Bryant 355CAV Condensate Trap Field Drain Attachment, Upper Inducer Housing Drain Connection

Page 9

PLUG

COLLECTOR BOX

DRAIN TUBE (BLUE &

WHITE STRIPED)

CAP

COLLECTOR BOX

TUBE (PINK)

INDUCER HOUSING (MOLDED) DRAIN TUBE (BEHIND COLLECTOR BOX DRAIN TUBE)

COLLECTOR BOX

DRAIN TUBE (BLUE)

COLLECTOR BOX

TUBE (GREEN

ROUTES BEHIND

INDUCER)

CONDENSATE

TRAP

FIELD-INSTALLED

FACTORY-SUPPLIED

DRAIN TUBE

COUPLING (LEFT

DRAIN OPTION)

FIELD-INSTALLED

 

FACTORY-SUPPLIED

 

DRAIN TUBE

FIELD- INSTALLED

FIELD-INSTALLED

FACTORY-SUPPLIED

FACTORY-SUPPLIED

DRAIN TUBE

½ - IN. CPVC STREET

COUPLING (LEFT

ELBOWS (2) FOR

DRAIN OPTION)

LEFT DRAIN OPTION

 

A07274

Fig. 7 - Factory-Shipped Trap Location (Shown with Blower Access Panel Removed)

1.Collector Box Drain Tube

Connect collector box drain tube (blue label) to condensate trap.

NOTE: On 17-1/2-in. (444.5mm) wide furnaces ONLY, cut tube between corrugated sections to prevent kinks.

2.Inducer Housing Drain Tube

a.Remove and discard LOWER (molded) inducer housing drain tube which was previously connected to condensate trap.

b.Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to condensate trap.

c.Determine appropriate length, then cut and connect tube.

d.Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

a.Connect relief port tube (green label) to condensate trap.

b.Extend this tube (if required) by splicing to small diameter tube (factory-supplied in loose parts bag).

c.Determine appropriate length, then cut and connect tube.

Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and procedures.

PLUG

COLLECTOR BOX

DRAIN TUBE (BLUE &

WHITE STRIPED)

CAP

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

 

DRAIN TUBE (BLUE)

355CAV

CONDENSATE

COLLECTOR BOX

 

TUBE (GREEN)

 

TRAP

 

INDUCER HOUSING

 

(MOLDED) DRAIN

 

TUBE (VIOLET)

 

A07281

Fig. 8 - Alternate Trap Location

Pressure Switch Tubing

The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch and should not require any modification.

NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.

Upper Collector Box and Inducer Housing (Unused) Drain

Connections

Upper Collector Box Drain Connection

Attached to the UPPER collector box drain connection is a factory-installed corrugated, plugged tube (blue and white striped label). This tube is plugged to prevent condensate leakage in this application. Ensure this tube is plugged.

NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.

Upper Inducer Housing Drain Connection

Attached to the UPPER (unused) inducer housing drain connection is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped.

NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.

Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommendations and procedures.

