Bryant 355CAV installation instructions Maximum Capacity of Pipe, Electrical Shock Hazard, Wiring

Page 23

Table 3 – Maximum Capacity of Pipe*

NOMINAL

INTERNAL

 

LENGTH OF PIPE (FT/M)

 

IRON

 

 

 

 

 

 

 

PIPE

DIAMETER

 

 

 

 

 

10/

20/

30/

40/

50/

SIZE

(IN.)

3.0

6.1

9.1

12.2

15.2

(IN.)

 

 

 

 

 

 

 

1/2

0.622

175

120

97

82

73

3/4

0.824

360

250

200

170

151

1

1.049

680

465

375

320

285

1---1/4

1.380

1400

950

770

660

580

1---1/2

1.610

2100

1460

1180

990

900

*Cubic ft of gas per hr for gas pressure of 0.5 psig (14--- in. wc) or less, and a pressure drop of 0.5--- in. wc (based on a 0.60 specific gravity gas). Ref: Table 9--- 2 NFPA 54--- 2002.

NOTE: The gas valve inlet pressure tap connection is suitable to use as test gauge connection providing test pressure DOES NOT exceed maximum 0.5 psig (14-in. wc) stated on gas valve. (See Fig. 60.)

Piping should be pressure and leak tested in accordance with NFGC in the United States or CAN/CSA-B149.1-05 in Canada, local, and national plumbing and gas codes before the furnace has been connected. If pressure exceeds 0.5 psig (14-in. wc), gas supply pipe must be disconnected from furnace and capped before pressure test.

If test pressure is equal to or less than 0.5 psig (14-in. wc), turn off electric shutoff switch located on gas valve before test. It is recommended that ground joint union be loosened before pressure testing. After all connections have been made, purge lines and check for leakage at furnace prior to placing it into service.

The gas supply pressure shall be within the maximum (13.6-in. wc) and minimum (4.5-in.wc) inlet supply pressures marked on the rating plate with the furnace burners ON at HI-HEAT and OFF.

Electrical Connections

See Fig. 29 for field wiring diagram showing typical field 115-v and 24-v wiring. Check all factory and field electrical connections for tightness.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Blower access door switch opens 115-v power to furnace control. No component operation can occur. Do not bypass or close switch with panel removed.

!WARNING

UNIT MAY NOT OPERATE

Failure to follow this caution may result in intermittent unit operation.

Furnace control must be grounded for proper operation or control will lock out. Control is grounded through green/yellow wire connected to gas valve and burner box screw.

115-v Wiring

Before proceeding with electrical connections, make certain that voltage, frequency, and phase correspond to that specified on furnace rating plate. Also, check to be sure that service provided by power supply is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 4 for equipment electrical specifications.

Make all electrical connections in accordance with National Electrical Code (NEC) ANSI/NFPA 70-2005 and any local codes or ordinances that might apply. For Canadian installations, all electrical connections must be made in accordance with Canadian Electrical Code CSA C22.1 or authorities having jurisdiction.

Field-supplied wiring shall conform with the limitations of 63_F (33_C) rise.

The furnace must be electrically grounded in accordance with local codes; or in the absence of local codes, with the National Electric Code ANSI/NFPA 70 and/or the Canadian Electric Code, CSA C22.1, Part I, if an external electrical source is utilized.

Use a separate branch electrical circuit containing a properly sized fuse or circuit breaker for this furnace. See Table 4 for wire size and fuse specifications. A disconnecting means must be located within sight from and readily accessible to furnace.

NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect or furnace is not grounded properly, furnace control status code indicator light will flash rapidly and furnace will NOT operate.

!WARNING

FIRE HAZARD

Failure to follow this warning could result in personal injury, death, or property damage.

Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. (See Fig. 30.)

