Bryant 355CAV installation instructions Vent Termination, Extended Exposed Sidewall Pipes

Page 37

12MIN

12MIN

VENT PIPE

VENT PIPE

COMBUSTION-AIR PIPE

COMBUSTION-AIR PIPE

HORIZONTAL TO ROOF

HORIZONTAL TO SIDEWALL

COMBUSTION-AIR PIPE

VENT PIPE

COMBUSTION-AIR PIPE

 

 

 

 

 

 

 

 

 

12MIN

 

 

 

12MIN

 

 

 

 

 

(304.8mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENT PIPE

 

 

 

 

 

 

 

 

 

(304.8mm)

 

 

 

 

 

 

 

 

 

 

 

 

VERTICAL TO ROOF

 

 

 

 

VERTICAL TO SIDEWALL

NOTE: A 12-in. (304.8mm) minimum offset pipe section is recommended with short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets

A96230

Fig. 44 - Short Vent (5 to 8 Ft or 1.5M - 2.4M) System

355CAV

NOTE: Starting at furnace, slope vent pipe a minimum of 1/4-in. (6.4mm) per linear ft back toward furnace with no sags between hangers.

VENT TERMINATION

General

Combustion-air (direct vent/2-pipe system only) and vent pipe must terminate outside structure, either through sidewall or roof. For vent termination clearance, refer to Fig. 34 for Direct Vent/2- Pipe system and Fig. 35 for Ventilated Combustion Air option.

Roof termination is preferred since it is less susceptible to damage or contamination, and it has less visible vent vapors. Sidewall termination require sealing or shielding of building surfaces with a corrosive resistance material due to corrosive combustion products of vent system.

NOTE: (Direct Vent/2-Pipe system ONLY) A factory accessory termination kit MUST be used. See section “Vent Termination Kit (Direct Vent/2-Pipe System Only)” in this instruction.

When determining appropriate location for termination, consider the following guidelines:

1.Comply with all clearance requirements stated in Fig. 34 or Fig. 35 per application.

2.Termination or termination kit should be positioned where vent vapors will not damage plants/shrubs or air conditioning equipment.

3.Termination or termination kit should be positioned so that it will not be affected by wind eddy, such as inside building corners, nor by recirculation of flue gases, airborne leaves, or light snow.

4.Termination or termination kit should be positioned where it will not be damaged by or subjected to foreign objects such as stones, balls, etc.

5.Termination or termination kit should be positioned where vent vapors are not objectionable.

Extended Exposed Sidewall Pipes

Sidewall combustion air pipe termination (direct vent/2-pipe system only) and vent pipe termination may be extended beyond area shown in Fig. 36 or in Fig. 37 per application in outside ambient by insulating pipe as indicated in Table 6.

1.Determine combustion air pipe diameter (direct vent/2-pipe system only) and vent pipe diameter, as stated above, using total pipe length and number of elbows.

2.Using winter design temperature (used in load calculations), find appropriate temperature for your application and furnace model.

3.Determine required insulation thickness for exposed pipe length(s).

NOTE: Pipe length(ft) specified for maximum pipe lengths located in unconditioned spaces cannot exceed total allowable pipe length as specified in Table 6.

