Bryant 355CAV installation instructions Burner Orifice

Page 54

355CAV

NOTE: DO NOT set medium-heat manifold pressure less than 1.3- in. wc or more than 1.7-in. wc for natural gas.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in reduced furnace life.

DO NOT bottom out gas valve regulator adjusting screws. This can result in unregulated manifold pressure and result in excess overfire and heat exchanger failures.

NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics. (See Fig. 61.)

f. Move setup switch SW4-2 to OFF position after completing medium-heat adjustment.

g.Jumper R and W/W1 and W2 thermostat connections on furnace control. (See Fig. 33.) This keeps furnace locked in high-heat operation.

h.Turn high-heat adjusting screw counterclockwise (out) to decrease manifold pressure or clockwise (in) to increase manifold pressure.

NOTE: DO NOT set high-heat manifold pressure less than 3.2-in. wc or more than 3.8-in. wc for natural gas.

i.Remove jumpers R to W/W1 and R to W2.

j.Wait for blower off-delay to finish then reset 115-v power to furnace.

k.Jumper R and W/W1 thermostat connections on control to start furnace.

l.Wait for the blower to turn ON then check low-heat manifold pressure. It should be between .5 to .6-in. wc. This setting should not require adjustment but if it does remove the low-heat adjustment cap (See Fig. 60) and turn the low-heat adjusting screw clockwise (in) to decrease manifold pressure or counterclockwise (out) to increase manifold pressure. You will only have 15 minutes to make an adjustment if needed. If you need more time then move setup switch SW1-2 on control center to ON position (See Fig. 33).

NOTE: DO NOT set low-heat manifold pressure before setting medium-heat manifold pressure. DO NOT set low-heat manifold pressure less than .5-in. wc or more than .6-in. wc for natural gas.

m. When correct manifold pressures are obtained, replace caps that conceal gas valve adjustment screws. Main burner flame should be clear blue, almost transparent. (See Fig. 62.)

n.Remove jumper across R and W/W1. If necessary move setup switch SW1-2 to the OFF position.

3.Verify natural gas input rate by clocking gas meter.

NOTE: Be sure all pressure tubing, combustion-air and vent pipes, and burner enclosure front are in place when checking input by clocking gas meter.

a.Calculate high-altitude adjustment (if required).

UNITED STATES

At altitudes above 2000 ft, this furnace has been approved for 2 percent derate for each 1000 ft above sea level. See Table 11 for derate multiplier factor and example.

CANADA

At installation altitudes from 2000 to 4500 ft, this furnace must be derated 5 percent by an authorized Gas Conversion Station or Dealer. To determine correct input rate for altitude, see example and use 0.95 as derate multiplier factor.

EXAMPLE: 80,000 BTUH HIGH-HEAT INPUT FURNACE INSTALLED AT 4,300 FT

Furnace Input Rate at Sea Level X Derate Multiplier Factor = Furnace Input Rate at Installation Altitude 80,000 X 0.91 = 72,800

b.Reinstall burner box cover.

NOTE: Clocking gas input rate MUST always be performed with the burner box cover INSTALLED.

c. Check that gas valve adjustment caps are in place for proper input to be clocked.

d. Obtain average heat value (at altitude) from local gas supplier.

NOTE: Be sure heating value of gas used for calculations is correct for your altitude. Consult local gas utility for altitude adjustment of gas heating value.

e. Check and verify orifice size in furnace. NEVER ASSUME THE ORIFICE SIZE. ALWAYS CHECK AND VERIFY.

f.Turn off all other gas appliances and pilots.

g.Move setup switch SW4-2 to ON position. (See Fig. 33.) This keeps furnace locked in medium-heat operation.