355CAV

23

Image 23
Contents Table of Contents Installation InstructionsRequired Notice for Massachusetts Installations CUT Hazard Safety ConsiderationsDimensional Drawing Dimensions In. / mmInstallation Codes and Standards Upflow Application Electrostatic Discharge ESD PrecautionsIntroduction ApplicationsCondensate Trap Tubing Alternate Upflow Orientation Condensate Trap Alternate Upflow OrientationCarbon Monoxide Poisoning Hazard Condensate Trap Freeze Protection Upper Inducer Housing Drain ConnectionCondensate Trap Field Drain Attachment Condensate Trap Location Downflow ApplicationsHorizontal Left SUPPLY-AIR Discharge Applications Horizontal Left Tube ConfigurationManual Shutoff GAS Valve Sediment Trapcondensate Trap Property DamageUnit Operation Hazard Horizontal Right SUPPLY-AIR Discharge ApplicationsConstruct a Working Platform Condenste Trap Field Drain Attachment LocationFire or Death Hazard Prohibit Installation on BackUnit MAY not Operate Hazard InstallationFIRE, EXPLOSION, Injury or Death Hazard Furnace, Plenum, and Coil Assembly or Coil Box Locations Reqd PER ROD AIR Ducts Unit MAY not Operate Fire HazardFIRE, Carbon Monoxide and Poisoning Hazard Fire or Explosion Hazard Bottom Closure PanelGas Piping Removing Bottom Closure Panel Electrical Shock Hazard WiringMaximum Capacity of Pipe Electrical Shock and Fire Hazard Disconnect Switch and FurnaceFire or Electrical Shock Hazard Factory Installed J-Box LocationAccessories Fire and Explosion Hazard AIR for Combustion and VentilationCement AstmMaterial Pipe Fittings DescriptionFurnace Control Direct Vent Termination Clearance Ventilated Combustion Air Vent Termination Clearance Vent Pipe Termination for Ventilated Combustion Air System Unit Corrosion Hazard Combustion AIR PipeCombustion Air Termination Ventilated Combustion Air Option Attachment of Combustion Air Intake Housing Plug FittingAttachment of Vent Pipe Vent PipeCombustion Air Termination-Direct Vent / 2-Pipe System Carbon Monoxide Poisoning Property Damage Hazard304.8mm minimum 76.2mm minimum Extended Exposed Sidewall Pipes Vent TerminationTwo-Pipe Termination Kit Direct Vent/2-Pipe System Only Vent Termination Kit Direct Vent/2-Pipe System Only042060 Btuh Maximum Allowable Pipe Length Ft / MUnit Size Personal Injury Hazard Condensate DrainAdditional Setup Switches SW4 START-UP, Adjustment and Safety CheckAir Conditioning A/C Setup Switches Continuous Fan CF Setup SwitchesPrime Condensate Trap with Water Example of Setup Switch in Off PositionWiring Diagram Furnace Setup Switch Description Inducer Housing Drain TubePurge Gas Lines Sequence of OperationTwo-Stage Thermostat and Two-Stage Low / High Heating See -55 for thermostat connections Thermidistat ModeHeat Pump Super Dehumidify ModeContinuous Blower Mode Continuous Blower Speed Selection from ThermostatStep-Modulating Furnace with Single-Speed Air Conditioning Furnace and Two-Speed Heat Pump Pump Furnace and Two-Speed Air ConditionerRedundant Automatic Gas Valve Set Gas Input RateBurner Orifice A07253 A07254 Burner Flame Altitude Derate Multiplier for U.S.ASet Thermostat Heat Anticipator Set Temperature RiseGas Rate cu Ft/Hr Check Primary Limit Control ChecklistCheck Safety Controls Check Pressure SwitchesCombustion and Vent Piping Checklist Installation
Related manuals
Manual 14 pages 23.93 Kb Manual 62 pages 7.79 Kb

355CAV specifications

The Bryant 355CAV is a state-of-the-art automated vertical machining center designed to enhance precision and efficiency in the manufacturing sector. Renowned for its robust construction, this machine is engineered to handle a broad spectrum of machining tasks, making it suitable for both small and large-scale production environments.

One of the standout features of the Bryant 355CAV is its advanced CNC control system, which provides users with exceptional ease of use. The intuitive user interface allows operators to program complex machining operations with minimal effort, significantly reducing setup times. The machine's high-speed spindle achieves impressive rotational speeds, which allows for quick material removal, ultimately optimizing productivity and throughput.

The Bryant 355CAV exhibits superior rigidity and stability due to its solid cast iron frame and carefully designed structural components. This construction minimizes vibrations during machining, ensuring that even the most intricate parts are produced with high accuracy. The machine's precision ground linear guideways further enhance its performance by providing smooth motion and high load capacity.

Equipped with a large work envelope, the Bryant 355CAV enables manufacturers to accommodate various part sizes and geometries. Additionally, its automatic tool changers can hold a variety of tools, thus facilitating quick transitions between different machining operations without requiring manual intervention. This flexibility is essential for meeting the diverse needs of modern manufacturing.

Another notable characteristic of the Bryant 355CAV is its energy-efficient design. It integrates modern technologies aimed at reducing power consumption while maintaining optimum performance. This environmentally conscious approach not only cuts operational costs but also aligns with the growing demand for sustainable manufacturing practices.

Moreover, the Bryant 355CAV features advanced monitoring capabilities, allowing operators to track machine performance in real time. Data analytics from these systems can be utilized to improve operational efficiency, reduce downtime, and enhance predictive maintenance protocols.

In summary, the Bryant 355CAV is a versatile, high-performance machining center that showcases cutting-edge features and technologies. Its combination of user-friendly controls, sturdy construction, energy efficiency, and advanced monitoring positions it as a vital asset for manufacturers aiming to elevate their productivity and precision in an increasingly competitive landscape.