9

Image 9
Contents Table of Contents Installation InstructionsRequired Notice for Massachusetts Installations CUT Hazard Safety ConsiderationsDimensional Drawing Dimensions In. / mmInstallation Codes and Standards Introduction Electrostatic Discharge ESD PrecautionsApplications Upflow ApplicationCondensate Trap Alternate Upflow Orientation Carbon Monoxide Poisoning HazardCondensate Trap Tubing Alternate Upflow Orientation Upper Inducer Housing Drain Connection Condensate Trap Field Drain AttachmentCondensate Trap Freeze Protection Condensate Trap Location Downflow ApplicationsHorizontal Left SUPPLY-AIR Discharge Applications Horizontal Left Tube ConfigurationManual Shutoff GAS Valve Sediment Trapcondensate Trap Property DamageHorizontal Right SUPPLY-AIR Discharge Applications Construct a Working PlatformUnit Operation Hazard Condenste Trap Field Drain Attachment LocationFire or Death Hazard Prohibit Installation on BackInstallation FIRE, EXPLOSION, Injury or Death HazardUnit MAY not Operate Hazard Furnace, Plenum, and Coil Assembly or Coil Box Locations Reqd PER ROD AIR Ducts Fire Hazard FIRE, Carbon Monoxide and Poisoning HazardUnit MAY not Operate Bottom Closure Panel Gas PipingFire or Explosion Hazard Removing Bottom Closure Panel Wiring Maximum Capacity of PipeElectrical Shock Hazard Electrical Shock and Fire Hazard Disconnect Switch and FurnaceFactory Installed J-Box Location AccessoriesFire or Electrical Shock Hazard Fire and Explosion Hazard AIR for Combustion and VentilationMaterial Pipe Fittings AstmDescription CementFurnace Control Direct Vent Termination Clearance Ventilated Combustion Air Vent Termination Clearance Vent Pipe Termination for Ventilated Combustion Air System Unit Corrosion Hazard Combustion AIR PipeCombustion Air Termination Ventilated Combustion Air Option Attachment of Combustion Air Intake Housing Plug FittingCombustion Air Termination-Direct Vent / 2-Pipe System Vent PipeCarbon Monoxide Poisoning Property Damage Hazard Attachment of Vent Pipe304.8mm minimum 76.2mm minimum Extended Exposed Sidewall Pipes Vent TerminationTwo-Pipe Termination Kit Direct Vent/2-Pipe System Only Vent Termination Kit Direct Vent/2-Pipe System Only042060 Btuh Maximum Allowable Pipe Length Ft / MUnit Size Personal Injury Hazard Condensate DrainAir Conditioning A/C Setup Switches START-UP, Adjustment and Safety CheckContinuous Fan CF Setup Switches Additional Setup Switches SW4Prime Condensate Trap with Water Example of Setup Switch in Off PositionWiring Diagram Furnace Setup Switch Description Inducer Housing Drain TubePurge Gas Lines Sequence of OperationTwo-Stage Thermostat and Two-Stage Low / High Heating See -55 for thermostat connections Thermidistat ModeContinuous Blower Mode Super Dehumidify ModeContinuous Blower Speed Selection from Thermostat Heat PumpStep-Modulating Furnace with Single-Speed Air Conditioning Furnace and Two-Speed Heat Pump Pump Furnace and Two-Speed Air ConditionerRedundant Automatic Gas Valve Set Gas Input RateBurner Orifice A07253 A07254 Burner Flame Altitude Derate Multiplier for U.S.ASet Temperature Rise Gas Rate cu Ft/HrSet Thermostat Heat Anticipator Check Safety Controls ChecklistCheck Pressure Switches Check Primary Limit ControlCombustion and Vent Piping Checklist Installation
Related manuals
Manual 14 pages 23.93 Kb Manual 62 pages 7.79 Kb

355CAV specifications

The Bryant 355CAV is a state-of-the-art automated vertical machining center designed to enhance precision and efficiency in the manufacturing sector. Renowned for its robust construction, this machine is engineered to handle a broad spectrum of machining tasks, making it suitable for both small and large-scale production environments.

One of the standout features of the Bryant 355CAV is its advanced CNC control system, which provides users with exceptional ease of use. The intuitive user interface allows operators to program complex machining operations with minimal effort, significantly reducing setup times. The machine's high-speed spindle achieves impressive rotational speeds, which allows for quick material removal, ultimately optimizing productivity and throughput.

The Bryant 355CAV exhibits superior rigidity and stability due to its solid cast iron frame and carefully designed structural components. This construction minimizes vibrations during machining, ensuring that even the most intricate parts are produced with high accuracy. The machine's precision ground linear guideways further enhance its performance by providing smooth motion and high load capacity.

Equipped with a large work envelope, the Bryant 355CAV enables manufacturers to accommodate various part sizes and geometries. Additionally, its automatic tool changers can hold a variety of tools, thus facilitating quick transitions between different machining operations without requiring manual intervention. This flexibility is essential for meeting the diverse needs of modern manufacturing.

Another notable characteristic of the Bryant 355CAV is its energy-efficient design. It integrates modern technologies aimed at reducing power consumption while maintaining optimum performance. This environmentally conscious approach not only cuts operational costs but also aligns with the growing demand for sustainable manufacturing practices.

Moreover, the Bryant 355CAV features advanced monitoring capabilities, allowing operators to track machine performance in real time. Data analytics from these systems can be utilized to improve operational efficiency, reduce downtime, and enhance predictive maintenance protocols.

In summary, the Bryant 355CAV is a versatile, high-performance machining center that showcases cutting-edge features and technologies. Its combination of user-friendly controls, sturdy construction, energy efficiency, and advanced monitoring positions it as a vital asset for manufacturers aiming to elevate their productivity and precision in an increasingly competitive landscape.