37

Image 37
Contents Table of Contents Installation InstructionsRequired Notice for Massachusetts Installations CUT Hazard Safety ConsiderationsDimensional Drawing Dimensions In. / mmInstallation Codes and Standards Introduction Electrostatic Discharge ESD PrecautionsApplications Upflow ApplicationCarbon Monoxide Poisoning Hazard Condensate Trap Alternate Upflow OrientationCondensate Trap Tubing Alternate Upflow Orientation Condensate Trap Field Drain Attachment Upper Inducer Housing Drain ConnectionCondensate Trap Freeze Protection Condensate Trap Location Downflow ApplicationsHorizontal Left SUPPLY-AIR Discharge Applications Horizontal Left Tube ConfigurationManual Shutoff GAS Valve Sediment Trapcondensate Trap Property DamageConstruct a Working Platform Horizontal Right SUPPLY-AIR Discharge ApplicationsUnit Operation Hazard Condenste Trap Field Drain Attachment LocationFire or Death Hazard Prohibit Installation on BackFIRE, EXPLOSION, Injury or Death Hazard InstallationUnit MAY not Operate Hazard Furnace, Plenum, and Coil Assembly or Coil Box Locations Reqd PER ROD AIR Ducts FIRE, Carbon Monoxide and Poisoning Hazard Fire HazardUnit MAY not Operate Gas Piping Bottom Closure PanelFire or Explosion Hazard Removing Bottom Closure Panel Maximum Capacity of Pipe WiringElectrical Shock Hazard Electrical Shock and Fire Hazard Disconnect Switch and FurnaceAccessories Factory Installed J-Box LocationFire or Electrical Shock Hazard Fire and Explosion Hazard AIR for Combustion and VentilationMaterial Pipe Fittings AstmDescription CementFurnace Control Direct Vent Termination Clearance Ventilated Combustion Air Vent Termination Clearance Vent Pipe Termination for Ventilated Combustion Air System Unit Corrosion Hazard Combustion AIR PipeCombustion Air Termination Ventilated Combustion Air Option Attachment of Combustion Air Intake Housing Plug FittingCombustion Air Termination-Direct Vent / 2-Pipe System Vent PipeCarbon Monoxide Poisoning Property Damage Hazard Attachment of Vent Pipe304.8mm minimum 76.2mm minimum Extended Exposed Sidewall Pipes Vent TerminationTwo-Pipe Termination Kit Direct Vent/2-Pipe System Only Vent Termination Kit Direct Vent/2-Pipe System Only042060 Btuh Maximum Allowable Pipe Length Ft / MUnit Size Personal Injury Hazard Condensate DrainAir Conditioning A/C Setup Switches START-UP, Adjustment and Safety CheckContinuous Fan CF Setup Switches Additional Setup Switches SW4Prime Condensate Trap with Water Example of Setup Switch in Off PositionWiring Diagram Furnace Setup Switch Description Inducer Housing Drain TubePurge Gas Lines Sequence of OperationTwo-Stage Thermostat and Two-Stage Low / High Heating See -55 for thermostat connections Thermidistat ModeContinuous Blower Mode Super Dehumidify ModeContinuous Blower Speed Selection from Thermostat Heat PumpStep-Modulating Furnace with Single-Speed Air Conditioning Furnace and Two-Speed Heat Pump Pump Furnace and Two-Speed Air ConditionerRedundant Automatic Gas Valve Set Gas Input RateBurner Orifice A07253 A07254 Burner Flame Altitude Derate Multiplier for U.S.AGas Rate cu Ft/Hr Set Temperature RiseSet Thermostat Heat Anticipator Check Safety Controls ChecklistCheck Pressure Switches Check Primary Limit ControlCombustion and Vent Piping Checklist Installation
Related manuals
Manual 14 pages 23.93 Kb Manual 62 pages 7.79 Kb

355CAV specifications

The Bryant 355CAV is a state-of-the-art automated vertical machining center designed to enhance precision and efficiency in the manufacturing sector. Renowned for its robust construction, this machine is engineered to handle a broad spectrum of machining tasks, making it suitable for both small and large-scale production environments.

One of the standout features of the Bryant 355CAV is its advanced CNC control system, which provides users with exceptional ease of use. The intuitive user interface allows operators to program complex machining operations with minimal effort, significantly reducing setup times. The machine's high-speed spindle achieves impressive rotational speeds, which allows for quick material removal, ultimately optimizing productivity and throughput.

The Bryant 355CAV exhibits superior rigidity and stability due to its solid cast iron frame and carefully designed structural components. This construction minimizes vibrations during machining, ensuring that even the most intricate parts are produced with high accuracy. The machine's precision ground linear guideways further enhance its performance by providing smooth motion and high load capacity.

Equipped with a large work envelope, the Bryant 355CAV enables manufacturers to accommodate various part sizes and geometries. Additionally, its automatic tool changers can hold a variety of tools, thus facilitating quick transitions between different machining operations without requiring manual intervention. This flexibility is essential for meeting the diverse needs of modern manufacturing.

Another notable characteristic of the Bryant 355CAV is its energy-efficient design. It integrates modern technologies aimed at reducing power consumption while maintaining optimum performance. This environmentally conscious approach not only cuts operational costs but also aligns with the growing demand for sustainable manufacturing practices.

Moreover, the Bryant 355CAV features advanced monitoring capabilities, allowing operators to track machine performance in real time. Data analytics from these systems can be utilized to improve operational efficiency, reduce downtime, and enhance predictive maintenance protocols.

In summary, the Bryant 355CAV is a versatile, high-performance machining center that showcases cutting-edge features and technologies. Its combination of user-friendly controls, sturdy construction, energy efficiency, and advanced monitoring positions it as a vital asset for manufacturers aiming to elevate their productivity and precision in an increasingly competitive landscape.