COLLECTOR BOX

TUBE EXTENSION

INDUCER HOUSING (MOLDED) DRAIN TUBE (VIOLET)

CONDENSATE

TRAP

COLLECTOR BOX EXTENSION

DRAIN TUBEDRAIN TUBE COUPLING

A07277

Fig. 10 - Factory-Shipped Trap Location (Shown with Blower Access Panel Removed)

Condensate Trap Tubing

NOTE: See Fig. 9 or 10 or tube routing label on main furnace door to check for proper connections.

1.Collector Box DrainTube

a.Remove factory-installed plug from LOWER collector box drain tube (blue and white striped label).

b.Install removed clamp and plug into UPPER collector box drain tube (blue label) which was connected to condensate trap.

c.Connect LOWER collector box drain connection to condensate trap.

(3.) Condensate Trap Located on Left Side of Casing

(a.)Connect LOWER collector box drain tube (blue and white striped label) to condensate trap. Tube does not need to be cut.

(b.)Clamp tube to prevent any condensate leakage. (4.) Condensate Trap Located on Right Side of Casing

(a.)Install drain tube coupling (factory-supplied in loose parts bag) into collector box drain tube (blue and white striped label) which was previously plugged.

(b.)Connect larger diameter drain tube (factory-supplied in loose parts bag) to drain tube coupling, extending collecor box drain tube for connection to condensate trap.

(c.)Route extended collector box drain tube between gas valve and inlet housing as shown in Fig. 10.

(d.)Determine appropriate length and cut. (e.)Connect to condensate trap.

2.Inducer Housing Drain Tube

a.Remove factory-installed cap and clamp from LOWER inducer housing drain connection.

10

Image 10
Contents Installation Instructions Table of ContentsRequired Notice for Massachusetts Installations Safety Considerations CUT HazardDimensions In. / mm Dimensional DrawingInstallation Codes and Standards Applications Electrostatic Discharge ESD PrecautionsIntroduction Upflow ApplicationCarbon Monoxide Poisoning Hazard Condensate Trap Alternate Upflow OrientationCondensate Trap Tubing Alternate Upflow Orientation Condensate Trap Field Drain Attachment Upper Inducer Housing Drain ConnectionCondensate Trap Freeze Protection Downflow Applications Condensate Trap LocationHorizontal Left Tube Configuration Horizontal Left SUPPLY-AIR Discharge ApplicationsProperty Damage Manual Shutoff GAS Valve Sediment Trapcondensate TrapConstruct a Working Platform Horizontal Right SUPPLY-AIR Discharge ApplicationsUnit Operation Hazard Location Condenste Trap Field Drain AttachmentProhibit Installation on Back Fire or Death HazardFIRE, EXPLOSION, Injury or Death Hazard InstallationUnit MAY not Operate Hazard Furnace, Plenum, and Coil Assembly or Coil Box Locations Reqd PER ROD AIR Ducts FIRE, Carbon Monoxide and Poisoning Hazard Fire HazardUnit MAY not Operate Gas Piping Bottom Closure PanelFire or Explosion Hazard Removing Bottom Closure Panel Maximum Capacity of Pipe WiringElectrical Shock Hazard Disconnect Switch and Furnace Electrical Shock and Fire HazardAccessories Factory Installed J-Box LocationFire or Electrical Shock Hazard AIR for Combustion and Ventilation Fire and Explosion HazardDescription AstmMaterial Pipe Fittings CementFurnace Control Direct Vent Termination Clearance Ventilated Combustion Air Vent Termination Clearance Vent Pipe Termination for Ventilated Combustion Air System Combustion AIR Pipe Unit Corrosion HazardAttachment of Combustion Air Intake Housing Plug Fitting Combustion Air Termination Ventilated Combustion Air OptionCarbon Monoxide Poisoning Property Damage Hazard Vent PipeCombustion Air Termination-Direct Vent / 2-Pipe System Attachment of Vent Pipe304.8mm minimum 76.2mm minimum Vent Termination Extended Exposed Sidewall PipesVent Termination Kit Direct Vent/2-Pipe System Only Two-Pipe Termination Kit Direct Vent/2-Pipe System Only042060 Maximum Allowable Pipe Length Ft / M BtuhUnit Size Condensate Drain Personal Injury HazardContinuous Fan CF Setup Switches START-UP, Adjustment and Safety CheckAir Conditioning A/C Setup Switches Additional Setup Switches SW4Example of Setup Switch in Off Position Prime Condensate Trap with WaterWiring Diagram Inducer Housing Drain Tube Furnace Setup Switch DescriptionSequence of Operation Purge Gas LinesTwo-Stage Thermostat and Two-Stage Low / High Heating Thermidistat Mode See -55 for thermostat connectionsContinuous Blower Speed Selection from Thermostat Super Dehumidify ModeContinuous Blower Mode Heat PumpStep-Modulating Furnace with Single-Speed Air Conditioning Pump Furnace and Two-Speed Air Conditioner Furnace and Two-Speed Heat PumpSet Gas Input Rate Redundant Automatic Gas ValveBurner Orifice A07253 A07254 Altitude Derate Multiplier for U.S.A Burner FlameGas Rate cu Ft/Hr Set Temperature RiseSet Thermostat Heat Anticipator Check Pressure Switches ChecklistCheck Safety Controls Check Primary Limit ControlChecklist Installation Combustion and Vent Piping
Related manuals
Manual 14 pages 23.93 Kb Manual 62 pages 7.79 Kb

355CAV specifications

The Bryant 355CAV is a state-of-the-art automated vertical machining center designed to enhance precision and efficiency in the manufacturing sector. Renowned for its robust construction, this machine is engineered to handle a broad spectrum of machining tasks, making it suitable for both small and large-scale production environments.

One of the standout features of the Bryant 355CAV is its advanced CNC control system, which provides users with exceptional ease of use. The intuitive user interface allows operators to program complex machining operations with minimal effort, significantly reducing setup times. The machine's high-speed spindle achieves impressive rotational speeds, which allows for quick material removal, ultimately optimizing productivity and throughput.

The Bryant 355CAV exhibits superior rigidity and stability due to its solid cast iron frame and carefully designed structural components. This construction minimizes vibrations during machining, ensuring that even the most intricate parts are produced with high accuracy. The machine's precision ground linear guideways further enhance its performance by providing smooth motion and high load capacity.

Equipped with a large work envelope, the Bryant 355CAV enables manufacturers to accommodate various part sizes and geometries. Additionally, its automatic tool changers can hold a variety of tools, thus facilitating quick transitions between different machining operations without requiring manual intervention. This flexibility is essential for meeting the diverse needs of modern manufacturing.

Another notable characteristic of the Bryant 355CAV is its energy-efficient design. It integrates modern technologies aimed at reducing power consumption while maintaining optimum performance. This environmentally conscious approach not only cuts operational costs but also aligns with the growing demand for sustainable manufacturing practices.

Moreover, the Bryant 355CAV features advanced monitoring capabilities, allowing operators to track machine performance in real time. Data analytics from these systems can be utilized to improve operational efficiency, reduce downtime, and enhance predictive maintenance protocols.

In summary, the Bryant 355CAV is a versatile, high-performance machining center that showcases cutting-edge features and technologies. Its combination of user-friendly controls, sturdy construction, energy efficiency, and advanced monitoring positions it as a vital asset for manufacturers aiming to elevate their productivity and precision in an increasingly competitive landscape.