BURNER

ORIFICE

A93059

Fig. 61 - Burner Orifice

54

Image 54
Contents Installation Instructions Table of ContentsRequired Notice for Massachusetts Installations Safety Considerations CUT HazardDimensions In. / mm Dimensional DrawingInstallation Codes and Standards Applications Electrostatic Discharge ESD PrecautionsIntroduction Upflow ApplicationCondensate Trap Alternate Upflow Orientation Carbon Monoxide Poisoning HazardCondensate Trap Tubing Alternate Upflow Orientation Upper Inducer Housing Drain Connection Condensate Trap Field Drain AttachmentCondensate Trap Freeze Protection Downflow Applications Condensate Trap LocationHorizontal Left Tube Configuration Horizontal Left SUPPLY-AIR Discharge ApplicationsProperty Damage Manual Shutoff GAS Valve Sediment Trapcondensate TrapHorizontal Right SUPPLY-AIR Discharge Applications Construct a Working PlatformUnit Operation Hazard Location Condenste Trap Field Drain AttachmentProhibit Installation on Back Fire or Death HazardInstallation FIRE, EXPLOSION, Injury or Death HazardUnit MAY not Operate Hazard Furnace, Plenum, and Coil Assembly or Coil Box Locations Reqd PER ROD AIR Ducts Fire Hazard FIRE, Carbon Monoxide and Poisoning HazardUnit MAY not Operate Bottom Closure Panel Gas PipingFire or Explosion Hazard Removing Bottom Closure Panel Wiring Maximum Capacity of PipeElectrical Shock Hazard Disconnect Switch and Furnace Electrical Shock and Fire HazardFactory Installed J-Box Location AccessoriesFire or Electrical Shock Hazard AIR for Combustion and Ventilation Fire and Explosion HazardDescription AstmMaterial Pipe Fittings CementFurnace Control Direct Vent Termination Clearance Ventilated Combustion Air Vent Termination Clearance Vent Pipe Termination for Ventilated Combustion Air System Combustion AIR Pipe Unit Corrosion HazardAttachment of Combustion Air Intake Housing Plug Fitting Combustion Air Termination Ventilated Combustion Air OptionCarbon Monoxide Poisoning Property Damage Hazard Vent PipeCombustion Air Termination-Direct Vent / 2-Pipe System Attachment of Vent Pipe304.8mm minimum 76.2mm minimum Vent Termination Extended Exposed Sidewall PipesVent Termination Kit Direct Vent/2-Pipe System Only Two-Pipe Termination Kit Direct Vent/2-Pipe System Only042060 Maximum Allowable Pipe Length Ft / M BtuhUnit Size Condensate Drain Personal Injury HazardContinuous Fan CF Setup Switches START-UP, Adjustment and Safety CheckAir Conditioning A/C Setup Switches Additional Setup Switches SW4Example of Setup Switch in Off Position Prime Condensate Trap with WaterWiring Diagram Inducer Housing Drain Tube Furnace Setup Switch DescriptionSequence of Operation Purge Gas LinesTwo-Stage Thermostat and Two-Stage Low / High Heating Thermidistat Mode See -55 for thermostat connectionsContinuous Blower Speed Selection from Thermostat Super Dehumidify ModeContinuous Blower Mode Heat PumpStep-Modulating Furnace with Single-Speed Air Conditioning Pump Furnace and Two-Speed Air Conditioner Furnace and Two-Speed Heat PumpSet Gas Input Rate Redundant Automatic Gas ValveBurner Orifice A07253 A07254 Altitude Derate Multiplier for U.S.A Burner FlameSet Temperature Rise Gas Rate cu Ft/HrSet Thermostat Heat Anticipator Check Pressure Switches ChecklistCheck Safety Controls Check Primary Limit ControlChecklist Installation Combustion and Vent Piping
Related manuals
Manual 14 pages 23.93 Kb Manual 62 pages 7.79 Kb

355CAV specifications

The Bryant 355CAV is a state-of-the-art automated vertical machining center designed to enhance precision and efficiency in the manufacturing sector. Renowned for its robust construction, this machine is engineered to handle a broad spectrum of machining tasks, making it suitable for both small and large-scale production environments.

One of the standout features of the Bryant 355CAV is its advanced CNC control system, which provides users with exceptional ease of use. The intuitive user interface allows operators to program complex machining operations with minimal effort, significantly reducing setup times. The machine's high-speed spindle achieves impressive rotational speeds, which allows for quick material removal, ultimately optimizing productivity and throughput.

The Bryant 355CAV exhibits superior rigidity and stability due to its solid cast iron frame and carefully designed structural components. This construction minimizes vibrations during machining, ensuring that even the most intricate parts are produced with high accuracy. The machine's precision ground linear guideways further enhance its performance by providing smooth motion and high load capacity.

Equipped with a large work envelope, the Bryant 355CAV enables manufacturers to accommodate various part sizes and geometries. Additionally, its automatic tool changers can hold a variety of tools, thus facilitating quick transitions between different machining operations without requiring manual intervention. This flexibility is essential for meeting the diverse needs of modern manufacturing.

Another notable characteristic of the Bryant 355CAV is its energy-efficient design. It integrates modern technologies aimed at reducing power consumption while maintaining optimum performance. This environmentally conscious approach not only cuts operational costs but also aligns with the growing demand for sustainable manufacturing practices.

Moreover, the Bryant 355CAV features advanced monitoring capabilities, allowing operators to track machine performance in real time. Data analytics from these systems can be utilized to improve operational efficiency, reduce downtime, and enhance predictive maintenance protocols.

In summary, the Bryant 355CAV is a versatile, high-performance machining center that showcases cutting-edge features and technologies. Its combination of user-friendly controls, sturdy construction, energy efficiency, and advanced monitoring positions it as a vital asset for manufacturers aiming to elevate their productivity and precision in an increasingly competitive landscape.